Bryant 558D installation instructions Internal Trap Condensate Drain

Page 7

Fig. 7 Ð Internal Trap Condensate Drain

NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A 4-in. trap is recommended.

Fig. 8 Ð External Trap Condensate Drain

3.Use ¯exible transition between rigid ductwork and unit to prevent transmission of vibration. The transition may be screwed or bolted to duct ¯anges. Use suitable gas- kets to ensure weather- and airtight seal.

4.When horizontal return is used, install external ®eld- supplied air ®lter(s) in return-air ductwork where it is easily accessible for service. Recommended ®lter sizes are shown in Table 1.

5.Size all ductwork for maximum required air¯ow (either heating or cooling) for unit being installed. Avoid abrupt duct size increases or decreases.

6.Adequately insulate and weatherproof all ductwork located outdoors. Insulate ducts passing through un- conditioned space, and use vapor barrier in accordance with latest issue of SMACNA (Sheet Metal and Air Con- ditioning Contractors National Association) and ACCA (Air Conditioning Contractors National Association) mini- mum installation standards for heating and air condi- tioning systems. Secure all ducts to building structure.

A minimum clearance to combustibles is not required around ductwork on vertical discharge units. On hori- zontal discharge units, a minimum clearance of one in. is required for the ®rst 12 in. of ductwork.

7.Flash, weatherproof and vibration-isolate all openings in building structure in accordance with local codes and good building practices.

Fig. 9 Ð Location of Coil Area Not to be Drilled C. Electrical Connections

WARNING: The unit cabinet must have an uninter- rupted, unbroken, electrical ground to minimize the pos- sibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire con- nected to the unit ground lug in the control compart- ment or conduit approved for electrical ground when installed in accordance with NEC ANSI (American National Standards Institute)/NFPA, latest edition, (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1); and local electrical codes. Failure to adhere to this warning could result in per- sonal injury.

CAUTION: Failure to obey the following precau- tions could result in damage to the unit being installed:

Field Power Supply (Fig. 10 and 11)

1.Make all electrical connections in accordance with NEC ANSI/NFPA, latest edition, and local electrical codes gov- erning such wiring. In Canada, all electrical connec- tions must be in accordance with CSA Standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.A unit disconnect switch is required within sight from the unit. The disconnect switch may be mounted on the unit corner post. When mounting disconnect switch, be sure the unit rating plate is not obstructed.

3.Use only copper conductor for connections between ®eld- supplied electrical disconnect switch and unit. The use of aluminum wire is not recommended. Maximum wire size is number 2 AWG (American Wire Gage) on units without heat. The maximum wire size is number 2/0 AWG on units with heat.

4.Insulate low-voltage wires for highest voltage con- tained within conduit when low-voltage control wires are run in same conduit as high-voltage wires.

5.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

High-Voltage Connections (Fig. 10)

The unit must have a separate electrical service with a ®eld- supplied, waterproof, fused, disconnect switch mounted at, or within sight of, the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing. Be sure disconnect switch does not obstruct unit rating plate.

Ð7Ð

Image 7
Contents Installation Important Ð Read Before InstallingContents Safety ConsiderationsWeight Durablade Parablade STD Unit Economizer Weight Corner WeightII. Unit Duct Connections Locate the UnitClearance Slab Mount Horizontal Units OnlyCRRFCURB001A00 AccessoryRoof Curb Unit SizeSpecications Field Duct Connections Maximum Allowable DifferenceIV. Field Connections External Trap Condensate DrainInternal Trap Condensate Drain Low-Voltage Connections Typical Component Location RLA LRA FLA Electrical DataSize TypeRLA HacrMocp NECOptional Outdoor-Air Damper Installation Accessory InstallationOptional Parablade Economizer Optional Durablade EconomizerHorizontal Durablade Economizer Installation Degree Rotation Outdoor-Air Thermostat Enthalpy Control Installation AT 50% RH Control Control Point Approx CurvePRE-START-UP START-UP Heating Section START-UP and AdjustmentsII. Cooling Section START-UP and Adjustments Fan Rpm at Motor Pulley Settings III. Indoor Airflow and Airflow AdjustmentsDirect Drive Motors Standard Direct Drive Motor Airflow Motor DataESP Alternate Belt Drive Motor Airflow 1400 610 252 673 315 732 378 791 441 Cfm Rpm WattsWatts Rpm 1200 542 168 616 221 678 278 739 336 1300 576 210 644 263 704 326 764 389Standard Belt Drive Motor Airflow Ð24Ð 1500 609 273 670 326 729 394 788 462 Watts Rpm 1200 514 158 590 210 657 263 723 315 828 4411300 545 189 615 242 680 305 744 368 1400 577 221 642 284 704 347 766 4101364 1676 1432 1931 1800 765 460 821 521 Cfm Rpm Watts 1500 658 276 722 337 840 4701343 1615 1431 1829 1600 693 327 754 388 867 531 1350 1645 1424 1921 1700 729 388 787 450 895 593Ventilation Sequence Belt Drive MotorsEvaporator Coil Care and MaintenanceService Cleaning AIR FilterFan-Motor Bearings III. CONDENSER-FAN Adjustment FigII. Lubrication CompressorsIV. Refrigerant Charge Replacement PartsCooling Charging Chart 558D036 Cooling Troubleshooting TroubleshootingDamper does not Durablade Economizer TroubleshootingEnthalpy readings Parablade Economizer TroubleshootingCAP AHALSM MTRPage Page Call for Free Catalog Service TrainingPage Pressures TemperaturesPreliminary Information III. START-UP Electrical

558D specifications

The Bryant 558D represents a leading-edge model in the realm of advanced heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and light commercial applications, this unit brings together efficiency, performance, and reliability, making it a go-to choice for homeowners and contractors alike.

One of the standout features of the Bryant 558D is its high-efficiency rating. With SEER (Seasonal Energy Efficiency Ratio) ratings that can reach up to 18, it allows homeowners to enjoy significant savings on electricity bills while maintaining a comfortable indoor environment. The system is powered by advanced compressors that ensure optimal performance across various climate conditions, providing consistent cooling and heating as needed.

In terms of technology, the Bryant 558D incorporates a two-stage cooling system, which allows for better temperature control and humidity management. This technology enhances comfort by preventing the system from frequently starting and stopping, thus reducing wear and tear while extending the unit's lifespan. The variable-speed blower motor further contributes to this efficiency by adjusting its speed to meet the precise needs of the space, ensuring optimal air distribution and comfort.

Durability is another hallmark of the Bryant 558D. The unit is built with high-quality materials, including a galvanized steel cabinet coated with a sleek, weather-resistant finish that protects against rust and environmental wear. Its compact design makes installation seamless, allowing it to fit into various spaces without significant modifications.

The Bryant 558D also features smart technology compatibility, allowing users to integrate it with modern home automation systems. This connectivity provides homeowners with remote control capabilities, enabling them to regulate their home’s temperature via smartphone applications. This not only adds to convenience but also supports energy management strategies, as users can adjust settings based on occupancy and lifestyle patterns.

Finally, noise levels have been an important consideration in the design of the Bryant 558D. With innovative sound-dampening features, the unit operates quietly, making it an ideal choice for residential areas where noise sensitivity is paramount.

Overall, the Bryant 558D stands out as a sophisticated solution for heating and cooling needs, combining energy efficiency, advanced technology, durability, and user-friendly features. It is an excellent investment for those looking to enhance their home comfort while also being mindful of energy consumption.