Bryant 558D Care and Maintenance, AIR Filter, Service Cleaning, Evaporator Coil, Condenser Coil

Page 28

Whenever the evaporator fan is energized (during heating, cooling or continuous fan), 24-v power is on terminal IFO on the economizer or two-position damper control board. The damper motor will be energized with 12-vdc power and the damper will drive open until SW3 on the damper is deacti- vated. The damper motor will stop, and damper will remain in the minimum ventilation position until the evaporator fan is shut off. When the evaporator fan is shut off, the damper motor is again energized and the damper runs closed until SW2 is activated and the damper motor turns off.

CARE AND MAINTENANCE

To ensure continuing high performance, and to minimize the possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina- tion heating/cooling unit should be inspected at least once each year by a quali®ed service person.

NOTE TO EQUIPMENT OWNER: Consult your local dealer about the availability of a maintenance contract.

WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not pos- sess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User's Information Manual. FAILURE TO HEED THIS WARNING COULD RESULT IN SE- RIOUS PERSONAL INJURY AND POSSIBLE DAM- AGE TO THIS EQUIPMENT.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air ®lters each month. Clean or replace when necessary.

2.Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect fan motor and wheel. Clean and lubricate as necessary.

4.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.

5.Check and inspect accessory electric heaters before each heating season. Clean and adjust when necessary.

6.Check and clean outdoor-air inlet screen if needed.

WARNING: Failure to follow these warnings could re- sult in serious personal injury:

1.Turn off electrical power to the unit before per- forming any maintenance or service on the unit.

2.Use extreme caution when removing panels and parts. As with any mechanical equipment, per- sonal injury can result from sharp edges, etc.

3.Never place anything combustible either on, or in contact with, the unit.

I. AIR FILTER

CAUTION: Never operate the unit without a suit- able air ®lter in the return-air duct system. Always re- place the ®lter with the same dimensional size and type as originally installed. See Table 1 for recommended ®l- ter sizes.

Inspect air ®lters at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice dur- ing each heating and cooling season, or whenever the ®lter(s) becomes clogged with dust and lint.

When necessary, replace ®lters with the same dimensional size and type as originally provided.

SERVICE

CAUTION: When servicing unit, shut off all electri- cal power to unit to avoid shock hazard or injury from rotating parts.

I. CLEANING

Inspect unit interior at the beginning of each heating and cool- ing season and as operating conditions require.

A.Evaporator Coil

1.Turn unit power off. Remove evaporator coil access panel.

2.If accessory economizer is installed, remove economizer by disconnecting Molex plug and economizer mounting screws. Refer to Optional Economizer sections on page 13 or Accessory Economizer Installation Instruc- tions for further details.

3.Slide ®lters out of unit.

4.Clean coil using a commercial coil cleaner or dish- washer detergent in a pressurized spray canister. Wash both sides of coil and ¯ush with clean water. For best results, back¯ush toward return-air section to remove foreign material.

5.Flush condensate pan.

6.Reinstall economizer and ®lters.

7.Reconnect wiring.

8.Replace access panels.

B.Condenser Coil

Inspect coil monthly. Clean condenser coil annually, and as required by location or outdoor-air conditions.

One-Row Coils (sizes 036-060)

To access one-row coils, remove screws securing condenser- fan grille to condenser coil top cover. Place grille on top of condenser coil top cover as shown in Fig. 36. It is not neces- sary to remove the top cover.

Use a water hose or other suitable equipment to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.

Reverse the procedure outlined above to reinstall the condenser- fan grille and condenser coil top cover.

