TROUBLESHOOTING GUIDE

Start Up Conditions

Thermal Expansion

Water supply system may, because of such events as high line pressure, frequent cut-offs and the effects of water hammer have installed devices such as pressure reducing valves, check valves, back flow preventers, etc., to control these types of problems. When these devices are not equipped with an internal by-pass, and no other measures are taken, the devices cause the water system to be closed. As water is heated, it expands (thermal expansion) and closed systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and increases the pressure of the water system. If the relieving point of water heater’s temperature-pressure relief valve is reached, the valve will relief the excess pressure. The temperature- pressure relief valve is not intended for the constant relief of thermal expansion. This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a closed system have a by-pass and/or the system have an expansion tank or device to relieve the pressure built by thermal expansion. Thermal expansion tanks are available from Sears stores and through the Sears Service Centers. Contact the local plumbing inspector, water supplier and/or the Sears Service Center for assistance in controlling these situations, see Figure 27.

Thermal Expansion Tank Specifications

 

Tank

Dimensions

Pipe

Model

Capacity

in Inches

 

Fitting

Number

In Gallons

Diameter

 

Length

On Tank

153.331020

2

8 (203 mm)

12-3/4 (323 mm)

3/4” Male

153.331050

5

11 (279 mm)

14-3/4 (375 mm)

3/4” Male

 

 

 

 

 

 

Expansion Tank Sizing Chart

 

Inlet*

 

Water Heater Capacity (Gallons)

 

Water

 

 

 

 

 

 

Expansion

Pressure

 

30

40

50

66

82

40psi

2

2

2

5

5

Tank

50psi

2

2

2

5

5

Capacity

60psi

2

2

5

5

5

Needed

70psi

2

2

5

5

5

 

80psi

2

5

5

5

5

 

 

 

 

 

 

 

 

*Highest recorded inlet water pressure in a 24 hour period or regulated water pressure.

NOTE: Expansion tanks are pre-charged with a 40 psi air charge. If the inlet water pressure is higher than 40 psi, the expansion tank’s air pressure must be adjusted to match that pressure, but must not be higher than 80 psi.

FIGURE 27.

Strange Sounds

Possible noises due to expansion and contraction of some metal parts during periods of heat-up and cool-down do not represent harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be considered normal. See Condensation section.

Draft Hood Operation

Check draft hood operation by performing a worst case depressurization of the building. With all doors and windows closed, and with all air handling equipment and exhaust fans operating such as furnaces, clothes dryers, range hoods and bathroom fans, a match flame should still be drawn into the draft hood of the water heater with its burner firing. If the flame is not drawn toward the draft hood, shut off water heater and make necessary air supply changes to correct.

23

Image 23
Contents Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A Power Miser 9 GAS Water HeaterImportant Definitions Safe INSTALLATION, USE and ServiceSafety Precautions Table of Contents Customer Responsibilities Product SpecificationsBasic Tools Additional Tools Needed When Sweat SolderingMaterials and Basic Tools Needed Materials NeededGET to Know Your Water Heater GAS Models Typical InstallationRemoving the Old Water Heater Installation InstructionsFacts to Consider About the Location Insulation Blankets ALL AIR from Inside Buildings Hotter Water can Scald Water PipingValve and Pipe Insulation Temperature-Pressure Relief Valve Venting Filling the Water HeaterGas Piping Sediment Traps GAS Piping with Flexible ConnectorOperating Instructions For Your Safety Read Before LightingTemperature Time to Produce 2nd & 3rd Temperature RegulationVent System Inspection Burner Inspection Service and AdjustmentTank Sediment Cleaning Burner CleaningAnode Rod Temperature-Pressure Relief Valve OperationHousekeeping Draining Drain Valve Washer ReplacementService Start Up Conditions Troubleshooting GuideCondensation Operational ConditionsLeakage Checkpoints Troubleshooting Guide Parts Order List 153.339962 Gallon L.P 153.339161 Gallon Short Part Description 153.339562 153.339762 153.339640 153.339680 Page Page MY-HOME