5.3E Setting Relative Humidity Set point

The relative humidity Set point operates the dehumidifier function of the Ultra-Aire. It has no effect on any other function of the unit. The control senses the ambient relative humidity of the space in which it is located. The ambient condition is displayed on the right in the relative humidity display sequence, under the word “HUMIDITY”. The current Set point is displayed on the left, under the word “SET”.

If the Set point is equal to or greater than the current ambient condition, the space does not need to be dried, sothe dehumidifier function will be off. Example: Set point: 50%RH Current condition 45% RH = Dehumidifier off, red “DEHU”indicator not lit.

If the Set point is less than the ambient condition, thedehumidifier will be on, and the red “DEHU” indicator will be lit. The space is more humid than the Set point, so the controller operates the dehumidifier to dry the space.Example: Set point: 50% RH Current condition: 55% RH =Dehumidifier on, red “DEHU” indicator lit.

To set the relative humidity Set point, press the “HUM”button. The display will show the “HUMIDITY” display, and theword “SET” will flash. Use the “SET” + or – buttons to adjustthe relative humidity Set point as desired. Therma-Stor LLC recommends relative humidity levels of 45% in the summer,and lower levels in the winter. It is not recommended thehumidity Set point be set below 35%. In order to dry thehome in the winter in a cold climate, use the ventilationfunction of the system rather than the dehumidifier function.

5.3F Fan Setting and Operation

Use the “FAN” button to adjust the fan operation. There are 3 choices for fan operation: “on”, “off” (denoted by “OF”), or program (denoted by “Pr”). To set operation,

1.Press the “FAN” button. The display will indicate the current fan setting.

2.Use the “SET” + or – buttons to adjust fan operation (“on”, “OF”’ or “Pr”). Press the “FAN” button again or leave the unit alone for 10 seconds to return to home state.

5.3G Fan On Fan Off Fan Program

The fan display reading in the normal display sequence does not indicate the current fan setting, it indicates the current fan status, and will always read either on or off. With the fan in the

“on” mode, the fan will run continuously. This does not effect the dehumidification functions of the system. The system may or may not be ventilating or dehumidifying while the fan is running. Common reasons for operating the fan continuously are continuous filtration and air recirculation. With the fan in the “off” or “program” mode, the fan will operate only when needed by other functions of the system. The fan will remain off unless the system is dehumidifying and/or ventilating. The fan always runs during dehumidification, it also always runs during ventilation. To completely turn the system off, use the “ON/OFF” button as described earlier.

5.3H Damper Operation and Setting (Ventilation)

The damper setting controls the ventilation function of the system. It has no control over the dehumidification function. In order to provide ventilation, the damper must be open (“on”) and the fan must be running. The controller takes care of these two functions automatically, so whenever the damper is open (“on”), the fan is running.

This is true even if the fan has been set to the “off” mode. The ventilation indicator will be lit whenever the unit is ventilating.

There are three damper operation modes, “on”, “off” (denoted by “OF”), and program (denoted by “Pr”). With the damper in the “on” mode, the damper will be open and the fan of the system will be operating in order to introduce fresh air into the space. Use this mode for continuous fresh air ventilation. The fan is always on when the damper is open. When in “off” mode, the damper will not open and the system will not ventilate.

When in the “program” mode, the control will operate the damper and fan (ventilate) according to the programmed ventilation schedule (see the section referring to programming the ventilation schedule).

To select damper operation:

1.Press the “DAMPER” button. The letter “d” will appear on the display, along with the current mode setting.

2.Use the “SET” + or – buttons to adjust the fan setting to the desired mode (“on”, “OF”, or “Pr”).

3.Press the “DAMPER” button again or leave the control alone for 10 seconds to select the indicated damper mode and return to the home state.

13

Ultra-Aire 150H Installer’s & Owner’s Manual

Image 13
Contents Ultra-Aire150H Whole House HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNERVentilating Dehumidifier DehumidificationTable of Contents TABLE OF CONTENTS1. Safety Precautions SAFETY PRECAUTIONSREAD AND SAVE THESE INSTRUCTIONS 2. Specifications FOR HVAC INSTALLER ONLY3. Installation 1. Intended Application for Ultra-Aire150H3.4 Ducting 3.4A Installing Duct Collars FOR HVAC INSTALLER ONLY3.3 Condensate Removal 3.4B Ducting for Dehumidification3.4C Ducting for Fresh Air FOR HVAC INSTALLER ONLY3.5 Quiet Installation FOR HVAC INSTALLER ONLY4. Controls 4.1 Humidity/Fan Control Panel4.2Ventilation Timer and Humidity Control Panel FOR HVAC INSTALLER ONLY4.3 Humidity Control Adjustment 4.4 Fan/Filter Switch4.6 Low Pressure Control FOR HVAC INSTALLER ONLYATTENTION INSTALLER 5.1Specifications FOR HVAC INSTALLER ONLY5.2Installation 5.2A Install Instructions5.3B Setting FOR HVAC INSTALLER AND HOMEOWNER5.3C On/Off Setting 5.3D Setting Clock Time5.3E Setting Relative Humidity Set point FOR HVAC INSTALLER ONLY AND HOMEOWNER5.3F Fan Setting and Operation 5.3H Damper Operation and Setting Ventilation5.3J Programming Notes FOR HVAC INSTALLER ONLY AND HOMEOWNER5.3L Stop Start 5.3M Low Pressure Control6. Maintenance FOR HVAC INSTALLER ONLY7. Service 7.1 Warranty7.3 Troubleshooting FOR HVAC INSTALLER ONLY7.6Compressor/Capacitor Replacement FOR HVAC INSTALLER ONLY7.5 Impeller Fan Replacement 7.4 Refrigerant Charging7.7 Remote Controls FOR HVAC INSTALLER ONLY7.7B Programmable Ventilation Timer 7.6C Replacing a Compressor, Nonburn OutElectric Schematics of the UA-150H FOR HVAC INSTALLER ONLY7.10 Low Pressure Control 7.11 Condensate Pump KitPictorial Electrical Diagrams of UA-150H FOR HVAC INSTALLER ONLYWiring Diagrams FOR HVAC INSTALLER ONLYThe UA-150H SERVICE PARTS LIST UA-150HAccessories OPTIONAL PARTS LIST UA-150HVIBRATION ISOLATION KIT UA-150H INSTRUCTIONS FOR APPLYING EXTERNAL INSULATION KIT UA-150HTHE INSULATION TO THE UA-150H ATTENTION INSTALLER WARRANTOR ULTRA-AIRE150H Dehumidifier Limited WarrantyPhone: 608-222-5301 Fax PO Box 8680 Madison, WI