Trane TSH 060, TSD manual Economizer Set-Up, ReliaTel Control Heating Operation, Ignition Module

Page 58

Operation

Economizer Set-Up

Adjusting the minimum position potentiometer located on the unit economizer Actuator (ECA) sets the required amount of ventilation air.

Two of the three methods for determining the suitability of the outside air can be selected utilizing the enthalpy potentiometer on the ECA, as described below:

1.Ambient Temperature - controlling the economizing cycle by sensing the outside air dry bulb temperature. The Table below lists the selectable dry bulb values by potentiometer setting.

2.Reference Enthalpy - controlling the economizer cycle by sensing the outdoor air humidity. The Table below lists the selectable enthalpy values by potentiometer setting.

If the outside air enthalpy value is less than the selected value, the economizer is allowed to operate.

3.Comparative Enthalpy - By utilizing a humidity sensor and a temperature sensor in both the return air stream and the outdoor air stream, the unit control processor (RTRM) will be able to establish which conditions are best suited for maintaining the zone temperature, i.e. indoor conditions or outdoor conditions. The potentiometer located on the ECA is non-functional when both the temperature and humidity sensors are installed.

Table 52 - Potentiometer Setting

Potentiometer

Dry BuIb

Enthalpy

Setting

(°C)

(KJ/kg)

 

 

 

A

23*

63

 

 

 

B

21

58

 

 

 

C

19

53

 

 

 

D

17

51

*Factory Setting

ReliaTel™ Control Heating Operation

When the system switch is set to the "Heat" position and the zone temperature falls below the heating setpoint controlband, a heat cycle is initiated when the RTRM communicates ignition information to the Ignition module (IGN).

Ignition Module

Two Stage (IGN) runs self-check (including verification that the gas valve is de-energized). (IGN) checks the high-limit switches (TC01 & TC02) for normally closed contacts. With 115 VAC power supplied to the ignition module (IGN), the hot surface ignition probe (IP) is preheated for approximately

45 seconds. The gas valve (GV) is energized for approximately

7 seconds for trial for ignition, to ignite the burner.

Once the burner is ignited, the hot surface ignition probe (IP) is de- energized by the ignition module (IGN) and functions as the flame sensing device.

If the burner fails to ignite, the ignition module will make two more attempts before locking out. The green LED will indicate a lock out by two fast flashes. An ignition lockout can be reset by:

1.Opening for 3 seconds and closing the main power disconnect switch

2.By switching the "Mode" switch on the zone sensor to "OFF" and then to the desired position

3.Allowing the ignition control module to reset automatically after one hour.

