Bryant 558D III. Indoor Airflow and Airflow Adjustments, Direct Drive Motors

Page 19

of cooling is satis®ed, the compressor and OFM will be deen- ergized. The damper position will be determined by the supply- air temperature. When the ®rst stage of cooling is satis®ed, there is a 30-second delay before the evaporator fan shuts off. The damper then moves to the fully closed position. When using a continous fan, the damper moves to the minimum position. Additional information on economizer operation is provided in the Ventilation Sequence section on page 27.

Cooling, Units With PARABLADE Economizer

When the outdoor-air is above the enthalpy control setting, and the room thermostat calls for cooling, the compressor con- tactor is energized to start the compressor and the outdoor (condenser) fan motor. The indoor (evaporator) fan motor is energized and the economizer damper moves to the mini- mum position. After the room thermostat is satis®ed the damper will spring return to the fully closed position.

When the outdoor-air is below the enthalpy control setting and the thermostat calls for cooling, the economizer outdoor- air damper is opened proportionally to maintain between 50 and 56 F at the mixed-air sensor. If outside air alone cannot satisfy the cooling requirements, economizer cooling is inte- grated with mechanical cooling. When the room thermostat is satis®ed, the damper will spring return to the full closed position. Additional information on economizer operation is provided in the Ventilation Sequence section on page 27.

Time Guard II Device

If the unit is equipped with accessory Time Guard II recycle timer, the unit will delay 5 minutes between compressor starts.

Controls Kit

Loss-of-Charge/Low-Pressure Switch (LPS) Ð When the liq- uid line pressure drops below 7 psig, the LPS opens 24-v power

to the compressor contactor and stops the compressor. When the pressure reaches 22 psig, the switch resets and the com- pressor is allowed to come back on.

High-Pressure Switch (HPS) Ð When the refrigerant high- side pressure reaches 428 psig, the HPS opens 24-v power to the compressor contactor and stops the compressor. When the pressure drops to 320 psig, the switch resets and the com- pressor is allowed to restart.

Freeze-Protection Thermostat (FPT) Ð When the evaporator- coil leaving refrigerant temperature drops below 30 F, the FPT opens 24-v power to the compressor contactor and stops the compressor. When the leaving refrigerant temperature warms to 45 F, the switch resets and the compressor is allowed to restart.

III. INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

CAUTION: For cooling operation, the recommended air¯ow is 300 to 500 cfm per each 12,000 Btuh of rated cooling capacity. For heating operation, the air¯ow must produce a temperature rise that falls within the range stamped on the unit rating plate.

Adjust evaporator-fan speed to meet jobsite conditions. Table 3 shows fan rpm at motor pulley settings. Table 4 shows maximum amp draw of belt drive motor. Refer to Tables 5-18 to determine fan speed settings.

A. Direct Drive Motors

The evaporator-fan motor factory speed setting is shown on label diagram affixed to base unit. If other than factory set- ting is desired, refer to label diagram for motor reconnection.

Table 3 Ð Fan Rpm at Motor Pulley Settings*

UNIT

 

 

 

 

MOTOR PULLEY TURNS OPEN

 

 

 

 

558D

0

1¤2

1

11¤2

2

21¤2

3

31¤2

4

41¤2

5

036²

1090

1055

1025

990

960

925

890

860

825

795

760

048²

1185

1150

1115

1080

1045

1015

980

945

910

875

840

060²

1300

1260

1220

1180

1140

1100

1060

1020

980

940

900

072**

1460

1420

1380

1345

1305

1265

1225

1185

1150

1110

1070

*Approximate fan rpm shown.

²Indicates alternate motor and drive package. **Indicates standard motor and drive package.

