Operation

Unit start-up

Verification of gas valve settings - (Reserved for the qualified gas technician)

WARNING! Improper gas valve setting may lead to burner destruction and people injury.

Note: Unit factory-set for G20.

Figure 32 - Gas valve

G20 - 7.5mbar

G25 -10.5mbar

 

Note: Unit to be installed outside

 

only.

 

Note: Expansion valve must be

 

adapted to the type of gas used:

1 3/32"

• G 20: 20 mb

 

• G 25: 25 mb

 

• G 31 (Propane): 37 or 50 mb

1 = Screw to set gas valve

Table 50 - Gas type designation per country

Destination countries

Pressure in mbar

Category

FR

20/25 37

II2E+3P

DE-LU-PL

20

I2E

CH-ES-GB-IE-PT-CZ-GR

20

37

II2H3P

NL

25

30

II2L3P

IT-AT-NO-FI-SE-EE-LT-LV

20

I2H

IT

28-30/37

I3+

BE

20/25

I2E

DK-SK-SI-TR

20

I2H

BE-PL

37

I3P

AT-DE-LU-HU-SK

50

I3P

HU

25

I2H

Table 51 - Gas burner data

Burner

 

G120

 

 

G200

 

 

G250

 

Gas Type

G20

G25

G31

G20

G25

G31

G20

G25

G31

 

 

 

 

 

 

 

 

 

 

Heating Input (kW)

0,0

0,0

0,0

0,0

0,0

0,0

0,0

0,0

0,0

 

 

 

 

 

 

 

 

 

 

Heating Output (kW)

24,6

25

25,1

41,3

41,7

41,9

51,9

52,3

52,6

 

 

 

 

 

 

 

 

 

 

Efficiency

93%

93%

93%

93%

93%

93%

#DIV/0!

#DIV/0!

93%

 

 

 

 

 

 

 

 

 

 

Gas Flow rate (Nm3/h)

2,8

3,3

2,1

4,7

5,5

3,5

5,9

6,9

4,4

 

 

 

 

 

 

 

 

 

 

Specific Heating Capacity (MJ/kg)

34,02

29,3

46,34

34,02

29,3

46,34

34,02

29,3

46,34

 

 

 

 

 

 

 

 

 

 

Heating Output per stage (1st/2nd) (%)

 

0%-100%

 

 

0%-70%-100%

 

 

0%-70%-100%

 

 

 

 

 

 

 

 

 

 

 

Inlet pressure Min/Nominal/Max (mbar)

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

17 / 20 / 25

20 / 25 / 30

25 / 37 / 45

 

 

 

 

 

 

 

 

 

 

Low pressure switch setting (mbar)

15

15

20

15

15

20

15

15

20

 

 

 

 

 

 

 

 

 

 

Manifold pressure (mbar)

7,5

10,5

24,9

7,5

10,5

24,9

7,5

10,5

24,9

 

 

 

 

 

 

 

 

 

 

No of injectors

 

3

 

 

4

 

 

5

 

 

 

 

 

 

 

 

Injector size (Drill / mm)

(33) / 2.87mm

(51) / 1.70mm

(1/8") / 3.175mm

(49) / 1.85mm

(1/8") / 3.175mm

(49) / 1.85mm

 

 

 

 

 

 

 

 

 

 

Smoke analysis

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas / Voltage

G20 - 20mbar

G25 - 25mbar

G31 - 37mbar

G20 - 20mbar

G25 - 25mbar

G31 - 37mbar

G20 - 20mbar

G25 - 25mbar

G31 - 37mbar

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

400/3/50

 

 

 

 

 

 

 

 

 

 

 

CO %

0.0012%

0.0017%

0.0003%

0.0020%

0.0015%

0.0011%

0.0020%

0.0015%

0.0011%

 

 

 

 

 

 

 

 

 

 

Nox ppm

59 ppm

44 ppm

8.7 ppm

10 ppm

10 ppm

11 ppm

10 ppm

10 ppm

11 ppm

 

 

 

 

 

 

 

 

 

 

CO2 %

8,29%

9,20%

8,90%

7,10%

7,10%

8,28%

7,10%

7,10%

8,28%

 

 

 

 

 

 

 

 

