Heat & Glo LifeStyle BW36 operating instructions Materials for the Chase, Chase Assembly

Page 19

BW36 SERIES WOODBURNING FIREPLACE

1. Materials for the Chase.

The chase is constructed using framing mate- rials much the same as the walls in your home. A variety of materials may be used including brick, stone, veneer brick, or stan- dard siding materials.

In constructing the chase, several factors must be considered.

a.Maintain a 1" minimum air space around the firebox.

b.Maintain a 2" air space around the chim- ney.

c.The chase top must be constructed of a non-combustible material.

d.In cold climates a firestop spacer should be installed in an insulated false ceiling at the 8 foot level above the firebox assembly. This prevents heat loss through the fireplace.

e.In cold climates, the walls of the chase should be insulated to the level of the false ceiling as shown in Figure 21. This will help prevent heat loss from the home around and through the fireplace.

No one builds a better fire

WARNING!

DETAIL INSTRUCTIONS FOR INSTALLA- TION OF THE CHASE TOP, STORM COL- LAR AND TERMINAL CAP ARE PACKAGED WITH THESE PARTS. TO AVOID DANGER OF FIRE, ALL INSTRUCTIONS MUST BE STRICTLY FOLLOWED, INCLUDING THE PROVISION OF AIR SPACE CLEARANCE BETWEEN CHIMNEY SYSTEM AND ENCLO- SURE. TO PROTECT AGAINST AGAINST THE EFFECTS OF CORROSION ON THOSE PARTS EXPOSED TO THE WEATHER, WE RECOMMEND THAT THE CHASE TOP AND TERMINAL CAP BE PAINTED WITH A RUST RESISTANT PAINT.

2.Installing a Terminal Cap on a Chase Enclosed Chimney.

Construct a chase of desired materials maintaining a mini- mum 2" air space around the chimney.

WARNING!

NEVER INSTALL A SINGLE WALL SLIP SECTION OR SMOKE-PIPE IN A CHASE STRUCTURE. THE HIGH- ER TEMPERATURE OF THIS SINGLE WALL PIPE MAY RADIATE SUFFICIENT HEAT TO COM- BUSTIBLE CHASE MATERIALS TO CAUSE A FIRE.

ROUND TERMINAL CAP

(TR342, TR344)

METAL CHASE TOP

FIRESTOP

SPACER

FALSE

CEILING

Figure 21

Chase Assembly

4-00

Install the chimney sections up through the chase enclosure. When using a round terminal cap (TR344), the last section of pipe must extend above the top of the chase cone to allow installation of the storm collar and terminal cap.

A telescoping round terminal cap (TR342) is provided to simplify the installation of the terminal cap on a chase installation. The uppermost chimney section must terminate below the level of the chase top, but be no more than 15” below the level of the chase top. A 2” tall flashing collar must be provided on the chase top.

The ST375 Square Terminal Cap is intended for a chase installation. The uppermost chimney section must terminate no more than 4-3/4 below the level of the chase top. A 2” tall flashing collar must be pro- vided on the chase top.

When installing a TS345 or TS345P Square Termination, the uppermost chimney section must not be more than 3” below the chase top.

Attach the chase top (CT35) to the top of the chase.

Install the terminal cap, using the instructions provid- ed with it.

19

30491D

Image 19
Contents For Residential USE Woodburning Fireplace Installation & Operating InstructionsPlease Retain this Manual for Future Reference Glass Doors Heat Circulating Fans Listings and Code ApprovalsDescription of the Fireplace System Fireplace/Integral Grate Chimney System Hearth ExtensionHTI Catalog # Description Fireplace System ComponentsOutside AIR KIT Uninsulated Duct AS8Integral Grates Insulated Duct ID4Chimney Bracket Joint Band Chimney Sections Chimney Stabilizer OFFSETS/RETURNSHTI CAT.# Firestop Spacers Roof FlashingSquare Terminal CAP Chimney Terminal Caps & Vent SectionsRound Terminal CAP With Storm CollarCAT. # PRE-INSTALLATION PreparationFireplace Locations and Space Requirements Without Outside AIR With Outside AIRFraming the Fireplace Factory-Built Hearth Extension Hearth ExtensionsMantel Using Offsets and ReturnsChimney Requirements SIDEWALLS/SURROUNDSChimney Offset/Return Offset Chart SL306 SL312 SL318 SL324 SL336 SL348Determining the Number of Chimney Sections Required Chimney Height REQUIREMENTS. Above the roof linePositioning the Metal Strips Positioning the FireplacePlacing the Protective Metal Hearth Strips Leveling the FireplaceAssembling Chimney Sections Installing the Firestop SpacersSecuring the Chimney System Installing an AS8 Double-checking the Chimney AssemblyMarking the Exit Point of the Roof Outside Air Location Installing Roof Flashing optionalInstalling an Outside Combustion Air Kit Assembling the Chimney SectionsConstructing a Chase Chase Assembly Installing a Terminal Cap on a Chase Enclosed ChimneyMaterials for the Chase Operating Instructions Installing a Terminal CapEdges are SHARP! Hand PRO Tection is Recommended Recommended Operating Positions of Doors Sectional View of FireplaceBW36 Series Woodburning Fireplace Terminal Caps Warranty For HEAT-N-GLO Fireplaces