CC880/LP880, SC8016 Operators Guide 4.0 | Arming the System |
|
|
EN 7
3.4System Disarmed
This indicator displays with the indicator when the system is disarmed.
3.5MAINS Indicator
The MAINS indicator displays that the systems AC mains supply is normal or failed.
Table 5: MAINS Indicator
MAINS Indicator | Definition |
On | AC mains power normal. |
Flashing | AC mains supply failed. |
3.6Off Indicator/Zone Sealed
The indicator displays when the system is in the disarmed state and flashes when a zone becomes unsealed during the disarmed state. The indicator stops flashing when all zones are sealed.
3.7On Indicator/Zone In Alarm
The indicator displays when the system is armed in AWAY Mode and flashed when an alarm occurs. The indicator resets once a valid user code is entered.
3.8FAULT Indicator
The FAULT indicator displays when the system detects a system fault. See Section 14.0 Fault Analysis Mode for additional information on system faults. Every time a new system fault is detected (such as, FAULT indicator flashing), the codepad beeps once every minute. Pressing the [#] button once cancels the once a minute beep and acknowledges the fault (such as, FAULT indicator on steady).
Table 6: FAULT Indicator
FAULT Indicator | Definition |
On | There is a system fault that must |
| be rectified. |
Off | The system is normal, there are |
| no faults. |
Flashing | There is a system fault that must |
| be acknowledged. |
3.9Audible Indications
Table 7 defines the audible indicators emitted by the codepad buzzer.
Table 7: Audible Indicators
Audible Indicator | Definition |
Once short beep | A button was pressed on the |
| codepad, or end of exit time |
| when armed in STAY Mode 1 or |
| STAY Mode 2. |
Two short beeps | The system accepted your |
| code. |
Three short beeps | The requested function was |
| executed. |
One long beep | Indicates the end of exit time |
| when armed in AWAY Mode, or |
| the requested operation was |
| denied or aborted. |
One beep every | Walk Test Mode is currently |
second | active or warning before |
| automatic arming takes place. |
One short beep | There is a system fault waiting |
every minute | to be acknowledged. |
4.0 Arming the System
There are several ways to arm the system, depending on whether you are:
•leaving the premises and require all active zones to be in a ready state for an intruder, or
•remaining in the premises and only require part of the system to be in a ready state for an intruder.
If a zone is not sealed at the end of exit time, the zone is automatically isolated and is constantly displayed on the remote codepad. The zone becomes an active part of the system when the zone reseals. (For example, if a window is left open after exit time expires, the window is not an active part of the system until the window is closed. Opening the window after exit time expires causes an alarm condition.)
Table 8 defines the different methods for arming the system.
Table 8: Arming Methods
AWAY Mode Arms the entire system. See Section 4.2 Arming in AWAY Mode.
STAY Mode 1 Arms all zones except those programmed to be automatically isolated by the installer. See Section 4.3 Arming in STAY Mode 1.
STAY Mode 2 Arms all zones except those programmed to be automatically isolated by the master code holder. See Section 4.4 Arming in STAY Mode 2.
Bosch Security Systems 6/04 920036O.OG.162