Bryant 558D II. Lubrication, Compressors, Fan-Motor Bearings, III. CONDENSER-FAN Adjustment Fig

Page 29

CONDENSER

FAN

Fig. 36 Ð Condenser Coil Cleaning

Two-Row Coils (size 072)

NOTE: Save all screws removed in this section. The screws must be used when reinstalling the equipment.

1.To access 2-row coils, remove screws securing condenser- fan grille to condenser coil top cover. Place grille on top of condenser coil top cover as shown in Fig. 36. It is not necessary to remove the top cover.

2.Remove 3 screws on right side of compressor access panel. Remove one screw securing condenser coil top cover to compressor access panel. Remove lower screw secur- ing condenser coil to compressor mounting plate. See Fig. 11.

3.Remove 4 screws securing control box access cover. Re- move 3 screws (located in front of the control box ac- cess cover) securing condenser coil top cover.

4.Remove screws securing low-voltage access panel. Re- move 2 screws inside the 24-v barrier access panel. Tilt sheet metal (located on left side of the 24-v connec- tions) back 45 degrees.

5.Remove screw securing refrigerant service port access panel.

6.Remove 2 U-clips securing 2-row coils together at hair- pin end.

7.Remove screws securing two corner posts. Remove two corner posts.

8.Use right corner post to prop up right side of con- denser coil top cover. Slide condenser coil partially out of condenser fan housing. See Fig. 37.

9.Use left corner post to prop up left side of condenser coil top cover.

10.Carefully separate the outer coil section 3 to 4 in. from the inner coil section. See Fig. 38.

11.Use a water hose or other suitable equipment to ¯ush down between the 2 coil section to remove dirt and de- bris. Clean the outer surfaces with a stiff brush in the normal manner.

12.Secure inner and outer coil together with U-clip.

13.Reposition the outer and inner coil section.

14.Reverse the procedure outlined above to reinstall equipment.

Fig. 37 Ð Propping Up Condenser Coil Top Cover

Fig. 38 Ð Separating Coil Sections

II. LUBRICATION

A. Compressors

Each compressor is charged with correct amount of oil at the factory.

B. Fan-Motor Bearings

Fan-motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser- or evaporator-fan motors is required.

III. CONDENSER-FAN ADJUSTMENT (Fig. 39)

Shut off unit power supply. Remove condenser-fan assembly (grille, motor, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 39. Tighten setscrews and re- place condenser-fan assembly.

Ð29Ð

Image 29
Contents Contents Important Ð Read Before InstallingSafety Considerations InstallationWeight Durablade Parablade STD Unit Economizer Weight Corner WeightClearance Locate the UnitSlab Mount Horizontal Units Only II. Unit Duct ConnectionsRoof Curb AccessoryUnit Size CRRFCURB001A00Specications IV. Field Connections Maximum Allowable DifferenceExternal Trap Condensate Drain Field Duct ConnectionsInternal Trap Condensate Drain Low-Voltage Connections Typical Component Location Size Electrical DataType RLA LRA FLAMocp HacrNEC RLAOptional Outdoor-Air Damper Installation Accessory InstallationOptional Parablade Economizer Optional Durablade EconomizerHorizontal Durablade Economizer Installation Degree Rotation Outdoor-Air Thermostat Enthalpy Control Installation AT 50% RH Control Control Point Approx CurvePRE-START-UP START-UP Heating Section START-UP and AdjustmentsII. Cooling Section START-UP and Adjustments Direct Drive Motors III. Indoor Airflow and Airflow AdjustmentsFan Rpm at Motor Pulley Settings ESP Motor DataStandard Direct Drive Motor Airflow Alternate Belt Drive Motor Airflow Watts Rpm 1200 542 168 616 221 678 278 739 336 Cfm Rpm Watts1300 576 210 644 263 704 326 764 389 1400 610 252 673 315 732 378 791 441Standard Belt Drive Motor Airflow Ð24Ð 1300 545 189 615 242 680 305 744 368 Watts Rpm 1200 514 158 590 210 657 263 723 315 828 4411400 577 221 642 284 704 347 766 410 1500 609 273 670 326 729 394 788 4621343 1615 1431 1829 1600 693 327 754 388 867 531 Cfm Rpm Watts 1500 658 276 722 337 840 4701350 1645 1424 1921 1700 729 388 787 450 895 593 1364 1676 1432 1931 1800 765 460 821 521Ventilation Sequence Belt Drive MotorsService Cleaning Care and MaintenanceAIR Filter Evaporator CoilII. Lubrication III. CONDENSER-FAN Adjustment FigCompressors Fan-Motor BearingsIV. Refrigerant Charge Replacement PartsCooling Charging Chart 558D036 Cooling Troubleshooting TroubleshootingDamper does not Durablade Economizer TroubleshootingEnthalpy readings Parablade Economizer TroubleshootingLSM AHAMTR CAPPage Page Call for Free Catalog Service TrainingPage Preliminary Information TemperaturesIII. START-UP Electrical Pressures

558D specifications

The Bryant 558D represents a leading-edge model in the realm of advanced heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and light commercial applications, this unit brings together efficiency, performance, and reliability, making it a go-to choice for homeowners and contractors alike.

One of the standout features of the Bryant 558D is its high-efficiency rating. With SEER (Seasonal Energy Efficiency Ratio) ratings that can reach up to 18, it allows homeowners to enjoy significant savings on electricity bills while maintaining a comfortable indoor environment. The system is powered by advanced compressors that ensure optimal performance across various climate conditions, providing consistent cooling and heating as needed.

In terms of technology, the Bryant 558D incorporates a two-stage cooling system, which allows for better temperature control and humidity management. This technology enhances comfort by preventing the system from frequently starting and stopping, thus reducing wear and tear while extending the unit's lifespan. The variable-speed blower motor further contributes to this efficiency by adjusting its speed to meet the precise needs of the space, ensuring optimal air distribution and comfort.

Durability is another hallmark of the Bryant 558D. The unit is built with high-quality materials, including a galvanized steel cabinet coated with a sleek, weather-resistant finish that protects against rust and environmental wear. Its compact design makes installation seamless, allowing it to fit into various spaces without significant modifications.

The Bryant 558D also features smart technology compatibility, allowing users to integrate it with modern home automation systems. This connectivity provides homeowners with remote control capabilities, enabling them to regulate their home’s temperature via smartphone applications. This not only adds to convenience but also supports energy management strategies, as users can adjust settings based on occupancy and lifestyle patterns.

Finally, noise levels have been an important consideration in the design of the Bryant 558D. With innovative sound-dampening features, the unit operates quietly, making it an ideal choice for residential areas where noise sensitivity is paramount.

Overall, the Bryant 558D stands out as a sophisticated solution for heating and cooling needs, combining energy efficiency, advanced technology, durability, and user-friendly features. It is an excellent investment for those looking to enhance their home comfort while also being mindful of energy consumption.