Trane WSC060-120 manual Performance Data, Nom kW Standard Motor & Low Static Drive

Models: WSC060-120

1 52
Download 52 pages 50.2 Kb
Page 24
Image 24
Manual background

Performance

Data

Table PD-11 — Belt Drive Evaporator Fan Performance WSC072AD,T Downflow Configuration (SI)

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

25

 

 

50

 

75

 

100

 

125

150

175

200

225

250

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

1.12 Nom kW Standard Motor & Low Static Drive

 

 

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

3260

541

0.22

603

 

0.28

657

0.33

 

705

0.38

751

0.44

794

0.50

835

0.56

874

0.62

912

0.68

 

3670

579

0.29

635

 

0.35

688

0.41

 

736

0.47

779

0.53

821

0.59

860

0.65

898

0.72

936

0.79

 

4080

565

0.31

 

620

0.37

670

 

0.43

720

0.50

 

768

0.56

810

0.63

850

0.70

888

0.76

925

0.83

961

0.91

 

4490

610

0.40

 

662

0.47

709

 

0.53

753

0.60

 

799

0.67

843

0.75

882

0.82

919

0.89

954

0.97

987

1.04

 

4890

657

0.51

 

705

0.58

749

 

0.64

791

0.72

 

832

0.79

874

0.88

914

0.96

950

1.04

985

1.12

1018

1.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.12 Nom kW Standard Motor

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& Hi Static Drive

 

 

 

 

275

 

300

325

350

 

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

 

 

 

 

 

 

 

 

 

 

 

1.12 Nom kW Standard Motor

 

 

1.12 Nom kW Standard Motor &

 

 

 

 

 

 

 

 

 

 

 

 

 

& Drive

 

 

 

 

 

Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

3260

948

0.75

 

982

0.81

1015

 

0.87

1047

0.93

 

1079

0.99

 

 

 

 

 

 

 

 

 

 

 

3670

971

0.86

 

1004

0.93

1037

 

1.00

1069

1.07

 

1099

1.14

 

 

 

 

 

 

 

 

 

 

 

4080

995

0.98

 

1027

1.06

1060

 

1.13

1091

1.21

 

1121

1.29

 

 

 

 

 

 

 

 

 

 

 

4490

1021

1.12

 

1053

1.20

1085

 

1.28

1115

1.36

 

1145

1.45

 

 

 

 

 

 

 

 

 

 

 

4890

1050

1.28

 

1081

1.36

1112

 

1.44

1140

1.53

 

1170

1.62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.50 Nom kW Over-Sized Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are

 

 

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Definite Purpose Motors, Specifically Designed And Tested To

 

 

 

1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate Reliably And Continuously At All Cataloged Conditions.

 

 

 

1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

 

 

 

 

 

 

 

 

 

 

 

 

 

Using The Full Horsepower Range Of Our Fan Motors As Shown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In Our Tabular Data Will Not Result In Nuisance Tripping Or

 

 

 

 

Premature Motor Failure. Our Product’s Warranty Will Not Be

Affected.

Table PD-11a — Belt Drive Evaporator Fan Performance WSC072AD,T Downflow Configuration (IP)

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

0.10

0.20

0.30

 

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-1/2 HP Standard Motor & Low Static Drive

 

 

 

 

 

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

1920

 

541

0.30

603

0.37

 

657

0.44

705

0.51

751

0.59

794

0.67

835

0.75

874

0.83

912

0.92

2160

 

579

0.39

635

0.46

 

688

0.55

736

0.63

779

0.71

821

0.79

860

0.88

898

0.97

936

1.06

2400

565

0.42

620

0.49

670

0.57

 

720

0.66

768

0.76

810

0.84

850

0.93

888

1.02

925

1.12

961

1.22

2640

610

0.54

662

0.62

709

0.71

 

753

0.80

799

0.90

843

1.00

882

1.10

919

1.20

954

1.29

987

1.39

2880

657

0.68

705

0.78

749

0.86

 

791

0.96

832

1.06

874

1.17

914

1.28

950

1.39

985

1.50

1018

1.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

1-1/2 HP Standard Motor &

 

1.10

1.20

1.30

 

1.40

1.50

 

 

 

 

 

 

Hi Static Drive

 

 

CFM

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

1-1/2 HP Std Motor

 

1-1/2 HP Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& Hi Static Drive

 

 

& Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1920

 

948

1.00

982

1.08

1015

1.16

 

1047

1.25

1079

1.33

 

 

 

 

 

 

 

 

 

 

 

2160

971

1.15

1004

1.25

1037

1.34

 

1069

1.43

1099

1.52

 

 

 

 

 

 

 

 

 

 

 

2400

995

1.32

1027

1.42

1060

1.52

 

1091

1.62

1121

1.73

 

 

 

 

 

 

 

 

 

 

 

2640

1021

1.50

1053

1.60

1085

1.72

 

1115

1.83

1145

1.94

 

 

 

 

 

 

 

 

 

 

 

2880

1050

1.71

1081

1.82

1112

1.94

 

1140

2.05

1170

2.17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 HP Over-Sized Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment,

 

 

 

 

1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

 

 

 

 

 

Are Definite Purpose Motors, Specifically Designed And Tested To

 

 

2 HP – Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

 

 

 

 

 

Operate Reliably And Continuously At All Cataloged Conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using The Full Horsepower Range Of Our Fan Motors As Shown In

Our Tabular Data Will Not Result In Nuisance Tripping Or Premature

Motor Failure. Our Product’s Warranty Will Not Be Affected.

24