7.3 Troubleshooting

FOR HVAC INSTALLER ONLY

7.3 Troubleshooting

No dehumidification, neither impeller fan nor compressor run with fan switch and ventilation timer OFF.

1.Unit unplugged or no power to outlet.

2.Humidity control set too high or defective (Sec. 3.3 & 5.7A)

3.Loose connection in internal or control wiring.

4.Defective Compressor relay.

5.Defective control transformer.

6.Low pressure Control open (Sec 3.7 & 5.10).

7.Optional Condensate Pump Safety Switch open (Sec 5.11).

No dehumidification, compressor does not run but impeller fan runs with fan switch and ventilation timer OFF and humidity control turned to ON.

1.Defective compressor run capacitor (Sec. 5.6).

2.Bad connection in compressor circuit (See Fig. 4).

3.Defective compressor overload (Sec. 5.6A).

4.Defective compressor (Sec. 5.6).

5.Defrost thermostat open (Sec. 5.8).

Impeller fan runs with fan switch and ventilation timer OFF, but compressor cycles on & off.

1.Low ambient temperature and/or humidity causing unit to cycle through defrost mode.

2.Defective compressor overload (Sec. 5.6A).

3.Defective compressor (Sec. 5.6).

4.Defrost thermostat defective (Sec. 5.8).

5.Dirty air filter(s) or airflow restricted.

6.Low refrigerant charge, causing defrost control to cycle.

7.Bad connection in compressor circuit.

Impeller fan does not run with fan switch in either position. Impeller fan does not run with ventilation timer activated. Compressor runs briefly but cycles on & off with humidity control turned to ON.

1.Loose connection in impeller fan circuit (See Fig. 4).

2.Obstruction prevents impeller fan rotation.

3.Defective impeller fan.

4.Defective impeller fan relay.

5.Defective impeller fan capacitor.

Impeller fan runs with fan switch ON. Impeller fan does not run with ventilation timer activated.

1.Defective ventilation timer.

2.Time not correct on ventilation timer.

3.Ventilation timer set to manual & switched OFF.

4.Defective fan switch.

Evaporator coil frosted continuously, low dehumidifying capacity.

1.Defrost thermostat loose or defective (Sec. 5.8).

2.Low refrigerant charge

3.Dirty air filter(s) or airflow restricted.

4.Excessively restrictive ducting connected to unit.

Unit not providing ventilation. Ventilation timer not operating correctly.

1.If timer is not functioning correctly reset timer and reprogram (Sec. 3.5).

2.Check control wire connections (check

connections at fresh air damper also).

3.Defective fresh air damper (Sec. 5.9).

4.Defective fan switch.

Unit removes some water, but not as much as expected.

1.Air temperature and/or humidity have dropped.

2.Humidity meter and or thermometer used are out of calibration.

3.Unit has entered defrost cycle (Sec. 5.8).

4.Air filter dirty (Sec. 4.1 & 4.2).

5.Defective defrost thermostat (Sec 5.8).

6.Low refrigerant charge (Sec. 5.4).

7.Air leak such as loose cover or ducting leaks.

8.Defective compressor (Sec. 5.6).

9.Restrictive ducting (Sec. 2.4).

10.Optional Condensate Pump Safety Switch open (Sec 5.11).

Unit Test to determine problem:

1.Detach field control wiring connections from main unit.

2.Connect the yellow and green pigtails from the main unit together; only the impeller fan should run. Disconnect the wires.

3.Connect the yellow and blue pigtails from the main unit together; the compressor and impeller fan should run.

4.If these tests work, the main unit is working properly. You should check the control panel and field control wiring for problems next.

5.Remove the control panel from the mounting box and detach it from the field installed control wiring. Connect the blue, yellow, and green wires from the control panel directly to the corresponding colored pigtails on the main unit. Leave the violet, white and red wires disconnected!

6.Turn on the fan switch; the impeller fan should run. Turn off the fan switch.

7.Turn on the humidity control; the compressor and impeller fan should run.

8.If these tests work, the problem is most likely in the field control wiring.

16

Ultra-Aire 150H Installer’s & Owner’s Manual

Image 16
Contents HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNER Ultra-Aire150H Whole HouseVentilating Dehumidifier DehumidificationTABLE OF CONTENTS Table of Contents1. Safety Precautions SAFETY PRECAUTIONSREAD AND SAVE THESE INSTRUCTIONS FOR HVAC INSTALLER ONLY 2. Specifications3. Installation 1. Intended Application for Ultra-Aire150HFOR HVAC INSTALLER ONLY 3.4 Ducting 3.4A Installing Duct Collars3.3 Condensate Removal 3.4B Ducting for DehumidificationFOR HVAC INSTALLER ONLY 3.4C Ducting for Fresh AirFOR HVAC INSTALLER ONLY 3.5 Quiet Installation4. Controls 4.1 Humidity/Fan Control PanelFOR HVAC INSTALLER ONLY 4.2Ventilation Timer and Humidity Control Panel4.3 Humidity Control Adjustment 4.4 Fan/Filter SwitchFOR HVAC INSTALLER ONLY 4.6 Low Pressure ControlATTENTION INSTALLER FOR HVAC INSTALLER ONLY 5.1Specifications5.2Installation 5.2A Install InstructionsFOR HVAC INSTALLER AND HOMEOWNER 5.3B Setting5.3C On/Off Setting 5.3D Setting Clock TimeFOR HVAC INSTALLER ONLY AND HOMEOWNER 5.3E Setting Relative Humidity Set point5.3F Fan Setting and Operation 5.3H Damper Operation and Setting VentilationFOR HVAC INSTALLER ONLY AND HOMEOWNER 5.3J Programming Notes5.3L Stop Start 5.3M Low Pressure ControlFOR HVAC INSTALLER ONLY 6. Maintenance7. Service 7.1 WarrantyFOR HVAC INSTALLER ONLY 7.3 TroubleshootingFOR HVAC INSTALLER ONLY 7.6Compressor/Capacitor Replacement7.5 Impeller Fan Replacement 7.4 Refrigerant ChargingFOR HVAC INSTALLER ONLY 7.7 Remote Controls7.7B Programmable Ventilation Timer 7.6C Replacing a Compressor, Nonburn OutFOR HVAC INSTALLER ONLY Electric Schematics of the UA-150H7.10 Low Pressure Control 7.11 Condensate Pump KitFOR HVAC INSTALLER ONLY Pictorial Electrical Diagrams of UA-150HFOR HVAC INSTALLER ONLY Wiring DiagramsSERVICE PARTS LIST UA-150H The UA-150HOPTIONAL PARTS LIST UA-150H AccessoriesVIBRATION ISOLATION KIT UA-150H INSTRUCTIONS FOR APPLYING EXTERNAL INSULATION KIT UA-150HTHE INSULATION TO THE UA-150H ATTENTION INSTALLER ULTRA-AIRE150H Dehumidifier Limited Warranty WARRANTORPO Box 8680 Madison, WI Phone: 608-222-5301 Fax