Trane TSH 060 Resetting Cooling and Ignition Lockouts, Clogged Filter Switch, Fan Failure Switch

Page 64

Maintenance

Service Failure

Measure the voltage between terminals J6-10 & J6-6.

Clogged Filter = Approximately 32 VDC.

Normal = Less than 1 VDC, approximately 0.75 VDC

Fan Failure = voltage alternates between 32 VDC & 0.75 VDC.

To use LED's for quick status information at the unit, purchase a ZSM and connect wires with alligator clamps to terminals 6 through 10.

Connect each respective terminal wire (6 through 10) from the Zone Sensor to the unit J6 terminals 6 through 10.

Note: If the system is equipped with a programmable zone sensor THS03, the LED indicators will not function while the ZSM is connected.

Resetting Cooling and Ignition Lockouts

Cooling Failures and Ignition

Lockouts are reset in an identical manner. Method 1 explains resetting the system from the space, Method 2 explains resetting the system at the unit.

Note: Before resetting Cooling Failures and Ignition Lockouts, check the Failure Status Diagnostics by the methods previously explained.

Diagnostics will be lost when the power to the unit is disconnected.

Method 1

To reset the system from the zone, turn the "Mode" selection switch at the zone sensor to the "Off" position.

After approximately 30 seconds, turn the "Mode" selection switch to the desired mode, i.e. Heat, Cool or Auto.

Method 2

To reset the system at the unit, cycle the unit power by turning the disconnect switch "Off" and then "On".

Lockouts can be cleared through the building management system. Refer to the building management system instructions for more information.

Zone Temperature Sensor (ZTS) Service Indicator

The ZSM SERVICE LED is a generic indicator that will signal the closing of a Normally Open switch at any time, providing the Indoor Motor (IDM) is operating. This indicator is usually used to indicate a clogged filter, or an air side fan failure.

The RTRM will ignore the closing of this Normally Open switch for 2 (±1) minutes. This helps prevent nuisance SERVICE LED indications. The exception is the LED will flash 40 seconds after the fan is turned "On" if the Fan Proving Switch is not made.

Clogged Filter Switch

This LED will remain lit the entire time that the Normally Open switch is closed. The LED will be turned off immediately after resetting the switch (to the Normally Open position), or any time that the IDM is turned "Off".

If the switch remains closed, and the IDM is turned "On", the SERVICE LED will be turned "On" again after the 2 (±1) minute ignore delay.

This LED being turned "On", will have no other affect on unit operation. It is an indicator only.

Fan Failure Switch

When the "Fan Failure" switch is wired to the RTOM, the LED will remain flashing the entire time the fan proving switch is closed, indicating a fan failure, and it will shut the unit operations down.

64

RT-SVX20A-E4

Image 64
Contents Installation Operation Maintenance General information ForewordWarranty Maintenance contractReception RefrigerantContents Unit Options Roof curb Installation TSD-WSD-YSD accessories Roof curb accessoryReception of units Rooftop unitUnit weights and center of gravity Dimensions/Weights/ ClearancesMinimum recommended clearances Factory-installed options and accessories net weights kg Motorized ManualElectric Hot water Unit size Motor HeatersDischarge Conversion Installing the unitUnit mounting on roof Installing the unit on the ground Downflow discharge units TSD,WSD,YSD Using the rooftop curbConnection of duct network Horizontal discharge units TSH,WSH,YSHDuct dimensions for downflow units mm Duct dimensions for horizontal unitsCondensate drain piping Gas pipework installation Gas leak check procedureGas burner models UnitFilter installation Supply fan adjustmentFilter arrangement Unit EU2/G2 EU4/G4 Quantity SizeTo adjust belt To increase airflowTo decrease airflow Motor sheave / Fan speedPressure drop through accessories Component air pressure dropsUnit Airflow Filter 100%TSD 060 Available static pressure Supply fan performancesTSH 060 Available static pressure TSD 072 Available static pressure TSH 072 Available static pressureTSD 090 Available static pressure TSH 090 Available static pressureTSD 102 Available static pressure TSH 102 Available static pressureTSD 120 Available static pressure TSH 120 Available static pressureYSD 060 Available static pressure YSH 060 Available static pressureYSD 072 Available static pressure YSH 072 Available static pressureYSH 090 Available static pressure YSD 090 Available static pressureStandard drive Oversize drive YSD 102 Available static pressure YSH 102 Available static pressureYSD 120 Available static pressure YSH 120 Available static pressureWSD 060 Available static pressure WSH 060 Available static pressureWSD 072 Available static pressure WSH 072 Available static pressureWSD 090 Available static pressure WSH 090 Available static pressureFactory supplied disconnect switch option Power wiringElectrical connection Over current protectionUnit wiring Ampacity SizePh/Hz Without Electric heat option With Electric heatCompressor and condenser motors Supply fan motorControl wiring Unit controlled by thermostatZone sensor wire and maximum length Unit controlled by BASUnit controlled by Tracker supervisor MaximumSpecifications CO2 sensor wire sizeCO2 sensors Wiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorJumper settings Mounting the wall-mounted sensorCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatHigh temperature safety thermostat Remote fault relayClogged filter detector Smoke detectorThermostat features ThermostatsOther accessories available Communication InterfacesRefer to separate documentation for more information Trane Communication Interface TCI-R boardDown flow units only Hot water coilEthylene glycol percentage Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodEconomizer flow chart with barometric relief Barometric reliefOperation with a conventional thermostat Terminal stripThermostat signals are as follows Input / connection Function when energized Cooling modeHeating mode Heat pump onlySetting the economizer or 0-50% motorized hood option Unoccupied modeCooling/Economizer Operation Cooling/Economizer Operation with ThermostatMinimum fresh air adjustment ECA board LEDTest procedures Operating checklist before start-upPower-up initialization Test mode procedure at the ReliaTel control boardAuto Test Mode Step Test ModeTest modes Gas type designation per country Unit start-upGas burner data Starting the unit in cooling mode Final installation checklistCheck torque of power cables contact Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerPotentiometer Setting Economizer Set-UpReliaTel Control Heating Operation Ignition ModuleFinal installation checklist LED statusAir filters End user routine maintenanceRefrigerant charge Condenser coil Service technician maintenanceHot water coil option Troubleshooting System Status Checkout ProcedureService Failure System failureHeating Failure Cooling FailureResetting Cooling and Ignition Lockouts Zone Temperature Sensor ZTS Service IndicatorClogged Filter Switch Fan Failure SwitchThermistor Resistance / Temperature Chart ResistanceTo Test Humidity Sensors Return Air Humidity Sensor Outdoor Humidity SensorHumidity sensor test DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.