White Rodgers 37-5086B, 37-5086A Operation System Configuration, Attach Thermostat to Subbase

Page 6

ATTACH THERMOSTAT TO SUBBASE

IT IS RECOMMENDED THAT YOU SET OPTION SWITCHES TO DESIRED POSITION BEFORE ATTACH- ING ON SUBBASE (see OPERATION). IT IS ALSO

RECOMMENDED THAT YOU PROGRAM THE THERMOSTAT WITH BATTERIES INSTALLED BE- FORE ATTACHING ON SUBBASE (see OPERATION GUIDE for programming instructions).

!CAUTION

USE SYSTEM TO TURN THERMOSTAT OFF BE-

SWITCH

FORE ATTACHING THERMOSTAT TO WALL. FAILURE TO TURN THERMOSTAT OFF BEFORE ATTACHING TO WALL MAY CAUSE EQUIPMENT DAMAGE DUE TO RAPID COMPRESSOR CY- CLING.

To attach thermostat to subbase, line up the plastic snap guides at the bottom of the thermostat and the three connector pins on the thermostat with the connectors near the bottom left section of the subbase (when viewed

from the front). Gently pivot the thermostat up until the six pin connectors and the plastic snaps lock into place (see fig. 12). Be gentle when attaching thermostat. If the thermostat does not seem to be attaching to the subbase easily, make sure that the connector pins and plastic snaps are properly aligned, and that excess wire is pushed into the wall. Damage to the thermostat may occur if force is used.

ENGAGE TWO LOWER GUIDES;

PIVOT UP

Figure 12. Attaching thermostat to subbase

OPERATION

SYSTEM CONFIGURATION

A. SET GROUP A OPTION SWITCHES

NOTE

DO NOT REMOVE THE “AA” BATTERIES WHEN CHANGING GROUP A OPTION SWITCHES. Any time Group B option switches are changed, the bat- teries must be removed for a minimum of two minutes.

1.Total Keypad Activity

ON

Switch #1 OFF

Switch #2 OFF

12

2.Total Keypad Lockout — All thermostat buttons are disabled.

ON

Switch #1 ON

Switch #2 OFF

12

3.Limited Temperature Range — Temperature may be raised or lowered within programmed temperature limits (temperature adjustment cannot exceed the lowest cooling or highest heating program tempera- tures).

ON

Switch #1 OFF

Switch #2 ON

1 2

When thermostat is in Limited Temperature Range only the following buttons are disabled:

ADV

HOLD

SET

PRGM

TEMP

DAY

6-pin connector

Batteries

W14

 

W22

 

(Group A)

 

(Group B)

 

Option switches

3-pin connector

Figure 13. Back of thermostat

B. SET GROUP B OPTION SWITCHES

NOTE

ANY TIME GROUP B OPTION SWITCHES ARE CHANGED, THE “AA” BATTERIES MUST BE REMOVED FOR A MINIMUM OF 2 MINUTES. DO NOT REMOVE THE BATTERIES WHEN CHANGING GROUP A OP- TION SWITCHES.

1.Automatic Changeover (Heating/Cooling Systems Only) — enables thermostat to automatically switch between heating and cooling programs to maintain desired room temperature.

ON

 

 

 

 

 

Switch #1 ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch #2 OFF

 

 

 

 

 

 

 

Switch #3 (see step B5)

1

2

3

 

 

 

6

Image 6
Contents Precautions ContentsDescription Route Wires to Location SpecificationsInstallation NEW Installation Select Thermostat LocationReplacement Installation Remove OLD ThermostatAttach Subbase to Wall Thermostat Typical wiring diagram for millivolt systems SET Group B Option Switches Operation System ConfigurationSET Group a Option Switches Attach Thermostat to SubbaseElectric Heat Systems Check Thermostat OperationHeating System FAN OperationTroubleshooting System ConfigurationCooling System