Trane SCWH, SCRH manual electrical, Installation requirements, Hazardous Voltage

Page 20
Table I-ER-1. Model SCWH/SCRHelectrical data

electrical

Installation requirements

Table I-ER-1. Model SCWH/SCRHelectrical data

 

 

 

 

 

 

 

 

evaporator standard motor

 

evaporator oversized motor

 

model

tons

voltage

compressor

 

evap. fan motor

min. circuit

MFS / MCB

evap. fan motor

min. circuit

 

MFS /

 

 

 

RLA

LRA

 

qty.

hp

FLA

qty.

ampacity

 

hp

FLA

qty

ampacity

 

MCB

SC*H0303....

 

208-230V/60Hz/3Ph

12.9

77.0

 

 

0.5

2.21

1

18.3

30

 

3.15

 

19.3

 

30

SC*H0304....

3

460V/60Hz/3Ph

5.7

35.0

 

1

 

1.00

 

8.1

15

1

1.42

1

8.5

 

15

SC*H0305....

 

575V/60Hz/3Ph

4.8

31.0

 

 

 

0.80

 

6.8

15

 

1.14

 

7.1

 

15

SC*H0503....

 

208-230V/60Hz/3Ph

22.9

155.0

 

 

 

5.00

 

33.6

50

 

5.81

 

34.4

 

50

SC*H0504....

5

460V/60Hz/3Ph

10.7

75.0

 

1

1

2.50

1

15.9

25

2

2.63

1

16.0

 

25

SC*H0505....

 

575V/60Hz/3Ph

8.5

54.0

 

 

 

1.50

 

12.1

20

 

2.10

 

12.7

 

20

SC*H0753....

 

208-230V/60Hz/3Ph

27.9

164.0

 

 

 

6.30

 

41.2

60

 

5.81

 

40.7

 

60

SC*H0754....

7.5

460V/60Hz/3Ph

13.6

100.0

 

1

2

3.10

1

20.1

30

2

2.63

1

19.6

 

30

SC*H0755....

 

575V/60Hz/3Ph

10.2

78.0

 

 

 

2.40

 

15.2

25

 

2.10

 

14.9

 

25

SC*H1003....

 

208-230V/60Hz/3Ph

22.9

155.0

 

 

 

6.30

 

57.8

80

 

13.70

 

65.2

 

80

SC*H1004....

10

460V/60Hz/3Ph

10.7

75.0

 

2

2

3.10

1

27.2

35

5

6.18

1

30.3

 

40

SC*H1005....

 

575V/60Hz/3Ph

8.5

54.0

 

 

 

2.40

 

21.5

30

 

4.94

 

24.1

 

30

SC*H1203....

 

208-230V/60Hz/3Ph

25.4

147.7

 

 

 

9.40

 

66.5

90

 

13.70

 

70.8

 

90

SC*H1204....

12

460V/60Hz/3Ph

11.8

75.0

 

2

3

4.60

1

31.2

40

5

6.18

1

32.7

 

45

SC*H1205....

 

575V/60Hz/3Ph

9.3

59.6

 

 

 

3.40

 

24.4

30

 

4.94

 

25.9

 

35

SC*H1503....

 

208-230V/60Hz/3Ph

27.9

164.0

 

 

 

9.40

 

72.2

100

 

13.70

 

76.5

 

100

SC*H1504....

15

460V/60Hz/3Ph

13.6

100.0

 

2

3

4.60

1

35.2

45

5

6.18

1

36.8

 

50

SC*H1505....

 

575V/60Hz/3Ph

10.9

78.0

 

 

 

3.40

 

27.9

35

 

4.94

 

29.5

 

35

Notes:

1. Voltage range:

Nominal voltage 208 - 230V - acceptable range: 187 - 253V

Nominal voltage 460V - acceptable range: 414 - 506V

Nominal voltage 575V - acceptable range: 518 - 633V

2.Ampacity is calculated per UL formula, ampacity = (1.25 x compressor RLA + sum of the second compressor RLA (if used) + evaporator motor FLA

3.Maximum fuse size is calculated per UL formula, MFS = (2.25 x compressor RLA) + sum of second compressor RLA (if used) + evaporator motor FLA

Manual background WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

CAUTION

Use Copper Conductors Only! Unit terminals are not designed to accept other type conductors. Failure to use copper conductors may result in equipment damage.

20

PKG-SVX14A-EN

Image 20
Contents “AO” and later design sequence OctoberInstallation, Operation, and Maintenance Midrange Self-ContainedUnitsgeneral information Warnings and CautionsExample Warnings and Cautions Special Note on Refrigeration Emissionscontents Installation…………………………………………………2Maintenance ……………………………………………25 Operation…………………………………………………24Installation information Unit Airflow Configurationsgeneral Midrange Model Number DescriptionRefrigerant Handling Procedures generalGeneral Installation informationpre-installation Installation considerations Installation PreparationReceiving and Handling Pre-InstallationConsiderations3 through 7.5-tonSCRH/SCWH Service Accesspre-installation Installation considerations 10 through 15-tonSCRH/SCWH pre-installation Installation considerationsService Access Isolator Placement pre-installation Installation considerationsNote Isolators are field-provided 1 7/8Improper Unit Lift Proper Lifting Procedurepre-installation Installation considerations dimensions & Installation weights3 & 5-tons SCWH/SCRH vertical discharge SCWH7.5-tons SCWH/SCRH dimensionsInstallation weights vertical dischargeSCWH/SCRH dimensionsInstallation weights SCWH/SCRH dimensions & weight, in-lbsdimensions Installation weightsSCWH/SCRH Dimensions, in SCWH/SCRHPlenum dimensionsInstallation weights Hot water coil 3 & 5-tonunitsHot water coil 7.5-tonunitsHot water coil 10 thru 15-tonunits dimensionsInstallation requirements Duct Connectionsmechanical Water PipingRefrigerant Piping Air-CooledUnits Only Electrical RequirementsInstallation requirements Brazing Procedureselectrical Electrical Data CalculationsInstallation requirements Supply Power WiringInstallation requirements electricalHazardous Voltage Table I-ER-1.Model SCWH/SCRHelectrical datainstallation Installation procedureInstallation Checklist Plenum InstallationPre-StartupChecklist pre-startupInstallation requirements ReceivingInstallation startup Unit Startup ProceduresUnit Startup Checklist Hazardous voltageSequence of Operation sequence ofOperation operation general Maintenance informationTable M-GI-1.Midrange maintenance general data maintenance Maintenance proceduresMaintenance Procedures Periodic Maintenance ChecklistRefrigerant System maintenanceMaintenance procedures Leak Testingmaintenance Maintenance proceduresMotor Winding Damage Hazardous PressuresMaintenance checklists Periodic Checklistsperiodic Monthly ChecklistHazardous voltage Maintenance troubleshootingTroubleshooting Hazardous voltage Maintenance troubleshootingInsufficient cooling typical wiring Maintenance diagramPKG-SVX01A-EN typical wiringMaintenance diagram typical wiring Maintenance diagramPKG-SVX01A-EN typical wiringMaintenance diagram Literature Order Number PKG-SVX14A-ENDate October