Calibrate]. If using the LTC 8555 Series keyboard, refer to the User Function 1 procedure. (See Chapter 14, “User Information,” on page 38).
21.3Video Monitor Display Checkout
1.No video display on any monitor: Verify proper CPU operation as described above under Main Bay Checkout Section.
2.No video display on some monitors: Verify operational camera is selected on suspect monitors. Confirm monitor is operational. Check monitor coax connec- tions. Verify coax connection to correct monitor output on rear of main bay.
Replace video output module.
3.Poor video on monitor: Check monitor for proper termination. Check opera- tion of known good camera directly to monitor.
4.Partial or no
5.Time and Date portion of the
21.4Remote Receiver/Driver Functions Inoperative
1.All receiver / drivers and functions inoperative: Verify power LED indica- tor on Signal Distribution Unit is lit. If not, check fuses on front of main CPU bay power supply. Verify the Code LED indicator flickers when control is acti- vated by the keyboard. If not, replace Signal Distribution Unit.
2.Individual receiver/driver
3.AutoDome series dome cameras are not operating in a variable speed fashion: Verify CPU DIP switch 7 is selected for variable speed mode.
21.5No Alarm Response
1.No system alarms operative: Verify power LED indicator on Alarm Interface Unit is lit. If not, check fuses on front of main CPU bay power supply. Verify the Alarm LED indicator lights and the audible buzzer sounds (if enabled) only when an 'alarm' is applied to the unit. If not, replace Alarm Interface unit.
2.Individual cameras/monitors not responding when alarmed: Ensure desired cameras are properly armed on the appropriate armed monitors in the system. Verify alarming device and cable to Alarm Interface unit intact.