Table 20 Ð Durablade Economizer Troubleshooting

 

PROBLEM

 

CAUSE

 

REMEDY

Damper does not

 

Indoor (evaporator) fan is off.

1.

Check to ensure that 24 vac is present at terminal C1 on the IFC or that

open.

 

 

 

24 vac is present at the IFO terminal. Check whether 24 vac is present at

 

 

 

 

 

PL6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is not present, check

 

 

 

 

 

wiring (see unit label diagram).

 

 

 

 

2.

Check proper thermostat connection to G on the connection board.

 

 

 

No power to economizer

1. Check that SW3 is properly making contact with the damper blade. Check

 

 

 

motor.

 

that SW1 is in the NC (normally closed) position.

 

 

 

 

2.

Check diode D18. If diode is not functioning properly, replace D18.

 

 

 

 

3.

Con®rm that the economizer control board is grounded properly at PL6-4

 

 

 

 

 

(brown wire) and at brown terminal of the economizer control board

 

 

 

 

 

(brown wire). The economizer motor must also be grounded properly at the

 

 

 

 

 

negative motor terminal (brown wire).

 

 

 

 

4.

Verify SW1 and SW3 are working and wired properly (see unit label

 

 

 

 

 

diagram).

 

 

 

 

5.

Check for 24 vac input at both PL6-1 (red wire) and PL6-3 (black wire). If

 

 

 

 

 

24 vac not present, check unit wiring (see unit label diagram). If 24 vac is

 

 

 

 

 

found in both places, check for 24 vac at the yellow terminal of the econo-

 

 

 

 

 

mizer control board (yellow wire). If 24 vac power is not present, replace the

 

 

 

 

 

economizer control board.

 

 

 

Economizer motor failure.

If the indoor (evaporator) fan and economizer motor are energized, verify that

 

 

 

 

there is a minimum of 18 vdc at the positive motor terminal. If the motor is not

 

 

 

 

operating, replace the motor.

Economizer op-

 

OAT or EC set too high.

1.

Set at correct temperature (3 F below indoor space temperature).

eration limited to

 

 

2.

Check OAT or EC by setting above outdoor temperature or humidity level. If

minimum position.

 

 

 

the OAT or EC switches do not close, replace OAT or EC.

 

 

 

Verify economizer control

1.

Perform the following tests when OAT or EC is closed, Y1 is called for and

 

 

 

board is correctly wired and

 

damper is at minimum position. Con®rm 24 vac on gray terminal of the

 

 

 

works properly.

 

economizer control board (gray wire). If 24 vac is not present, check wiring

 

 

 

 

 

(see unit label diagram).

 

 

 

 

2.

Verify that SW1 and SW3 are wired correctly and working properly (see unit

 

 

 

 

 

label diagram).

 

 

 

 

3.

Check to ensure that 24 vac exists at PL6-2 (blue wire). If 24 vac is not

 

 

 

 

 

present, check wiring (see unit wiring label diagram).

 

 

 

 

4.

Check 24 vac output at PL6-10 (white wire). If 24 vac is not present, replace

 

 

 

 

 

economizer control board.

 

 

 

Check SAT.

1.

After verifying that the OAT and EC settings and the economizer control

 

 

 

 

 

board wiring are correct, check to ensure that the 24 vac terminal of the SAT

 

 

 

 

 

has 24 vac (white wire). If OAT, EC, and control board are functioning and

 

 

 

 

 

wired properly and no 24 vac exists, check wiring (see unit label diagram).

 

 

 

 

2.

If supply-air temperature is greater than 57 F, 24 vac should be found at

 

 

 

 

 

terminal T2 on the SAT (pink wire). If 24 vac is not present, replace SAT.

Damper does not

 

Incorrect wiring of

1.

Verify that SW2 and SW4 are wired and working properly (see unit label

close.

 

economizer.

 

diagram).

 

 

 

 

2.

Check diode D19. If diode is not functioning properly, replace D19.

 

 

 

Verify economizer control

1.

After verifying that the wiring is correct, modulate the damper to the mini-

 

 

 

board is functioning properly.

 

mum position. Remove the calls for G.

 

 

 

 

2.

If the damper does not move, check for 24 vac at PL6-1 (red wire). If 24 vac

 

 

 

 

 

is not present, check wiring (see unit label diagram).

 

 

 

 

3.

If damper still does not move, check for 24 vac at blue terminal of econo-

 

 

 

 

 

mizer control board (blue wire). If 24 vac is not present, replace the econo-

 

 

 

 

 

mizer circuit board.

 

 

 

Check SAT.

1.

After verifying that the wiring is correct and the economizer control board is

 

 

 

 

 

functioning properly, place the OAT or EC switch in the closed position.

 

 

 

 

 

Place a call for Y1 and open the damper to the fully open position. Con®rm

 

 

 

 

 

that the 24 vac terminal of the SAT has 24 vac (white wire). If 24 vac is not

 

 

 

 

 

present, check wiring (see unit label diagram).

 

 

 

 

2.

If supply-air temperature is less than 52 F, 24 vac should be found at

 

 

 

 

 

terminal T1 on the SAT (violet wire). If 24 vac not found, replace SAT.

 

 

 

Economizer motor failure.

If economizer control board and SAT are functioning properly, verify that there is

 

 

 

 

a minimum of 18 vdc at the positive motor terminal. If a minimum of 18 vdc is

 

 

 

 

present and the motor is still not operating, replace the motor.

Economizer

 

Verify that close-on-power-

1.

