Honeywell F90A, F90B specifications Checkout, Adjustments, Service

Page 12

F90A,B SELF-CONTAINED COMMERCIAL ELECTRONIC AIR CLEANER

Installing Cover

1.Before installing, study the inside of the F90 cover. One end has two latches and the other has two hinge pins. To properly install the cover, connect the hinge pins to the hinges.

2.Attach the hinge pins by lifting the cover above the hinge and lowering the pins into the hinges. If the cover is properly attached, it can hang below the F90.

3.Carefully swing the opposite end of the cover upward and engage the latches. See Fig. 13. Assure the latches are connected properly.

M2364

Fig. 13. Opening and closing F90 cover.

CHECKOUT

Inspect The Installation

Be sure the F90:

‰Is securely fastened to the ceiling or wall.

‰Does not interfere with normal occupant traffic.

‰Is properly oriented for good air circulation.

‰Cells are correctly oriented with air flow arrows pointing toward the fan.

‰Prefilters are properly installed below the cells.

‰Discharge louvers are securely installed.

‰Cover is securely latched.

‰SYSTEM light turns on when fan is running.

‰Fan stops and ON LED turns off when the cover is opened.

‰Surfaces and the installation area are wiped clean.

‰Marked or nicked paint is retouched.

Check F90 Operation

‰Turn on power.

‰Push the test button to assure the power supply is functioning at all three speeds.

‰Use the manual switch on the F90, manual wall switch, or remote transmitter to assure that the fan runs correctly at all three speed settings.

‰Assure the ON LED lights when the fan is operating.

‰Assure the WASH LED (if used) lights when the cells are removed, grille is closed, and F90 is

turned on.

ADJUSTMENTS

Louver Adjustment

CAUTION

Do not operate air cleaner without the louvers installed.

The F90 plastic louvers can be repositioned to vary the airflow pattern. Three positions are available. Position 3 directs airflow along the ceiling. Positions 2 and 1 direct airflow downward. Use position 2 or 1 if ceiling staining is a problem or if beams or other obstacles disrupt airflow.

Louvers are shipped in position 1. Louvers can be adjusted as follows:

1. Loosen screw by turning counterclockwise 2-1/2 turns. Do not remove screw.

2. Push louvers up to disengage bottom tabs, and pull bottom of the louvers out slightly to desired position.

3. Retighten the screw. Assure that the tabs on the bottom of the louvers are positively engaged with the F90 frame.

SERVICE

WARNING

Sharp Edges.

Can cause personal injury.

Wear protective gloves and carefully handle the cells and prefilters to avoid cuts from the sharp metal edges, collection plates, and ionizer wires.

Steam, Hot Water, Strong Detergent.

Can cause personal injury.

Wear rubber gloves, eye protection, and rubber apron for protection from the strong cleaning chemicals and hot temperatures.

IMPORTANT

The F90 and its components are susceptible to damage. Be careful when working with them to avoid equipment damage. Never use an acid base detergent to wash cells.

68-0103-6 Revised 11-07

12

Image 12
Contents Features Application ContentsSpecifications Ordering InformationPlanning the Installation Application and OperationDetermine Number of F90 Needed Choose LocationExample 1. Sizing by Air Changes per Hour and Room Volume SolutionOutdoor Air Installation When Installing this Product…Example 3. Sizing by Air Changes per Hour and Room Volume Example 2. Sizing by Occupant LoadMounting the F90 Using Lag Screws UnpackingMounting F90 can be mounted in any of four waysInstalling the Wash LED Mounting the F90 Using Threaded Steel Rod Using the mounting template to locate holesArrange two 2 x 4 supports as shown in Fig Mount the steel rods to the supportsWiring Power CordInstalling Activated Carbon Filters, Cells, and Prefilters Permanent WiringAdjustments ServiceCheckout Cleaning the F90 Cleaning the PrefilterCleaning the Cell Using Alkaline Base Detergent Hazardous Chemical Can cause personal injuryDiscolored Aluminum Removing Specific Contaminants from the CellReplacing Ionizer Wires Modifying to Reduce Ozone OdorElectrical Troubleshooting Troubleshooting ProcedureRemoving The Power Box Tools And EquipmentStart Removing the F90 Power Box Assembly F90A 120 Vac model schematic diagram F90A 230 Vac model schematic diagram CE compliant model F90B 120 Vac model schematic diagram Replacement Parts LIST/EXPLODED View Parts and Optional Accessories Not IllustratedF90A exploded view. Part numbers are keyed to Parts List Limited ONE-YEAR Warranty How to make a warranty claim or have questions answered