Therma-Stor Products Group Complete DEH 3000 Manual for Testing and Troubleshooting Your Dehumidifier

Page 5

2.5 Testing

Verify the wiring connections.

WARNING! ONLY CONNECT THE WHITE WIRE TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE MAY RESULT.

After checking the wiring, this short test will confirm proper hook-up.

1.Install front cover of the DEH 3000R; connect the top first, then the bottom.

2.Plug in the Ultra-Aire dehumidifier. The DEH 3000R should power up.

3.Turn the DEH 3000R ON by pressing the “ON/OFF” button.

4.Verify dehumidification operation by adjusting the RH “SETPOINT” to below the “%RH” reading on the display. Use the down “RH” button. Confirm Ultra-Aire fan and compressor operation. Both should be ON now.

Increase the RH “SETPOINT” on the display to well above the “%RH” reading on the display. Press the “RH” up arrow to increase the RH “SETPOINT”.

After running the dehumidifier compressor the DEH 3000R applies a 10 minute restart lockout on all functions. You will have to wait for the restart lockout to expire.

5.Verify FAN-only operation:

a.Check the “VENT” mode on the display, it will either be “CLOSED” or “OPEN”. If it is “CLOSED” go to the next step. If it is “OPEN”, press and hold the “VENT” key until “OPEN” flashes on the display, release the key and then press it one more time. “OPEN” will change to “CLOSED”. Don’t touch the keys for several seconds until it stops flashing.

b.Press and hold the “FAN” button until “AUTO” begins flashing on the display, release it, and then press it again to switch the fan to the “ON” setting.

c.Confirm that the Ultra-Aire fan is ON. Ultra-Aire compressor must be OFF. Ventilation damper (if used) should be CLOSED.

6.Verify optional VENT operation (if electric damper is installed):

a.Press and hold the “FAN” button until “ON” flashes on the display.

b.Release the “FAN” button, then press it again to switch fan operation to “AUTO”.

c.Press and hold the “VENT” button until “CLOSED” flashes on the display.

d. Release the “VENT” button, then press it again to switch vent mode to “OPEN”.

e. Confirm that the Ultra-Aire fan is ON. Ventilation damper is OPEN. Ultra-Aire compressor must be OFF.

f. Press and hold the “VENT” button until the “OPEN” flashes on the display.

g. Release the “VENT” button, then press it again to switch vent mode to “CLOSED”.

WARNING! DO NOT MAKE ANY OTHER CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.

7.Verify any additional optional control operations such as fan interlock or A/C lockout.

8.Proceed to the Operation section.

2.6 Troubleshooting

FOR THE HVAC PROFESSIONAL:

nNo display on initial start up.

Note: This is often the result of a drained capacitor. The capacitor will recharge once power is applied or re-applied to the unit.

Verify unit has power.

Turn unit off then on.

Disconnect the unit from power source then re-apply power to the unit. Display should now operate.

nFunction not working properly.

– Verify wiring.

– Verify voltage with voltmeter.

nDehumidifier not working properly.

– See chart below:

 

Wire connections

Operation

 

Yellow & Blue

Fan & Compressor

 

Yellow & Green

Fan Only

 

 

 

DEH 3000R Dehumidifier & Ventilation System Controller

5

Installation, Operation & Service Manual

Image 5
Contents DEH 3000R Read and Save These Instructions Specifications Table of ContentsInstallation Install InstructionsAuxiliary relay operation WiringCOM to no COM to NC Lock-out the A/C during dehumidificationDehumidifier lock-OFF or lock-ON Sensor featureTroubleshooting TestingSetting For Installer & Homeowner 3. OperationPersonal Settings reference list Setting Clock TimeTo set the operation Fan Setting and OperationDamper Operation and Ventilation, Manual Hold Mode Running the Ventilation Program Temperature Cutout ProgrammingRouting signal wires Install and Wiring InstructionsSensor connection Sensor mountingDEH 3000R PO Box 8680 Madison, WI

DEH 3000R specifications

The Therma-Stor Products Group DEH 3000R is a powerful dehumidifier expertly designed to tackle moisture control in various environments. With its robust build and advanced features, the DEH 3000R caters to both commercial and residential applications, making it a versatile choice for reducing humidity levels effectively.

One of the standout features of the DEH 3000R is its high-efficiency operation. This model is equipped with an energy-efficient compressor that allows for effective moisture removal while minimizing energy consumption. As a result, users can enjoy a more cost-effective solution for maintaining optimal humidity levels, contributing to lower electricity bills. This dehumidifier is perfect for spaces such as basements, warehouses, and even job sites where moisture can lead to mold growth and structural damage.

The DEH 3000R employs advanced technologies such as its dual exhaust system, which enhances airflow and moisture removal efficiency. The unit features a built-in condensate pump that allows for continuous drainage, eliminating the need for manual emptying of water tanks. This is particularly beneficial in large spaces or during heavy moisture events, ensuring uninterrupted dehumidification.

Portability is another key characteristic of the DEH 3000R. The unit is designed with durable wheels, making it easy to transport from one location to another. This mobility ensures that the dehumidifier can be relocated as necessary to address moisture issues in different areas. Furthermore, the unit’s compact design does not compromise its performance, making it an ideal solution for any setting.

The control panel is user-friendly, featuring intuitive controls that allow for easy adjustment of settings and monitoring of humidity levels. With its adjustable humidity settings, users can customize operation to suit specific needs, ensuring optimal comfort and protection against moisture-related issues.

In summary, the Therma-Stor Products Group DEH 3000R stands out for its efficiency, advanced technologies, portability, and ease of use. It is a dependable choice for anyone seeking effective moisture control solutions in both commercial and residential settings, protecting properties from the damaging effects of high humidity.