Heat & Glo LifeStyle EM-485TH, EM-415 C. Sidewalls/Surrounds, D. Frame the Fireplace, C A B

Page 19
C. Sidewalls/Surrounds

C. Sidewalls/Surrounds

Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) (may be 24 in) from the fireplace opening.

Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed per Figure 6.3.

10 3/4 in.

[273 mm]

 

 

Grid represents 1 in. scale

 

FLUSH

 

 

BRICK

FRONT

 

 

FRONT

 

angle

A

 

50°

39°

angle

 

 

 

 

 

 

B

 

 

 

 

 

A

B

 

 

 

Model #

 

Fireplace Opening

Outside Dimensions

 

 

 

EM-415

in.

36

42

 

4 in.

mm

914

1067

 

 

 

 

 

 

 

[102 mm]

EM-485

in.

42

48

 

 

 

mm

1067

1219

 

 

 

 

 

 

9 3/4 in.

 

 

 

 

 

 

 

 

 

 

[248 mm]

 

 

 

 

 

 

 

 

 

 

12 in.

12 in.

[305 mm]

[305 mm]

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of opening)

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

Observe all required air space clearances to combustible materials as shown in Figure 6.2.

Framing across the top of fireplace must be above top standoffs.

2 in. (51 mm) min. air space clearance from chimney.

Note: Framing must be extended straight up, all the way to the ceiling.

C

A

B

Figure 6.4 Framing the Fireplace

Header MUST NOT be notched!

D = extra space needed for outside air connection.

If outside air duct has no bend, this dimension may be reduced as long as minimum clearances are met.

D

Model #

A

B*

C**

D

EM-415

in.

43

23

41 1/2

8

mm

1092

584

1054

203

 

EM-485

in.

49

23

41 1/2

8

 

 

 

 

 

mm

1245

584

1054

203

 

*If interior of chase will be drywalled, add the thickness to this measurement. ** Adjust header height for a raised floor under fireplace.

Heat & Glo • EM-415, EM-485 • 33056 • Rev V • 05/08

19

Image 19
Contents Models EM-415, EM-415H,36” EM-485T, EM-485TH,42” Wood Burning FireplaceCirculating FIREPLACE NO CongratulationsHomeowner Reference Information Listing Label Information/LocationUser Guide Table of ContentsInstaller Guide Safety Alert KeyWARRANTY FOR HEAT & GLO FIREPLACES C. Combustible Materials 1 Listing and Code ApprovalsA. Appliance Certification B. Non-CombustibleMaterialsHot glass will cause burns User Guide2 Operating Instructions A. Your FireplaceE. Firescreen B. Seasoned WoodC. Starting a Fire D. GrateM. Clear Space H. Glass DoorsK. Vented Gas Log Sets & Gas Log Lighters L. Optional ComponentsSeasoned Wood N. Wood FuelHardwood vs Softwood MoistureCreosote - Formation and Need for Removal 3 Maintainance and ServiceB. Chimney Inspection/Cleaning A. Disposal of AshesFrequency As desired E. Glass CleaningC. Check Firebox Refractory D. Inspect GratePossible Cause 4 Troubleshooting GuideStart Fire Problems SolutionIllustrations/diagrams are not drawn to scale Installer Guide5 Getting Started A. Typical Fireplace SystemC. Draft B. Design and Installation ConsiderationsD. Negative Pressure E. Locating Fireplace & Chimney G. Typical Fireplace System F. Tools and Supplies NeededH. Inspect Fireplace and Components A. Select Fireplace Location 6 Framing & ClearancesB. Clearances C A B C. Sidewalls/SurroundsD. Frame the Fireplace 2 in. 51 mm min. air space clearance from chimneyC. Place Protective Metal Hearth Strips 7 Installation of FireplaceA. Things to Consider B. Position the Fireplacenot shown, but required Note Chimney air kitin Canada F. Junction Box Installation E. Install Outside Air KitBend this tab down G. Installation of FanBend this half tab 90 degrees down 90 degrees 8 Chimney Assembly A. Chimney Requirements B. Using Offsets/Returns E. Installing Ceiling Firestops D. Install Chimney Air KitC. Assembling Chimney Sections F. Installing Attic Insulation Shield WARNING! Risk of Fire! You MUST maintain 2 in H. Complete InstallationI. Install Flashing G. Cut out Hole in RoofJ. Chimney Termination Requirements A. Construct the Chase 9 Chase InstallationsC. Install Chase Top B. Install Fireplace & ChimneyTR342 Round Telescoping Termination Cap D. Install Termination CapRefer to termination cap instructions TR344 Round Termination CapEuropean Copper Series Termination Cap TS345/TS345P Square Termination CapTCT375 Terra Cotta Cap A. Radiation Shield 10 ShroudsB. Field Constructed Shrouds Roofed Style Shroud radiation shield required Mailbox Style Shroud radiation shield requiredC. Hearth Extension 11 FinishingA. Non-CombustibleMaterials B. Combustible MaterialsWARNING! Risk of Fire D. Finishing Material4in 102 mm 9 3/4 in 248 mm E. Combustible MantelF. Sidewalls/Surrounds 10 3/4 in 273 mmB. Wood Burning Inserts 12 AccessoriesC. Install Fan A. Gas Log/Lighter ProvisionPage Catalog # B. Fireplace ComponentsCatalog # Description66 in 1676 mm 20 in 508 mm B. Fireplace Components continued1/2 in 13 mm Catalog # C. Chimney Components368 mm 14-1/2inCatalog # 10-7/8in 276 mm 2 in. 51 mmCatalog # European Copper Caps Service Parts List Service PartsEM-415SERIES D. Service PartsBeginning Manufacturing Date N/A EM-485SERIESService Parts Service Parts ListThis page intentionally left blank This page intentionally left blank DO NOT DISCARD THIS MANUAL E. Contact InformationDO DISCARDNOT