Ð19Ð

Image 19
Contents Installation Important Ð Read Before InstallingContents Safety ConsiderationsWeight Durablade Parablade STD Unit Economizer Weight Corner WeightII. Unit Duct Connections Locate the UnitClearance Slab Mount Horizontal Units OnlyCRRFCURB001A00 AccessoryRoof Curb Unit SizeSpecications Field Duct Connections Maximum Allowable DifferenceIV. Field Connections External Trap Condensate DrainInternal Trap Condensate Drain Low-Voltage Connections Typical Component Location RLA LRA FLA Electrical DataSize TypeRLA HacrMocp NECOptional Outdoor-Air Damper Installation Accessory InstallationOptional Parablade Economizer Optional Durablade EconomizerHorizontal Durablade Economizer Installation Degree Rotation Outdoor-Air Thermostat Enthalpy Control Installation AT 50% RH Control Control Point Approx CurvePRE-START-UP START-UP Heating Section START-UP and AdjustmentsII. Cooling Section START-UP and Adjustments Fan Rpm at Motor Pulley Settings III. Indoor Airflow and Airflow AdjustmentsDirect Drive Motors Standard Direct Drive Motor Airflow Motor DataESP Alternate Belt Drive Motor Airflow 1400 610 252 673 315 732 378 791 441 Cfm Rpm WattsWatts Rpm 1200 542 168 616 221 678 278 739 336 1300 576 210 644 263 704 326 764 389Standard Belt Drive Motor Airflow Ð24Ð 1500 609 273 670 326 729 394 788 462 Watts Rpm 1200 514 158 590 210 657 263 723 315 828 4411300 545 189 615 242 680 305 744 368 1400 577 221 642 284 704 347 766 4101364 1676 1432 1931 1800 765 460 821 521 Cfm Rpm Watts 1500 658 276 722 337 840 4701343 1615 1431 1829 1600 693 327 754 388 867 531 1350 1645 1424 1921 1700 729 388 787 450 895 593Ventilation Sequence Belt Drive MotorsEvaporator Coil Care and MaintenanceService Cleaning AIR FilterFan-Motor Bearings III. CONDENSER-FAN Adjustment FigII. Lubrication CompressorsIV. Refrigerant Charge Replacement PartsCooling Charging Chart 558D036 Cooling Troubleshooting TroubleshootingDamper does not Durablade Economizer TroubleshootingEnthalpy readings Parablade Economizer TroubleshootingCAP AHALSM MTRPage Page Call for Free Catalog Service TrainingPage Pressures TemperaturesPreliminary Information III. START-UP Electrical

558D specifications

The Bryant 558D represents a leading-edge model in the realm of advanced heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and light commercial applications, this unit brings together efficiency, performance, and reliability, making it a go-to choice for homeowners and contractors alike.

One of the standout features of the Bryant 558D is its high-efficiency rating. With SEER (Seasonal Energy Efficiency Ratio) ratings that can reach up to 18, it allows homeowners to enjoy significant savings on electricity bills while maintaining a comfortable indoor environment. The system is powered by advanced compressors that ensure optimal performance across various climate conditions, providing consistent cooling and heating as needed.

In terms of technology, the Bryant 558D incorporates a two-stage cooling system, which allows for better temperature control and humidity management. This technology enhances comfort by preventing the system from frequently starting and stopping, thus reducing wear and tear while extending the unit's lifespan. The variable-speed blower motor further contributes to this efficiency by adjusting its speed to meet the precise needs of the space, ensuring optimal air distribution and comfort.

Durability is another hallmark of the Bryant 558D. The unit is built with high-quality materials, including a galvanized steel cabinet coated with a sleek, weather-resistant finish that protects against rust and environmental wear. Its compact design makes installation seamless, allowing it to fit into various spaces without significant modifications.

The Bryant 558D also features smart technology compatibility, allowing users to integrate it with modern home automation systems. This connectivity provides homeowners with remote control capabilities, enabling them to regulate their home’s temperature via smartphone applications. This not only adds to convenience but also supports energy management strategies, as users can adjust settings based on occupancy and lifestyle patterns.

Finally, noise levels have been an important consideration in the design of the Bryant 558D. With innovative sound-dampening features, the unit operates quietly, making it an ideal choice for residential areas where noise sensitivity is paramount.

Overall, the Bryant 558D stands out as a sophisticated solution for heating and cooling needs, combining energy efficiency, advanced technology, durability, and user-friendly features. It is an excellent investment for those looking to enhance their home comfort while also being mindful of energy consumption.