Trane WSC060-120 manual Performance Data, 5 Ton

Models: WSC060-120

1 52
Download 52 pages 50.2 Kb
Page 33
Image 33
5 Ton

Performance

Data

Table PD-25 — Air Temperature Rise Across Electric Heaters (Degrees C)

 

 

5 Ton

6 Ton

7.5 Ton

10 Ton

 

 

3400 M3/H

 

4100 M3/H

 

5100 M3/H

 

6800 M3/H

 

kW

Stages

WSC060AD, T

WSC072AD, T

WSC090AD, T

WSC120AD, T

 

 

 

 

 

 

 

 

 

 

7.5

2

6.6

 

8.3

2

7.3

 

9.0

2

7.9

 

10.9

2

9.6

 

11.3

1

8.3

 

6.6

 

12.1

2

10.6

 

12.5

1

9.1

 

7.3

 

13.0

2

11.4

 

13.5

1

9.9

 

7.9

 

14.4

2

12.6

 

16.0

2

14.0

 

16.9

2

12.4

 

9.9

 

7.4

 

17.2

2

15.1

 

18.8

2

13.8

 

11.0

 

8.3

 

20.2

2

14.8

 

11.8

 

8.9

 

22.6

2

16.5

 

13.2

 

9.9

 

25.0

2

18.3

 

14.6

 

11.0

 

26.9

2

19.7

 

15.7

 

11.8

 

33.9

2

14.9

 

37.5

2

16.5

 

40.4

2

17.7

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

For minimum design airflow, see performance table for each unit.

To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (C0) across Elect Htr = (kW x 2985) / (M3/H)

Table PD-25a — Air Temperature Rise Across Electric Heaters (Degrees F)

 

 

5 Ton

6 Ton

7.5 Ton

10 Ton

 

 

2000 CFM

 

2400 CFM

 

3000 CFM

 

4000 CFM

 

kW

Stages

WSC060AD, T

WSC072AD, T

WSC090AD, T

WSC120AD, T

 

 

 

 

 

 

 

 

 

 

7.5

2

11.9

 

8.3

2

13.1

 

9.0

2

14.2

 

10.9

2

17.2

 

11.3

1

14.9

 

11.9

 

12.1

2

19.1

 

12.5

1

16.5

 

13.2

 

13.0

2

20.5

 

13.5

1

17.8

 

14.2

 

14.4

2

22.8

 

16.0

2

25.3

 

16.9

2

22.3

 

17.8

 

13.4

 

17.2

2

27.2

 

18.8

2

24.8

 

19.8

 

14.9

 

20.2

2

26.6

 

21.3

 

16.0

 

22.6

2

29.8

 

23.8

 

17.9

 

25.0

2

32.9

 

26.3

 

19.8

 

26.9

2

35.4

 

28.3

 

21.3

 

33.9

2

26.8

 

37.5

2

29.6

 

40.4

2

31.9

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

For minimum design airflow, see performance table for each unit.

To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (F0) across Elect Htr = (kW x 3414) / ( 1.08 x CFM)

Table PD-26 — Electric Heater Temperature Rise Correction Factors

% Variation From Nominal Airflow – 20

– 15

– 10

– 5

0

+ 5

+ 10

+ 15

+ 20

Temperature Rise Multiplier

1.25

1.17

1.11

1.05

1

0.95

0.91

0.87

0.83

 

 

 

 

 

 

 

 

 

 

PKGP-PRC004-EN

33

Page 33
Image 33
Trane WSC060-120 manual Performance Data, 5 Ton