INSTALLER/CONFIGURATION MENU
To enter the menu: Press the Menu button. Press and hold for 5 seconds the Installer Config button. This displays menu item #1 in the table below. Press to advance to the next menu item or to return to a previous menu item. Press or to change a menu item.
|
|
|
|
| CONFIGURATION MENU | ||||
Menu |
| Non- |
| Displayed | Press | or |
|
|
|
|
|
|
| ||||||
Reference | Program- | Program- | Press | (Factory | to select from |
| |||
Number | mable | mable | Button | Default) | listed options | Comments | |||
|
|
|
|
|
|
| |||
1 | 1 | 1 |
| MS 2 | HP 1, HP 2, SS 1 | Selects | |||
|
|
|
|
|
|
|
|
| (HP 1, 1 compressor), Heat Pump 2 (HP 2, 2 compressor |
|
|
|
|
|
|
|
|
| or 2 speed compressor), or Single Stage. |
2 | 2 | 2 |
| (GAS) | ELE |
|
|
| GAS setting: furnace controls blower. |
|
|
|
|
|
|
|
|
| ELE setting: thermostat controls blower. |
3 | 3 | 3 |
| Days (7) | 5, 0 |
|
|
| Selects programming option. |
4 | 4 | * NA |
| PS (4) | 2 |
|
|
| Selects programming steps per day. |
5 | 5 | 4 |
| Cool Off | Cool Off Heat (Emer), | Selects system switch configuration for Heat and Cool with | |||
|
|
|
| Heat Auto | Off Heat, Cool Off | Auto changeover, Heat & Cool, Heat Only or Cool Only. | |||
6 | 6 | * NA |
| E (On) | OFF |
|
|
| Selects Energy Management Recovery on or off. |
7 | 7 | 5 |
| Cr Heat (FA) | SL |
|
|
| Selects Heat cycle rate Fast (FA) or Slow (SL). |
8 | 8 | 6 |
| Cr Cool (FA) | SL |
|
|
| Selects Cool cycle rate Fast (FA) or Slow (SL). |
9 | 9 | 7 |
| Cr Emer (FA) | SL |
|
|
| If HP 1 or HP 2 is selected for item #1, selects Emer cycle |
|
|
|
|
|
|
|
|
| rate. |
10 | 10 | 8 |
| CL (OFF) | On |
|
|
| Selects Compressor lockout ON or OFF. |
11 | 11 | 9 |
| dL (On) | OFF |
|
|
| Selects display light on or off. |
12 | 12 | 10 |
| 0 | 1, 2, 3, 4 HI | Selects temperature display adjustment 1, 2, 3 or 4 degrees | |||
|
|
|
| (Room temp) | 1, 2, 3, 4 LO | high or low. | |||
13 | 13 | 11 |
| °F | °C |
|
|
| Selects Fahrenheit or Celsius temperature display. |
14 | 14 | 12 |
| b (On) | OFF |
|
|
| Selects beeper on or off. |
15 | 15 | 13 |
| Heat (99) |
|
| Selects highest Heat setpoint temperature. | ||
|
|
|
|
|
|
|
|
| Can select 62° to 99°F. |
16 | 16 | 14 |
| Cool (45) |
|
| Selects lowest Cool setpoint temperature. | ||
|
|
|
|
|
|
|
|
| Can select 45° to 82°F. |
17 | 17 | 15 |
| Keypad | L, P |
|
|
| Selects keypad lockout full or partial to be set. |
|
|
|
| lockout (L) | Temperature Limit | Activates temperature limit ranges. | |||
18 | 18 | 16 |
| Keypad | On |
|
|
| Selects keypad lockout on or off. |
|
|
|
| lockout (OFF) |
|
|
|
|
|
|
|
|
| 000 | 000 to 999 | Selects keypad lockout combination number if lockout is on. | |||
|
|
|
|
|
|
|
|
| 000 is not a valid selection. |
19 | 19 | 17 |
| FA Heat (On) | OFF |
|
|
| If HP or MS selected in item 1, selects Heat Fast second |
|
|
|
|
|
|
|
|
| stage On or Off. |
20 | 20 | 18 |
| FA Cool (On) | OFF |
|
|
| If HP or MS selected in item 1, selects Cool Fast second |
|
|
|
|
|
|
|
|
| stage On or Off. |
21 | 21 | 19 |
| 000 Change | On |
|
|
| Select change filter alert time period. |
|
|
|
| Filter (OFF) |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| 200 hours | 25 to 1975 hours | When set ON, selects time in 25 hour increments. | |||
22 | 22 | 20 |
| Change | On |
|
|
| Selects change humidifier pad alert time period |
|
|
|
| Humidifier |
|
|
|
|
|
|
|
|
| (OFF) |
|
|
|
|
|
|
|
|
| 100 hours | 25 to 1975 hours | When set ON, selects time in 25 hour increments. | |||
* Not Applicable |
|
|
|
|
|
|
|
|
1)This control can be configured for:
MS2 –
HP1 – Heat Pump with one stage of compressor HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup
SS1 – Single Stage System
2)GAS or Electric (ELE) fan operation. If the heating system requires the thermostat to energize the fan, select ELE. Select GAS if the heating system energizes the fan on a call for heat. Note: Resetting the thermostat switches the option to ELE.
4
3)This control can be configured for 7 independent day or 5/1/1 day programming or
week can be toggled to "5 Days" or "0 Days" by pressing the or keys. A selection of 0 Days for
in the menu will be skipped.
4)Programmable Periods – This control can be configured for 4 or 2 programmable periods per day. The display
indicates "4 PS" in the display as default. The program- mable periods can be toggled by pressing the or keys.