Heat & Glo LifeStyle EM-415H, EM-485TH owner manual J. Chimney Termination Requirements

Page 30
J. Chimney Termination Requirements

J. Chimney Termination Requirements

Install a cap approved and listed for this fireplace system.

Locate cap where it will not become plugged by snow or other materials.

Locate cap away from trees or other structures.

The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion of roof within 10 ft (3.05 m) as shown in Figure 8.10.

The distance required between caps is shown in Figure 8.10.

Slanted Roofs

Chimney must extend 3 ft (.9 m) above the roof

Flat Roofs

Chimney must extend 3 ft (.9 m) above the roof

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Chimney must extend 2 ft (.6 m) above any portion of the roof or adjacent structures within

10 ft (3 m) of the chimney

Termination Requirements

Gas, Wood or Fuel

Gas, Wood or Fuel

Oil Termination

Oil Termination

 

See

 

A

illustration

 

18 in.

above for wood

See

(457 mm)

 

B

 

illustration

Wood

above for wood

 

20 in. min. *

 

Gas

(508 mm)

Gas

Fuel Oil

 

Termination

Termination

 

 

Termination Caps Staggered Height

Termination Caps Same Height

 

 

 

* If using decorative cap cover(s), this distance may

A

Gas Termination

Wood or Fuel Oil Termination

need to be increased. Refer to the installation instruc-

B

6 in. (152 mm) min.

20 in. (508 mm) min.

tions supplied with the decorative cap cover.

 

 

 

Multiple Chimney Locations

Figure 8.10 Multiple Chimney Locations

30

Heat & Glo • EM-415, EM-485 • 33056 • Rev V • 05/08

Image 30
Contents Wood Burning Fireplace Models EM-415, EM-415H,36” EM-485T, EM-485TH,42”Circulating Listing Label Information/Location CongratulationsHomeowner Reference Information FIREPLACE NOSafety Alert Key Table of ContentsInstaller Guide User GuideWARRANTY FOR HEAT & GLO FIREPLACES B. Non-CombustibleMaterials 1 Listing and Code ApprovalsA. Appliance Certification C. Combustible MaterialsA. Your Fireplace User Guide2 Operating Instructions Hot glass will cause burnsD. Grate B. Seasoned WoodC. Starting a Fire E. FirescreenL. Optional Components H. Glass DoorsK. Vented Gas Log Sets & Gas Log Lighters M. Clear SpaceMoisture N. Wood FuelHardwood vs Softwood Seasoned WoodA. Disposal of Ashes 3 Maintainance and ServiceB. Chimney Inspection/Cleaning Creosote - Formation and Need for RemovalD. Inspect Grate E. Glass CleaningC. Check Firebox Refractory Frequency As desiredSolution 4 Troubleshooting GuideStart Fire Problems Possible CauseA. Typical Fireplace System Installer Guide5 Getting Started Illustrations/diagrams are not drawn to scaleB. Design and Installation Considerations C. DraftD. Negative Pressure E. Locating Fireplace & Chimney F. Tools and Supplies Needed G. Typical Fireplace SystemH. Inspect Fireplace and Components 6 Framing & Clearances A. Select Fireplace LocationB. Clearances 2 in. 51 mm min. air space clearance from chimney C. Sidewalls/SurroundsD. Frame the Fireplace C A BB. Position the Fireplace 7 Installation of FireplaceA. Things to Consider C. Place Protective Metal Hearth StripsNote Chimney air kit not shown, but requiredin Canada E. Install Outside Air Kit F. Junction Box InstallationG. Installation of Fan Bend this tab downBend this half tab 90 degrees down 90 degrees 8 Chimney Assembly A. Chimney Requirements B. Using Offsets/Returns D. Install Chimney Air Kit E. Installing Ceiling FirestopsC. Assembling Chimney Sections F. Installing Attic Insulation Shield G. Cut out Hole in Roof H. Complete InstallationI. Install Flashing WARNING! Risk of Fire! You MUST maintain 2 inJ. Chimney Termination Requirements 9 Chase Installations A. Construct the ChaseB. Install Fireplace & Chimney C. Install Chase TopTR344 Round Termination Cap D. Install Termination CapRefer to termination cap instructions TR342 Round Telescoping Termination CapTS345/TS345P Square Termination Cap European Copper Series Termination CapTCT375 Terra Cotta Cap 10 Shrouds A. Radiation ShieldB. Field Constructed Shrouds Mailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredB. Combustible Materials 11 FinishingA. Non-CombustibleMaterials C. Hearth ExtensionD. Finishing Material WARNING! Risk of Fire10 3/4 in 273 mm E. Combustible MantelF. Sidewalls/Surrounds 4in 102 mm 9 3/4 in 248 mmA. Gas Log/Lighter Provision 12 AccessoriesC. Install Fan B. Wood Burning InsertsPage Description B. Fireplace ComponentsCatalog # Catalog #B. Fireplace Components continued 66 in 1676 mm 20 in 508 mm1/2 in 13 mm C. Chimney Components Catalog #14-1/2in 368 mm10-7/8in 276 mm 2 in. 51 mm Catalog #Catalog # European Copper Caps D. Service Parts Service PartsEM-415SERIES Service Parts ListService Parts List EM-485SERIESService Parts Beginning Manufacturing Date N/AThis page intentionally left blank This page intentionally left blank E. Contact Information DO NOT DISCARD THIS MANUALDO DISCARDNOT