Ð28Ð

Image 28
Contents Important Ð Read Before Installing ContentsSafety Considerations InstallationSTD Unit Economizer Weight Corner Weight Weight Durablade ParabladeLocate the Unit ClearanceSlab Mount Horizontal Units Only II. Unit Duct ConnectionsAccessory Roof CurbUnit Size CRRFCURB001A00Specications Maximum Allowable Difference IV. Field ConnectionsExternal Trap Condensate Drain Field Duct ConnectionsInternal Trap Condensate Drain Low-Voltage Connections Typical Component Location Electrical Data SizeType RLA LRA FLAHacr MocpNEC RLAAccessory Installation Optional Outdoor-Air Damper InstallationOptional Durablade Economizer Optional Parablade EconomizerHorizontal Durablade Economizer Installation Degree Rotation Outdoor-Air Thermostat Enthalpy Control Installation Control Control Point Approx Curve AT 50% RHSTART-UP Heating Section START-UP and Adjustments PRE-START-UPII. Cooling Section START-UP and Adjustments Fan Rpm at Motor Pulley Settings III. Indoor Airflow and Airflow AdjustmentsDirect Drive Motors Standard Direct Drive Motor Airflow Motor DataESP Alternate Belt Drive Motor Airflow Cfm Rpm Watts Watts Rpm 1200 542 168 616 221 678 278 739 3361300 576 210 644 263 704 326 764 389 1400 610 252 673 315 732 378 791 441Standard Belt Drive Motor Airflow Ð24Ð Watts Rpm 1200 514 158 590 210 657 263 723 315 828 441 1300 545 189 615 242 680 305 744 3681400 577 221 642 284 704 347 766 410 1500 609 273 670 326 729 394 788 462Cfm Rpm Watts 1500 658 276 722 337 840 470 1343 1615 1431 1829 1600 693 327 754 388 867 5311350 1645 1424 1921 1700 729 388 787 450 895 593 1364 1676 1432 1931 1800 765 460 821 521Belt Drive Motors Ventilation SequenceCare and Maintenance Service CleaningAIR Filter Evaporator CoilIII. CONDENSER-FAN Adjustment Fig II. LubricationCompressors Fan-Motor BearingsReplacement Parts IV. Refrigerant ChargeCooling Charging Chart 558D036 Troubleshooting Cooling TroubleshootingDurablade Economizer Troubleshooting Damper does notParablade Economizer Troubleshooting Enthalpy readingsAHA LSMMTR CAPPage Page Service Training Call for Free CatalogPage Temperatures Preliminary InformationIII. START-UP Electrical Pressures

558D specifications

The Bryant 558D represents a leading-edge model in the realm of advanced heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and light commercial applications, this unit brings together efficiency, performance, and reliability, making it a go-to choice for homeowners and contractors alike.

One of the standout features of the Bryant 558D is its high-efficiency rating. With SEER (Seasonal Energy Efficiency Ratio) ratings that can reach up to 18, it allows homeowners to enjoy significant savings on electricity bills while maintaining a comfortable indoor environment. The system is powered by advanced compressors that ensure optimal performance across various climate conditions, providing consistent cooling and heating as needed.

In terms of technology, the Bryant 558D incorporates a two-stage cooling system, which allows for better temperature control and humidity management. This technology enhances comfort by preventing the system from frequently starting and stopping, thus reducing wear and tear while extending the unit's lifespan. The variable-speed blower motor further contributes to this efficiency by adjusting its speed to meet the precise needs of the space, ensuring optimal air distribution and comfort.

Durability is another hallmark of the Bryant 558D. The unit is built with high-quality materials, including a galvanized steel cabinet coated with a sleek, weather-resistant finish that protects against rust and environmental wear. Its compact design makes installation seamless, allowing it to fit into various spaces without significant modifications.

The Bryant 558D also features smart technology compatibility, allowing users to integrate it with modern home automation systems. This connectivity provides homeowners with remote control capabilities, enabling them to regulate their home’s temperature via smartphone applications. This not only adds to convenience but also supports energy management strategies, as users can adjust settings based on occupancy and lifestyle patterns.

Finally, noise levels have been an important consideration in the design of the Bryant 558D. With innovative sound-dampening features, the unit operates quietly, making it an ideal choice for residential areas where noise sensitivity is paramount.

Overall, the Bryant 558D stands out as a sophisticated solution for heating and cooling needs, combining energy efficiency, advanced technology, durability, and user-friendly features. It is an excellent investment for those looking to enhance their home comfort while also being mindful of energy consumption.