OWNER’S MANUAL
INSTALLATION
Continued
CHECKING GAS
CONNECTIONS
WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure external regulator has been installed be- tween propane/LP supply and fire- place. See guidelines under Con- necting to Gas Supply, page 11.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG
1.Disconnect fireplace and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace regulator.
2.Cap off open end of gas pipe where manual shutoff valve was connected.
3.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.
4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.
5.Correct all leaks at once.
Test Pressures Equal To or Less Than 1/2 PSIG
1.Close manual shutoff valve (see Figure 20).
2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.
3.Check all joints from propane/LP sup- ply tank to manual shutoff valve (see Figure 21). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4.Correct all leaks at once.
Pressure Testing Fireplace Gas Connections
1.Open manual shutoff valve (see Figure 20).
2.Open propane/LP supply tank valve.
3.Make sure control knob of fireplace is in the OFF position.
4.Check all joints from manual shutoff valve to thermostat gas valve (see Fig- ure 19). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.
5.Correct all leaks at once.
6.Light fireplace (see Operating Fire- place, pages 14 and 15). Check all other internal joints for leaks.
7.Turn off fireplace (see To Turn Off Gas to Appliance, page 15).
8.Replace front panel.
Open
Manual
Shutoff
Valve
Closed
Figure 20 - Manual Shutoff Valve
Propane/LP
Supply
Tank Manual
Shutoff
Valve
Figure 21 - Checking Gas Joints Shown with Optional Mantel
INSTALLING 9-VOLT BATTERY FOR WIRELESS REMOTE CONTROL
Two
Installing 9-Volt Battery in Receiver
1.Locate back of receiver located at the bottom, left side of the heater base.
2.Locate the battery clip mounted on the back of the receiver.
3.Slide a
4.Attach the terminal wires to the battery.
Receiver
Terminal
Wires
Battery Clip
Figure 22 - Attaching Battery to Receiver
Installing 9-Volt Battery in Hand- Held Remote Control Unit
1.Remove battery cover on back of re- mote control unit.
2.Attach terminal wires to the battery. Place battery into the battery housing.
3.Replace battery cover onto remote con- trol unit.
Battery Cover Remote Control Unit
Terminal
Wires
Battery Housing
Figure 23 - Installing Battery in Hand- Held Remote Control Unit