AIR FOR COMBUSTION AND VENTILATION

WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven- tilation air. Read the following in- structions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy effi- cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com- bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following is excerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 5 through 7 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is de- fined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a con- tinuous water vapor retarder with a rating of one perm (6 x 10-11kg per pa-sec-m2) or less with open- ings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, be- tween sole plates and floors, be- tween wall-ceiling joints, be- tween wall panels, at penetra- tions for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 7.

If your home does not meet all of the three criteria above, proceed to Deter- mining Fresh-Air Flow For Fireplace Location, page 6.

Confined and Unconfined Space

The National Fuel Gas Code (ANSI Z223.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in- stalled*, through openings not furnished with doors, are considered a part of the unconfined space.

This heater shall not be installed in a con- fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.

*Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.

Continued

104324

5

Image 5
Contents What to do if YOU Smell GAS VENT-FREE PROPANE/LP GAS Compact FireplaceVENT-FREE Propane Compact Fireplace Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingInstalling Log AssemblyAssembling Fireplace Assembling HoodProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Items InstallationCheck GAS Type Locating FireplaceDepth BUILT-IN Fireplace InstallationOptional Mantel Installation Mantel Clearances for BUILT-IN InstallationAssembling Brass Trim Brass trim shipped with mantel Raise the mantel to an acceptable height Remove the mantelFor attaching base to solid floors concrete or masonry Connecting to GAS SupplyAttaching Wood Base to Solid Floor Installation Items Needed Connecting Fireplace to GAS SupplyChecking GAS Connections Installing 9-VOLT Battery for Wireless Remote ControlLighting Instructions For Your Safety Read Before LightingOperating Fireplace To Turn OFF GAS To Appliance Manual Lighting ProcedureThermostat Control Operation Hand Held Remote OperationInspecting Burners Cleaning and MaintenanceReplacement Parts Troubleshooting Pane gas company Lation requirementsTop Gas odor even when control knob is in OFF positionService Hints SpecificationsTechnical Service Wiring DiagramValve GA5010 AccessoriesFinished Oak Veneer- GMC43F Unfinished Oak Veneer Manual shutoff valve with 1/8 NPT tapCGCF26PR Illustrated Parts BreakdownKEY CGCF26PR Description QTY Parts ListWarranty Information