 

 

Notes:

(1)G20 heating output given for 34,02 MJ/m3 (15°C-1013)

(2)G25 heating output given for 29,30 MJ/m3 (15°C-1013)

(3)G31 heating output given for 46.34 MJ/kg

54

RT-SVX20A-E4

Image 54
Contents Installation Operation Maintenance General information ForewordReception WarrantyMaintenance contract RefrigerantContents Unit Options Reception of units Roof curb Installation TSD-WSD-YSD accessoriesRoof curb accessory Rooftop unitDimensions/Weights/ Clearances Unit weights and center of gravityMinimum recommended clearances Electric Hot water Unit size Factory-installed options and accessories net weights kgMotorized Manual Motor HeatersInstalling the unit Discharge ConversionUnit mounting on roof Connection of duct network Installing the unit on the groundDownflow discharge units TSD,WSD,YSD Using the rooftop curb Horizontal discharge units TSH,WSH,YSHDuct dimensions for downflow units mm Duct dimensions for horizontal unitsCondensate drain piping Gas burner models Gas pipework installationGas leak check procedure UnitFilter arrangement Filter installationSupply fan adjustment Unit EU2/G2 EU4/G4 Quantity SizeTo decrease airflow To adjust beltTo increase airflow Motor sheave / Fan speedUnit Airflow Filter Pressure drop through accessoriesComponent air pressure drops 100%Supply fan performances TSD 060 Available static pressureTSH 060 Available static pressure TSD 072 Available static pressure TSH 072 Available static pressureTSD 090 Available static pressure TSH 090 Available static pressureTSD 102 Available static pressure TSH 102 Available static pressureTSD 120 Available static pressure TSH 120 Available static pressureYSD 060 Available static pressure YSH 060 Available static pressureYSD 072 Available static pressure YSH 072 Available static pressureYSD 090 Available static pressure YSH 090 Available static pressureStandard drive Oversize drive YSD 102 Available static pressure YSH 102 Available static pressureYSD 120 Available static pressure YSH 120 Available static pressureWSD 060 Available static pressure WSH 060 Available static pressureWSD 072 Available static pressure WSH 072 Available static pressureWSD 090 Available static pressure WSH 090 Available static pressureElectrical connection Factory supplied disconnect switch optionPower wiring Over current protectionPh/Hz Without Electric heat option Unit wiringAmpacity Size With Electric heatCompressor and condenser motors Supply fan motorControl wiring Unit controlled by thermostatUnit controlled by Tracker supervisor Zone sensor wire and maximum lengthUnit controlled by BAS MaximumCO2 sensor wire size SpecificationsCO2 sensors Wiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorJumper settings Mounting the wall-mounted sensorCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatClogged filter detector High temperature safety thermostatRemote fault relay Smoke detectorThermostat features ThermostatsRefer to separate documentation for more information Other accessories availableCommunication Interfaces Trane Communication Interface TCI-R boardHot water coil Down flow units onlyEthylene glycol percentage Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodEconomizer flow chart with barometric relief Barometric reliefOperation with a conventional thermostat Terminal stripHeating mode Thermostat signals are as followsInput / connection Function when energized Cooling mode Heat pump onlyCooling/Economizer Operation Setting the economizer or 0-50% motorized hood optionUnoccupied mode Cooling/Economizer Operation with ThermostatMinimum fresh air adjustment ECA board LEDPower-up initialization Test proceduresOperating checklist before start-up Test mode procedure at the ReliaTel control boardStep Test Mode Auto Test ModeTest modes Unit start-up Gas type designation per countryGas burner data Check torque of power cables contact Starting the unit in cooling modeFinal installation checklist Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerReliaTel Control Heating Operation Potentiometer SettingEconomizer Set-Up Ignition ModuleFinal installation checklist LED statusEnd user routine maintenance Air filtersRefrigerant charge Service technician maintenance Condenser coilHot water coil option Troubleshooting System Status Checkout ProcedureHeating Failure Service FailureSystem failure Cooling FailureClogged Filter Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Fan Failure SwitchThermistor Resistance / Temperature Chart ResistanceHumidity sensor test To Test Humidity Sensors Return Air Humidity SensorOutdoor Humidity Sensor DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.