58

RT-SVX20A-E4

Image 58
Contents Installation Operation Maintenance General information ForewordReception WarrantyMaintenance contract RefrigerantContents Unit Options Reception of units Roof curb Installation TSD-WSD-YSD accessoriesRoof curb accessory Rooftop unitUnit weights and center of gravity Dimensions/Weights/ ClearancesMinimum recommended clearances Electric Hot water Unit size Factory-installed options and accessories net weights kgMotorized Manual Motor HeatersDischarge Conversion Installing the unitUnit mounting on roof Connection of duct network Installing the unit on the groundDownflow discharge units TSD,WSD,YSD Using the rooftop curb Horizontal discharge units TSH,WSH,YSHDuct dimensions for downflow units mm Duct dimensions for horizontal unitsCondensate drain piping Gas burner models Gas pipework installationGas leak check procedure UnitFilter arrangement Filter installationSupply fan adjustment Unit EU2/G2 EU4/G4 Quantity SizeTo decrease airflow To adjust beltTo increase airflow Motor sheave / Fan speedUnit Airflow Filter Pressure drop through accessoriesComponent air pressure drops 100%TSD 060 Available static pressure Supply fan performancesTSH 060 Available static pressure TSD 072 Available static pressure TSH 072 Available static pressureTSD 090 Available static pressure TSH 090 Available static pressureTSD 102 Available static pressure TSH 102 Available static pressureTSD 120 Available static pressure TSH 120 Available static pressureYSD 060 Available static pressure YSH 060 Available static pressureYSD 072 Available static pressure YSH 072 Available static pressureYSH 090 Available static pressure YSD 090 Available static pressureStandard drive Oversize drive YSD 102 Available static pressure YSH 102 Available static pressureYSD 120 Available static pressure YSH 120 Available static pressureWSD 060 Available static pressure WSH 060 Available static pressureWSD 072 Available static pressure WSH 072 Available static pressureWSD 090 Available static pressure WSH 090 Available static pressureElectrical connection Factory supplied disconnect switch optionPower wiring Over current protectionPh/Hz Without Electric heat option Unit wiringAmpacity Size With Electric heatCompressor and condenser motors Supply fan motorControl wiring Unit controlled by thermostatUnit controlled by Tracker supervisor Zone sensor wire and maximum lengthUnit controlled by BAS MaximumSpecifications CO2 sensor wire sizeCO2 sensors Wiring the wall-mounted CO2 sensor Wiring the duct-mounted CO2 sensorJumper settings Mounting the wall-mounted sensorCO2 sensor maintenance Mounting the duct-mounted CO2 sensorRemote potentiometer dimensions Remote potentiometerFire thermostat Duct mounting of fire thermostatClogged filter detector High temperature safety thermostatRemote fault relay Smoke detectorThermostat features ThermostatsRefer to separate documentation for more information Other accessories availableCommunication Interfaces Trane Communication Interface TCI-R boardDown flow units only Hot water coilEthylene glycol percentage Electric Heater Soft Starter25% fresh air hood 25% manual fresh air hoodEconomizer flow chart with barometric relief Barometric reliefOperation with a conventional thermostat Terminal stripHeating mode Thermostat signals are as followsInput / connection Function when energized Cooling mode Heat pump onlyCooling/Economizer Operation Setting the economizer or 0-50% motorized hood optionUnoccupied mode Cooling/Economizer Operation with ThermostatMinimum fresh air adjustment ECA board LEDPower-up initialization Test proceduresOperating checklist before start-up Test mode procedure at the ReliaTel control boardAuto Test Mode Step Test ModeTest modes Gas type designation per country Unit start-upGas burner data Check torque of power cables contact Starting the unit in cooling modeFinal installation checklist Operating pressuresCooling without an Economizer Evaporator Fan OperationLow Ambient Operation Cooling with an EconomizerReliaTel Control Heating Operation Potentiometer SettingEconomizer Set-Up Ignition ModuleFinal installation checklist LED statusAir filters End user routine maintenanceRefrigerant charge Condenser coil Service technician maintenanceHot water coil option Troubleshooting System Status Checkout ProcedureHeating Failure Service FailureSystem failure Cooling FailureClogged Filter Switch Resetting Cooling and Ignition LockoutsZone Temperature Sensor ZTS Service Indicator Fan Failure SwitchThermistor Resistance / Temperature Chart ResistanceHumidity sensor test To Test Humidity Sensors Return Air Humidity SensorOutdoor Humidity Sensor DCmaRT-SVX20A-E4 RT-SVX20A-E4

TSD, TSH 060 specifications

The Trane TSH 060 and TSD series represent cutting-edge advancements in commercial HVAC systems, designed for efficient performance and enhanced reliability. These units are engineered for a wide range of applications, making them a popular choice for various industrial and commercial settings.

One of the standout features of the Trane TSH 060 is its energy efficiency. Equipped with advanced variable-speed scroll compressors, this series can modulate its output to match the specific cooling or heating demands of a building. This not only ensures optimal comfort but also significantly reduces energy consumption and operational costs. The integrated economizer enhances outdoor air usage, providing free cooling whenever outside conditions are favorable.

The TSD series complements the TSH models with its impressive flexibility and modular design. These units can be configured to accommodate diverse load requirements, ensuring that businesses can scale their HVAC solutions as their needs evolve. The TSD also incorporates Trane's proprietary Trane Tracerâ„¢ SC+ building management system, which allows for advanced monitoring and control capabilities. This system provides real-time data analysis and helps facilitate proactive maintenance, thereby minimizing downtime and maintenance costs.

Durability is another key characteristic of the TSH 060 and TSD units. Built with robust materials and components, these systems are designed to withstand the rigors of daily use in demanding environments. The corrosion-resistant cabinet and quality construction also contribute to extended service life and reduced risk of system failures.

In terms of sustainability, both the TSH 060 and TSD units use eco-friendly refrigerants, aligning with global initiatives to reduce greenhouse gas emissions. This commitment to environmentally responsible practices makes these HVAC systems a suitable choice for businesses aiming to enhance their sustainability profiles.

Finally, quiet operation is an essential feature of the Trane TSH 060 and TSD series. These units are designed with sound-dampening technology, ensuring that the systems operate discreetly without disrupting the work environment.

In summary, the Trane TSH 060 and TSD series offer a combination of energy efficiency, advanced technology, durability, and sustainability. Their modular design and compatibility with innovative building management systems make them ideal for businesses looking to optimize their HVAC systems while maintaining a commitment to environmental responsibility. With these features, Trane continues to set the standard in commercial HVAC solutions.