BW36 SERIES WOODBURNING FIREPLACE
STEP 12 - Assembling the Chimney Sections.
Continue to add chimney sections through the roof opening, maintaining at least a 2" air space.
STEP 13 - Installing Roof Flashing (optional).
If a roof flashing is to be used, install the roof flashing appropriate to the roof pitch and install a TR344 ter- minal cap (round) following the instructions shipped with these accessories.
STEP 14 - Installing an Outside Combustion Air Kit.
The outside air damper assembly is factory installed on the left hand side of the firebox assembly. While its use is optional, it is highly recommended to mini- mize the effects of negative pressure within the structure. Figure 17 illustrates two of many possible methods that can be used to supply outside air to the fireplace system. To complete the outside air system install the AK22 Outside Air Kit according to the installation instructions supplied with the compo- nents.
NOTE: The outside air kit can terminate at any level with the exception that it must terminate at least three feet below the chimney terminal cap as shown in Figure 17.
3' MIN. |
UPPERMOST |
CHIMNEY |
SECTION |
Figure 17
Outside Air Location
No one builds a better fire
STEP 15 - Completion of the Fireplace Enclosure.
Complete the fireplace enclosure, allowing space for out- side air ducts and gas piping if desired. Electrical wiring should not come in contact with the unit. A minimum clearance of 1" must be maintained between the fireplace sides and the enclosure as well as the fireplace back and the enclosure. See Figure 4 for framing details.
STEP 16 - Provisions for an Optional Gas Log Set.
Knockouts are provided on both sides of the fireplace to allow for connection of a certified gas log lighter or a dec- orative gas appliance with a maximum input of 100,000 BTU/hr. incorporating an automatic gas shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60. The decorative gas appliance should be installed in accordance with the National Fuel Gas Code, ANSI
This fireplace has been set up for installation of the gas pipe on the right hand side. If it is necessary to plumb the unit from the left hand side, remove the gas cover plate and gas tube from the right hand side of the unit and install on the left hand side. Cover the hole in the right hand side outer shell of the fireplace with the cover plate that covered the gas tube.
WARNING!
THIS FIREPLACE WAS NOT TESTED BY THE
FIREPLACE MANUFACTURER FOR USE WITH AN
UNVENTED GAS LOG HEATER. DO NOT
INSTALL AN UNVENTED GAS LOG HEATER IN THIS FIREPLACE UNLESS IT HAS BEEN SPECIFI- CALLY TESTED AND LISTED BY UNDER- WRITER’S LABORATORIES INC FOR USE IN THIS SPECIFIC MODEL FIREPLACE. UNLESS THE UNVENTED GAS LOG HEATER IS TESTED AND LISTED FOR USE IN THIS
CAUTION:
WHEN USING A GAS LOG SET, THE
FIREPLACE DAMPER MUST BE SET
IN THE FULLY OPEN POSITION.
THIS ENSURES A PROPER VENTING
OF COMBUSTION PRODUCTS.
17 | 30491D |