TOA Electronics P0055-DRG Spark ignitor will not Defective Ignitor, Electrode at pilot spark at

Page 14

14

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

Note: Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

 

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

 

 

1.

Spark ignitor will not

A. Defective Ignitor

Check for spark at electrode and pilot; if no spark and electrode wire

 

light pilot after repeated

(no spark at electrode)

is properly connected, replace the ignitor.

 

triggering of red button.

 

 

 

 

 

B. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off pilot and trigger the

 

 

 

 

 

 

electrode at pilot (spark at

red button again. If pilot lights an improper gas mixture caused the

 

 

 

electrode).

bad lighting and a longer purge period is recommended. If pilot will

 

 

 

 

not light check gap at electrode and pilot - should be ¹⁄₈"

 

 

 

 

(3 mm) to have a strong spark. If gap measures ¹⁄₈", replace pilot

 

 

 

 

assembly (Figure 11 on page 7).

 

 

 

 

 

 

 

 

C. Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits as marked on

 

 

 

 

the rating plate.

 

 

 

 

 

 

 

 

D. Pilot orifice plugged.

Clean or replace pilot orifice.

 

 

 

 

2.

Pilot will not stay lit

A. Defective pilot generator

Check pilot flame. It must impinge on pilot generator (Figure 11 on

 

after carefully following

(thermopile) or remote wall

page 7). Clean and/or adjust pilot for maximum flame impingement

 

lighting instructions.

switch wiring.

on generator.

 

 

 

 

Be sure wire connections from generator at gas valve terminals are

 

 

 

 

tight and generator is fully inserted into the pilot bracket.

 

 

 

 

One of the wall switch wires may be grounded. Remove wall switch

 

 

 

 

wires from valve terminals. If pilot now stays lit, trace wall switch

 

 

 

 

wires for a ground. May be grounded to appliance or gas supply.

 

 

 

 

With pilot operating (lit), check pilot generator with a millivolt meter.

 

 

 

 

Take reading at generator terminals of gas valve. Should read 325

 

 

 

 

millivolts minimum while holding valve knob depressed in pilot

 

 

 

 

position and wall switch “OFF.” Replace faulty generator if reading

 

 

 

 

is below specified minimum.

 

 

 

 

 

 

 

 

B. Defective automatic valve

Turn knob to “ON,” place wall switch to “ON.” Millivolt meter should

 

 

 

operator.

read greater than 100mV. If reading is OK and the burner does not

 

 

 

 

come on, replace the gas valve.

 

 

 

 

 

 

 

 

C. Defective limit switch.

Reset the limit switch button. If still not working, isolate the limit

 

 

 

 

switch. Disconnect the wires from the “ON/OFF” switch and the valve

 

 

 

 

(label wires for reattachment). Test for continuity with a multimeter.

 

 

 

 

If continuity is not indicated, switch is defective and must be replaced.

 

 

 

 

3.

Pilot burning, no gas to

A. Wall switch or wires

Check wall switch and wires for proper connections. Place jumper

 

burner, valve knob “ON,”

defective.

wires across terminals at wall switch. If burner comes on, replace

 

wall switch “ON.”

 

defective wall switch. If OK, place jumper wires across wall switch

 

 

 

 

wires at gas valve. If burner comes on, wires are defective or

 

 

 

 

connections are bad.

 

 

 

 

 

 

 

 

B. Pilot generator may not be

Re-check Symptom #2.

 

 

 

generating sufficient

 

 

 

 

millivoltage.

 

 

 

 

 

 

 

 

 

C. Plugged burner orifice.

Check burner orifice for blockage and remove.

 

 

 

 

4.

Frequent pilot outage

A. Pilot flame may be too low or

Clean/adjust pilot flame for maximum impingement on pilot genera-

 

problem.

blowing (high) causing the pilot

tor (Figure 11 on page 7).

 

 

 

safety to drop out.

 

 

 

 

 

 

Image 14
Contents 725,029M REV. C 07/2004 Retain These InstructionsVented GAS Fireplaces GRD-5500 SHOWNGHC-5500PGRD-5500NTable of Contents CongratulationsControl Compartment Access GHC-5500 Units Gas Controls/Control Compartment AccessControl Compartment Access GRD-5500 Units Operation and Care of Your ApplianceOutside Combustion Air Controls Millivolt Appliance LightingElectronic Appliance Lighting Firebox Wrapper Limit Switch Screws MaintenanceManual Reset Limit Switch Lintel Burner Adjustments Flame Appearance and SootingMaintenance Task Accomplishing Person Maintenance ScheduleMaintenance Task Accomplishing Person Procedure Electronic Appliance Checkout Logs and Rockwool Glowing Embers PlacementMillivolt Appliance Checkout LOG Placement Electronic System Wiring Without Forced Air Kit WarrantyReplacement Parts Product Reference InformationTo Turn OFF GAS to Appliance Lighting Instructions Millivolt GAS ValveLighting Instructions Pour Fermer LE GAZ QUI Alimente L’APPAREIL Instructions D’ALLUMAGE Vanne GAZ MillivoltInstructions Dallumage To Shut OFF Lighting Instructions ElectronicWhat to do if YOU Smell GAS Fermez la porte du compartiment de contrôle du bas Instructions D’ALLUMAGE ElectronicPilot burning, no gas to Wall switch or wires Lighting instructions Switch wiring On generatorDefective limit switch Wall switch onTroubleshooting the Electronic Ignition System Symptom Possible Causes Corrective ActionHorizontal Trim Installation Accessory ComponentsStandard Remote Control System Model RCL Aluminum-Framed Bi-Fold DoorsGRD-5500 Replacement Parts List Millivolt SystemGAS CONTROLS- Robertshaw Millivolt GHC/GRD-5500Replacement Parts Millivolt Replacement Parts List Electronic System GAS CONTROLS- Robertshaw ElectronicReplacement Parts Electronic Manufactured by LHP 725,029M REV. C 07/2004