Bryant GT-PG (50YE) manual AHRI/ISO/ASHRAE/ANSI 13256-1 Performance, Btuh/W, Watts

Page 8

GT-PG (50YE) Series

AHRI/ISO/ASHRAE/ANSI 13256-1 Performance

ASHRAE/AHRI/ISO 13256-1. English (I-P) Units

 

 

 

 

 

Water Loop Heat Pump

 

Ground Water Heat Pump

Ground Loop Heat Pump

 

 

Model

Fan

Cooling 86°F

Heating 68°F

Cooling 59°F

Heating 50°F

Cooling 77°F

Heating 32°F

 

 

Motor

Capacity

EER

Capacity

 

COP

Capacity

EER

Capacity

COP

Capacity

EER

Capacity

COP

 

 

 

 

 

 

 

 

 

 

Btuh

Btuh/W

Btuh

 

Btuh

Btuh/W

Btuh

Btuh

Btuh/W

Btuh

 

 

 

 

 

 

 

 

 

 

TS018

 

PSC

18,600

15.0

23,000

 

5.2

21,300

24.8

18,800

4.5

19,500

18.4

14,500

3.6

 

 

ECM

19,200

16.5

23,300

 

5.9

22,100

26.3

18,900

4.9

20,200

19.4

14,500

3.9

 

 

 

 

 

 

TS024

 

PSC

25,100

16.2

29,600

 

4.9

28,600

25.7

25,000

4.3

26,300

19.1

19,000

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECM

25,000

17.0

30,000

 

5.3

28,100

27.4

25,100

4.6

26,000

20.0

19,400

3.8

 

 

 

 

 

 

TS030

 

PSC

28,200

15.3

34,900

 

5.0

31,700

22.9

29,400

4.4

29,400

17.6

23,600

3.8

 

 

ECM

28,600

15.6

35,200

 

5.3

32,200

23.9

29,400

4.6

29,800

18.0

23,700

3.9

 

 

 

 

 

 

TS036

 

PSC

33,000

16.6

39,800

 

5.5

37,300

25.1

32,900

4.8

34,500

19.2

25,700

3.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECM

33,100

17.6

39,500

 

5.8

37,300

26.5

32,900

5.1

34,600

20.2

25,800

4.2

 

 

 

 

 

 

TS042

 

PSC

37,400

16.0

49,400

 

5.4

42,900

24.3

40,100

4.6

39,300

18.4

31,600

3.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECM

37,800

17.1

48,600

 

5.7

44,200

27.1

39,300

4.9

40,000

20.0

30,400

4.0

 

 

 

 

 

 

TS048

 

PSC

47,000

15.3

60,000

 

5.0

53,900

23.3

49,000

4.4

49,900

17.6

39,000

3.7

 

 

ECM

47,600

15.9

59,700

 

5.2

54,100

24.6

48,700

4.5

50,100

18.5

38,400

3.8

 

 

 

 

 

 

TS060

 

PSC

61,000

15.9

70,400

 

5.0

67,000

23.2

58,700

4.5

63,300

18.2

46,500

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECM

61,000

16.4

70,800

 

5.2

67,200

24.3

59,100

4.6

64,000

19.0

46,700

3.8

 

 

 

 

 

070

 

ECM

67,000

15.2

84,900

 

5.0

77,000

23.5

69,000

4.4

70,000

17.8

53,900

3.6

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature

 

 

 

 

 

 

 

Heating capacities based upon 68°F DB, 59°F WB entering air temperature

 

 

 

 

 

 

 

All ratings based upon operation at lower voltage of dual voltage rated models

 

 

 

 

 

 

 

ASHRAE/AHRI/ISO 13256-1. Metric (S-I) Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Loop Heat Pump

 

Ground Water Heat Pump

Ground Loop Heat Pump

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Cooling 30°C

Heating 20°C

Cooling 15°C

Heating 10°C

Cooling 25°C

Heating 0°C

 

 

 

 