Check voltage potential across batteries. If lower than 14 vdc, replace close-

damper does not

 

loss and economizer control

 

on-power-loss power supply (9-v alkaline batteries). It is recommended that

close on power

 

board are functioning

 

you check this emergency power supply on a regular basis or whenever the

loss.

 

properly.

 

®lters are changed.

 

 

 

 

2.

If the close-on-power-loss and economizer control board are functioning

 

 

 

 

 

properly, check for 14 vdc or higher at the blue terminal of the economizer

 

 

 

 

 

control board (blue wire) when power is disconnected from unit. If 14 vdc is

 

 

 

 

 

not present, replace the control board.

 

LEGEND

 

 

 

C1

Ð Common Power

 

 

 

EC

Ð Enthalpy Control

 

 

 

IFC

Ð Indoor (Evaporator) Fan Contactor

 

 

IFO

Ð Indoor (Evaporator) Fan On

 

 

OAT Ð Outdoor-Air Thermostat

 

 

PL

Ð Plug

 

 

 

SAT

Ð Supply-Air Thermostat

 

 

SW

Ð Economizer Position Switch

 

 

Ð33Ð

Image 33
Contents Contents Important Ð Read Before InstallingSafety Considerations InstallationWeight Durablade Parablade STD Unit Economizer Weight Corner WeightClearance Locate the UnitSlab Mount Horizontal Units Only II. Unit Duct ConnectionsRoof Curb AccessoryUnit Size CRRFCURB001A00Specications IV. Field Connections Maximum Allowable DifferenceExternal Trap Condensate Drain Field Duct ConnectionsInternal Trap Condensate Drain Low-Voltage Connections Typical Component Location Size Electrical DataType RLA LRA FLAMocp HacrNEC RLAOptional Outdoor-Air Damper Installation Accessory InstallationOptional Parablade Economizer Optional Durablade EconomizerHorizontal Durablade Economizer Installation Degree Rotation Outdoor-Air Thermostat Enthalpy Control Installation AT 50% RH Control Control Point Approx CurvePRE-START-UP START-UP Heating Section START-UP and AdjustmentsII. Cooling Section START-UP and Adjustments III. Indoor Airflow and Airflow Adjustments Fan Rpm at Motor Pulley SettingsDirect Drive Motors Motor Data Standard Direct Drive Motor AirflowESP Alternate Belt Drive Motor Airflow Watts Rpm 1200 542 168 616 221 678 278 739 336 Cfm Rpm Watts1300 576 210 644 263 704 326 764 389 1400 610 252 673 315 732 378 791 441Standard Belt Drive Motor Airflow Ð24Ð 1300 545 189 615 242 680 305 744 368 Watts Rpm 1200 514 158 590 210 657 263 723 315 828 4411400 577 221 642 284 704 347 766 410 1500 609 273 670 326 729 394 788 4621343 1615 1431 1829 1600 693 327 754 388 867 531 Cfm Rpm Watts 1500 658 276 722 337 840 4701350 1645 1424 1921 1700 729 388 787 450 895 593 1364 1676 1432 1931 1800 765 460 821 521Ventilation Sequence Belt Drive MotorsService Cleaning Care and MaintenanceAIR Filter Evaporator CoilII. Lubrication III. CONDENSER-FAN Adjustment FigCompressors Fan-Motor BearingsIV. Refrigerant Charge Replacement PartsCooling Charging Chart 558D036 Cooling Troubleshooting TroubleshootingDamper does not Durablade Economizer TroubleshootingEnthalpy readings Parablade Economizer TroubleshootingLSM AHAMTR CAPPage Page Call for Free Catalog Service TrainingPage Preliminary Information TemperaturesIII. START-UP Electrical Pressures

558D specifications

The Bryant 558D represents a leading-edge model in the realm of advanced heating, ventilation, and air conditioning (HVAC) systems. Designed for both residential and light commercial applications, this unit brings together efficiency, performance, and reliability, making it a go-to choice for homeowners and contractors alike.

One of the standout features of the Bryant 558D is its high-efficiency rating. With SEER (Seasonal Energy Efficiency Ratio) ratings that can reach up to 18, it allows homeowners to enjoy significant savings on electricity bills while maintaining a comfortable indoor environment. The system is powered by advanced compressors that ensure optimal performance across various climate conditions, providing consistent cooling and heating as needed.

In terms of technology, the Bryant 558D incorporates a two-stage cooling system, which allows for better temperature control and humidity management. This technology enhances comfort by preventing the system from frequently starting and stopping, thus reducing wear and tear while extending the unit's lifespan. The variable-speed blower motor further contributes to this efficiency by adjusting its speed to meet the precise needs of the space, ensuring optimal air distribution and comfort.

Durability is another hallmark of the Bryant 558D. The unit is built with high-quality materials, including a galvanized steel cabinet coated with a sleek, weather-resistant finish that protects against rust and environmental wear. Its compact design makes installation seamless, allowing it to fit into various spaces without significant modifications.

The Bryant 558D also features smart technology compatibility, allowing users to integrate it with modern home automation systems. This connectivity provides homeowners with remote control capabilities, enabling them to regulate their home’s temperature via smartphone applications. This not only adds to convenience but also supports energy management strategies, as users can adjust settings based on occupancy and lifestyle patterns.

Finally, noise levels have been an important consideration in the design of the Bryant 558D. With innovative sound-dampening features, the unit operates quietly, making it an ideal choice for residential areas where noise sensitivity is paramount.

Overall, the Bryant 558D stands out as a sophisticated solution for heating and cooling needs, combining energy efficiency, advanced technology, durability, and user-friendly features. It is an excellent investment for those looking to enhance their home comfort while also being mindful of energy consumption.