Desa VYGF33NR Checking GAS Connections, Pressure Testing Gas Supply Piping System

Page 12

DESA INTERNATIONAL

UNVENTED NATURAL GAS FIREPLACE

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1. Disconnect fireplace and its individual

manual shutoff valve from gas supply

piping system. Pressures in excess of 1/2

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 20).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 21). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Fireplace Gas Connections

1.Open manual shutoff valve (see Fig- ure 20).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from manual shutoff valve to thermostat gas valve (see Fig- ure 21). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 14 through 16). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 15).

Open

Manual

Shutoff

Valve

Closed

Figure 20 - Manual Shutoff Valve

 

psig will damage fireplace gas regulator.

2.

Cap off open end of gas pipe where

 

manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

main gas valve located on or near gas

 

meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Re-connect fireplace and manual

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks.

,Q¢,,,,,,,,QQQQQQQQ¢¢¢¢¢¢¢¢,Q¢

Manual Gas Valve

Figure 21 - Checking Gas Joints

Manual

Shutoff

Valve

Gas Meter

12

104352

Image 12
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASSafety Information Desa International Unvented Natural GAS FireplaceRemote Control Accessories Product IdentificationLocal Codes UnpackingProduct Features AIR for Combustion and VentilationProviding Adequate Ventilation AIR for Combustion Ventilation Determining AIR Flow for Fireplace LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsInstallation Installing HoodOptional GA3700 and GA3700T Blower Accessory Check GAS TypeInstallation Clearances Conventional Fireplace InstallationMinimum Wall and Ceiling Clearances see Figure BUILT-IN Fireplace Installation Location of Nailing FlangesInstalling GAS Piping to Fireplace Location Mantel Clearances for Built-In InstallationInstallation Items Needed Connecting Fireplace to GAS Supply Removing Log Base Assembly From FireplacePressure Testing Gas Supply Piping System Pressure Testing Fireplace Gas ConnectionsChecking GAS Connections Installing Logs Installing One Piece Log SetFor Your Safety Read Before Lighting Operating FireplaceLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation Inspecting Burners Optional Blower OperationPilot Flame Pattern Main BurnerTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram SpecificationsTechnical Service Service HintsCleaning and Maintenance Replacement PartsODS/PILOT and Burner LogsAccessories Receiver and HAND-HELD Thermostat Remote Control KIT Ghrct Receiver and HAND-HELD Remote Control KIT GhrcWALL-MOUNT Thermostat Switch GWMT1 WALL-MOUNT ON/OFF Switch GWMS2Illustrated Parts Breakdown Remote Ready Model VYGF33NRParts List KEY Part Number Description QTYFireplace VYGF33NR Parts List Warranty Information