Motor

Capacity

EER

Capacity

 

COP

Capacity

EER

Capacity

COP

Capacity

EER

Capacity

COP

 

 

 

 

 

Watts

W/W

Watts

 

Watts

Watts

Watts

Watts

W/W

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

PSC

5,470

4.4

6,764

 

5.2

6,264

7.3

5,529

4.5

5,735

5.4

4264

3.6

 

TS018

 

 

 

 

 

 

ECM

5,647

4.8

6,852

 

5.9

6,500

7.7

5,558

4.9

5,941

5.7

4,426

3.9

 

 

 

 

 

 

 

 

 

PSC

7,356

4.7

8,675

 

4.9

8,382

7.5

7,327

4.3

7,708

5.6

5,569

3.7

 

TS024

 

 

 

 

ECM

7,327

5.0

8,792

 

5.3

8,236

8.0

7,356

4.6

7,620

5.9

5,686

3.8

 

 

 

 

 

 

 

 

 

PSC

8,265

4.5

10,229

 

5.0

9,291

6.7

8,617

4.4

8,617

5.2

6,917

3.8

 

TS030

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

 

 

ECM

8,382

4.6

10,317

 

5.3

9,437

7.0

8,617

4.6

8,734

5.3

6,946

3.9

 

 

 

 

 

 

 

 

 

PSC

9,672

4.9

11,665

 

5.5

10,932

7.4

9,642

4.8

10,111

5.6

7,532

3.9

 

TS036030

 

 

 

 

 

ECM

9,701

5.2

11,577

 

5.8

10,932

7.8

9,642

5.1

10,141

5.9

7,562

4.2

 

 

 

 

 

 

 

 

 

PSC

10,961

4.7

14,478

 

5.4

12,573

7.1

11,753

4.6

11,518

5.4

9,261

3.8

 

TS042

 

 

 

 

 

ECM

11,079

5.0

14,244

 

5.7

12,954

7.9

11,518

4.9

11,723

5.9

8,910

4.0

 

 

 

 

 

 

 

 

 

PSC

13,775

4.5

17,585

 

5.0

15,797

6.8

14,361

4.4

14,625

5.2

11,430

3.7

 

TS048

 

 

 

 

 

ECM

13,951

4.7

17,497

 

5.2

15,856

7.2

14,273

4.5

14,683

5.4

11,254

3.8

 

 

 

 

 

 

 

 

 

PSC

17,878

4.7

20,633

 

5.0

19,637

6.8

17,204

4.5

18,552

5.3

13,628

3.7

 

TS060

 

 

 

 

 

ECM

17,878

4.8

20,750

 

5.2

19,695

7.1

17,321

4.6

18,757

5.6

13,687

3.8

 

 

 

 

 

 

 

 

 

ECM

19,637

4.5

24,883

 

5.0

22,567

6.9

20,223

4.4

20,516

5.2

15,797

3.6

070

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacities based upon 27°C DB, 19°C WB entering air temperature

Heating capacities based upon 20°C DB, 15°C WB entering air temperature

All ratings based upon operation at lower voltage of dual voltage rated models

GT-PG

Bryant: Whatever it Takes.

8

 

 

 

