E. Combustible Mantel

E. Combustible Mantel

See Figure 11.11.

A combustible mantel may be positioned no lower than 20 in. (508 mm) above the top of the fireplace opening.

A combustible mantel may have a maximum depth of 12 in. (305 mm).

Combustible trim and mantels cannot be placed within 6 in. (152 mm) of the fireplace opening (top or sides).

Combustible materials projecting more than 1-1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of the fireplace opening.

Combustible trim must not cover the metal surfaces of the fireplace.

Mantel clearance is in accordance with Section 7-3.3.3of ANSI/NFPA211.

F. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fireplace opening.

Combustible or noncombustible mantel legs, surrounds and stub walls may be constructed per Figure 11.12.

 

6 ft (1829 mm

 

MINIMUM

 

base of fireplace

 

to ceiling

Combustible Wall

Noncombustible Decorative Facing

2 x 4 stud wall

12 in./305 mm MAXIMUM

Standoffs

 

 

12 in.305 mm MINIMUM

 

Measured from top of fireplace opening

 

Seal Joint

Figure 11.11 Clearances to Mantels or other Combustibles above Fireplace

10 3/4 in.

[273 mm]

Grid represents 1 in. scale

FLUSH

BRICK

FRONT

FRONT

 

angle

A

 

50°

39°

angle

 

 

 

 

 

 

B

4in.

[102 mm]

9 3/4 in.

[248 mm]

12 in.

12 in.

 

 

[305 mm]

[305 mm]

 

 

 

 

 

A

B

 

Model #

Fireplace Opening

Outside Dimensions

 

EM-415

in.

36

42

 

mm

914

1067

 

 

 

 

 

 

 

 

EM-485

in.

42

48

 

mm

1067

1219

 

 

Figure 11.12 Mantel Leg or Wall Projections (acceptable on both sides of opening)

Heat & Glo • EM-415, EM-485 • 33056 • Rev V • 05/08

39

Image 39
Contents Wood Burning Fireplace Models EM-415, EM-415H,36” EM-485T, EM-485TH,42”Circulating FIREPLACE NO CongratulationsHomeowner Reference Information Listing Label Information/LocationUser Guide Table of ContentsInstaller Guide Safety Alert KeyWARRANTY FOR HEAT & GLO FIREPLACES C. Combustible Materials 1 Listing and Code ApprovalsA. Appliance Certification B. Non-CombustibleMaterialsHot glass will cause burns User Guide2 Operating Instructions A. Your FireplaceE. Firescreen B. Seasoned WoodC. Starting a Fire D. GrateM. Clear Space H. Glass DoorsK. Vented Gas Log Sets & Gas Log Lighters L. Optional ComponentsSeasoned Wood N. Wood FuelHardwood vs Softwood MoistureCreosote - Formation and Need for Removal 3 Maintainance and ServiceB. Chimney Inspection/Cleaning A. Disposal of AshesFrequency As desired E. Glass CleaningC. Check Firebox Refractory D. Inspect GratePossible Cause 4 Troubleshooting GuideStart Fire Problems SolutionIllustrations/diagrams are not drawn to scale Installer Guide5 Getting Started A. Typical Fireplace SystemB. Design and Installation Considerations C. DraftD. Negative Pressure E. Locating Fireplace & Chimney F. Tools and Supplies Needed G. Typical Fireplace SystemH. Inspect Fireplace and Components A. Select Fireplace Location 6 Framing & ClearancesB. Clearances C A B C. Sidewalls/SurroundsD. Frame the Fireplace 2 in. 51 mm min. air space clearance from chimneyC. Place Protective Metal Hearth Strips 7 Installation of FireplaceA. Things to Consider B. Position the FireplaceNote Chimney air kit not shown, but requiredin Canada F. Junction Box Installation E. Install Outside Air KitG. Installation of Fan Bend this tab downBend this half tab 90 degrees down 90 degrees 8 Chimney Assembly A. Chimney Requirements B. Using Offsets/Returns D. Install Chimney Air Kit E. Installing Ceiling FirestopsC. Assembling Chimney Sections F. Installing Attic Insulation Shield WARNING! Risk of Fire! You MUST maintain 2 in H. Complete InstallationI. Install Flashing G. Cut out Hole in RoofJ. Chimney Termination Requirements A. Construct the Chase 9 Chase InstallationsC. Install Chase Top B. Install Fireplace & ChimneyTR342 Round Telescoping Termination Cap D. Install Termination CapRefer to termination cap instructions TR344 Round Termination CapTS345/TS345P Square Termination Cap European Copper Series Termination CapTCT375 Terra Cotta Cap 10 Shrouds A. Radiation ShieldB. Field Constructed Shrouds Roofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredC. Hearth Extension 11 FinishingA. Non-CombustibleMaterials B. Combustible MaterialsWARNING! Risk of Fire D. Finishing Material4in 102 mm 9 3/4 in 248 mm E. Combustible MantelF. Sidewalls/Surrounds 10 3/4 in 273 mmB. Wood Burning Inserts 12 AccessoriesC. Install Fan A. Gas Log/Lighter ProvisionPage Catalog # B. Fireplace ComponentsCatalog # DescriptionB. Fireplace Components continued 66 in 1676 mm 20 in 508 mm1/2 in 13 mm Catalog # C. Chimney Components368 mm 14-1/2in10-7/8in 276 mm 2 in. 51 mm Catalog #Catalog # European Copper Caps Service Parts List Service PartsEM-415SERIES D. Service PartsBeginning Manufacturing Date N/A EM-485SERIESService Parts Service Parts ListThis page intentionally left blank This page intentionally left blank E. Contact Information DO NOT DISCARD THIS MANUALDO DISCARDNOT