6.3I Intermittent or Programmed Ventilation

FOR HVAC INSTALLER ONLY AND HOMEOWNER

6.3I Intermittent or Programmed Ventilation

With the damper in program mode (denoted by “Pr” when setting the damper operation) the system will operate the ventilation function according to the current ventilation program.

There are 4 programs available for ventilation Monday through Friday. There are also 4 programs for Saturday and 4 programs for Sunday. No other choice of days is available. Each program to be used has an “on event” called “START” which brings the ventilation function on, and an “off event” called “STOP” which turns the function off. Each START and STOP must be entered in to the controller.

To set or adjust the ventilation program:

9.Pressing the “PROG” button again to move onto “program 2/stop” and begin the process again if setting the other programs. Follow the same procedure for each program.

10.To end the program process simply leave the control alone (don’t push any buttons) for about 10 seconds. The unit will remember any changes and return to “home state”.

5.3J Programming Notes

To run the ventilation program, the damper mode must be in the “program” mode (“Pr”).

The timer can be operated manually without changing the program by adjusting the damper mode from “program” to either “on” or “off”.

To delete a program after it has been entered, adjust the program so the “START” and “STOP” times are identical.

Occupants should determine ventilation times and rates. Therma- Stor LLC makes no firm recommendations concerning when to ventilate. Common ventilation schedules include constant ventilation, ventilation based on occupancy times, intermittent operation, and seasonal ventilation.

Remember the control must be on for the unit to be functioning - make sure the green power indicator “ON” is lit.

1.Press the “PROG” button two times. The display will indicate “Program 1/start” at the bottom, and the hour display will flash.

2.Use the “SET” + or – button to adjust the hour for the Program 1 start time. Be sure to pay attention to the am/pm setting.

3.Press the “PROG” button again. The display will indicate “Program 1/start” at the bottom, and now the minute display will flash.

4.Use the “SET” + or – buttons to adjust to the desired minute setting.

5.Press the “PROG” button again to move on to the “Program 1/stop” event. The display will indicate “Program 1/stop” at the bottom, and the hour display will flash.

6.Use the “SET” + or – button to adjust the hour for the Program 1 stop time. Be sure to pay attention to the am/pm setting.

7.Press the “PROG” button again. The display will indicate “Program 1/stop” at the bottom, and now the minute display will flash.

8.Use the “SET” + or – buttons to adjust to the desired minute setting.

5.3K Ventilating or Dehumidifying to Control Indoor Relative Humidity Levels

Fresh air ventilation may have a drying effect or a wetting effect on the indoor space, depending on the amount of moisture present in the outdoor air. Relative humidity is not a good indicator of outside humidity levels: use dew point measurements instead. Consider outside humidity levels when using the ventilation function of the dehumidifier.

5.3L Stop Start

During summer in hot, humid climates operating in ventilation mode will increase the moisture load in the home.

Consider reducing the amount or frequency of fresh air ventilation if indoor humidity continues to be high.

5.3M Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the low- pressure control opens and shuts off the compressor and impeller fan. It is an automatically reset control. It will close when the refrigerant pressure rises to 35 PSIG. Its primary function is to prevent damage to the compressor if a leak develops in the refrigeration system. It may also open if the unit is A) installed in a cool area (below 50 F) or B) installed where it is below 40 F and then started. Under these conditions, the unit will restart within several minutes. Until the unit warms up, it may cycle several times.

14

Ultra-Aire 150H Installer’s & Owner’s Manual

Image 14
Contents Ventilating Dehumidifier HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNERUltra-Aire150H Whole House DehumidificationTABLE OF CONTENTS Table of ContentsREAD AND SAVE THESE INSTRUCTIONS SAFETY PRECAUTIONS1. Safety Precautions 3. Installation FOR HVAC INSTALLER ONLY2. Specifications 1. Intended Application for Ultra-Aire150H3.3 Condensate Removal FOR HVAC INSTALLER ONLY3.4 Ducting 3.4A Installing Duct Collars 3.4B Ducting for DehumidificationFOR HVAC INSTALLER ONLY 3.4C Ducting for Fresh Air4. Controls FOR HVAC INSTALLER ONLY3.5 Quiet Installation 4.1 Humidity/Fan Control Panel4.3 Humidity Control Adjustment FOR HVAC INSTALLER ONLY4.2Ventilation Timer and Humidity Control Panel 4.4 Fan/Filter SwitchFOR HVAC INSTALLER ONLY 4.6 Low Pressure ControlATTENTION INSTALLER 5.2Installation FOR HVAC INSTALLER ONLY5.1Specifications 5.2A Install Instructions5.3C On/Off Setting FOR HVAC INSTALLER AND HOMEOWNER5.3B Setting 5.3D Setting Clock Time5.3F Fan Setting and Operation FOR HVAC INSTALLER ONLY AND HOMEOWNER5.3E Setting Relative Humidity Set point 5.3H Damper Operation and Setting Ventilation5.3L Stop Start FOR HVAC INSTALLER ONLY AND HOMEOWNER5.3J Programming Notes 5.3M Low Pressure Control7. Service FOR HVAC INSTALLER ONLY6. Maintenance 7.1 WarrantyFOR HVAC INSTALLER ONLY 7.3 Troubleshooting7.5 Impeller Fan Replacement FOR HVAC INSTALLER ONLY7.6Compressor/Capacitor Replacement 7.4 Refrigerant Charging7.7B Programmable Ventilation Timer FOR HVAC INSTALLER ONLY7.7 Remote Controls 7.6C Replacing a Compressor, Nonburn Out7.10 Low Pressure Control FOR HVAC INSTALLER ONLYElectric Schematics of the UA-150H 7.11 Condensate Pump KitFOR HVAC INSTALLER ONLY Pictorial Electrical Diagrams of UA-150HFOR HVAC INSTALLER ONLY Wiring DiagramsSERVICE PARTS LIST UA-150H The UA-150HOPTIONAL PARTS LIST UA-150H AccessoriesVIBRATION ISOLATION KIT UA-150H THE INSULATION TO THE UA-150H EXTERNAL INSULATION KIT UA-150HINSTRUCTIONS FOR APPLYING ATTENTION INSTALLER ULTRA-AIRE150H Dehumidifier Limited Warranty WARRANTORPO Box 8680 Madison, WI Phone: 608-222-5301 Fax