Image 8
Contents GT-PG 50YE Packaged Series Table of Contents GT-PG 50YE SeriesOther New Features Whats New with Bryant Geothermals GT-PG?Puron Refrigerant Tin-Coated Air CoilGT-PG Design Features Options & Accessories Unit Model Key Series Revision LevelTest Condition Comparison Table About AHRI/ISO/ASHRAEAbout AHRI/ISO/ASHRAE AHRI/ISO/ASHRAE/ANSI 13256-1 Performance Ground Water Heat Pump Ground Loop Heat PumpBtuh/W BtuhReference Calculations & Legend CoolingPower Sensible PowerAir Flow Correction Factors 75%Air WBF Entering Air Correction FactorsAir DBF This is due to the potential of the refrigerant temperature Performance Data Selection NotesPerformance Data GT-PG Model 018 PSC Blower PSI EER LATPerformance Data GT-PG Model 018 ECM Blower Performance Data GT-PG Model 024 PSC Blower PSIPerformance Data GT-PG Model 024 ECM Blower Operation Not recommendedPerformance Data GT-PG Model 030 PSC Blower Performance Data GT-PG Model 030 ECM Blower AOperationPerformance Data GT-PG Model 036 PSC Blower Performance Data GT-PG Model 036 ECM Blower Performance Data GT-PG Model 042 PSC Blower 110Performance Data GT-PG Model 042 ECM Blower Performance Data GT-PG Model 048 PSC Blower Performance Data GT-PG Model 048 ECM Blower OperationPerformance Data GT-PG Model 060 PSC Blower Performance Data GT-PG Model 060 ECM Blower Performance Data GT-PG Model 070 ECM Blower Physical Data Dimensions Vertical Upflow GT-PG 50YE Series Discharge Connection Return Connection ReturnDimensions Vertical Downflow GT-PG 50YE Series Floor Foot Print Dimensions Horizontal GT-PG 50YE Series 1Discharge Connection Return Connection +/- 0.20 in, +/- 5.1mm ModelElectrical Data GT-PG ECM Electrical Wiring Diagram 96B0005N37 GT-PG PSC Electrical Wiring Diagram 96B0005N36 Bryant Whatever it Takes GT-PG ECM Control Features ECM Board Tap Settings ECM Blower Performance Data AuxIn. wg 640 800 400 500 620PSC Blower Performance Data Airflow cfm at External Static Pressure in. wgAuxiliary Electric Heat Auxiliary Heat Ratings Auxiliary Heat Electrical DataAuxiliary KW Rating Btuh Rating MinimumEngineering Guide Specifications Accessories & Options Accessories & Warranty Warranty InformationGT-PG 50YE Series Bryant Geothermal Heat Pump Systems ECM Electrical Data Updated Revision History

GT-PG (50YE) specifications

The Bryant GT-PG (50YE) is a state-of-the-art gas-fired packaged unit ideal for both commercial and residential applications. Renowned for its efficiency and reliability, this model stands out in the competitive HVAC market. With its sleek design and advanced features, it promises optimal performance while maintaining energy efficiency, making it a favorite among building owners and contractors alike.

One of the most remarkable features of the Bryant GT-PG (50YE) is its high-efficiency gas heat exchanger. This component enhances energy transfer, ensuring that maximum heat is produced with minimal energy consumption. With an Annual Fuel Utilization Efficiency (AFUE) rating that meets and exceeds industry standards, users can count on significant savings in energy bills over time. Additionally, the unit is equipped with a multi-speed blower that further enhances its efficiency by providing a consistent flow of air while reducing noise levels.

Another significant characteristic of the GT-PG (50YE) is its advanced control system. Featuring a user-friendly interface, this system allows for precise temperature control and integration with smart home technologies. The modulating gas valve optimizes performance based on heating demand, providing customized comfort for any environment.

Reliability is key with the Bryant GT-PG (50YE). It is built with sturdy materials designed to withstand the elements, enhancing its lifespan and reducing maintenance needs. The inclusion of a robust stainless steel heat exchanger aids in preventing corrosion, ensuring durability in various climates.

Moreover, safety features are paramount in the design of the GT-PG (50YE). It includes integrated safety controls, such as a flame rollout switch and limit control, providing peace of mind for users.

Installation and maintenance are made easy with this model, which includes a compact design allowing for versatile placement options. Service access has been thoughtfully designed, ensuring technicians can perform routine maintenance without hassle.

In conclusion, the Bryant GT-PG (50YE) is a powerhouse of an HVAC solution, blending efficiency, reliability, and advanced technology. With its exceptional heating capabilities, user-friendly controls, and durable construction, this model is perfect for anyone looking to invest in long-term comfort and performance. Whether for residential or commercial use, the GT-PG reflects Bryant's commitment to quality and customer satisfaction.