Performance

Data

Table PD-12 — Belt Drive Evaporator Fan Performance WSC072AD,T Horizontal Configuration (SI)

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

 

25

 

50

 

75

 

100

 

125

150

175

200

225

 

250

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

 

1.12 Nom kW Standard Motor & Low Static Drive

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

 

 

3260

 

535

0.21

595

0.26

654

0.32

703

0.36

 

750

0.42

794

0.48

838

0.55

882

0.61

923

0.67

 

963

0.73

3670

 

590

0.29

638

0.34

695

0.40

745

0.46

 

789

0.51

830

0.58

871

0.65

910

0.72

950

0.79

 

987

0.86

4080

 

647

0.38

686

0.43

737

0.49

787

0.57

 

831

0.64

870

0.70

908

0.76

944

0.84

980

0.92

 

1015

0.99

4490

 

703

0.50

740

0.55

781

0.61

828

0.68

 

872

0.77

911

0.84

948

0.91

983

0.98

1016

1.06

 

1049

1.14

4890

 

761

0.64

795

0.70

828

0.76

871

0.83

 

913

0.91

953

1.00

990

1.08

1023

1.15

1055

1.23

 

1086

1.31

 

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

 

1.12 Nom kW Standard Motor &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

275

300

325

350

 

375

 

 

 

 

 

 

 

 

 

 

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

 

 

 

 

 

 

 

 

 

 

3260

 

1002

0.80

1.12 Nom kW Standard Motor & Hi Static Drive

1140

1.09

 

 

 

 

 

 

 

 

 

 

 

 

1038

0.87

1073

0.94

1107

1.01

 

 

 

 

 

 

 

 

 

 

 

 

3670

 

1025

0.93

1060

1.00

1096

1.07

1129

1.15

 

1162

1.23

 

 

 

 

 

 

 

 

 

 

 

4080

 

1051

1.07

1085

1.15

1118

1.23

1152

1.31

 

1185

1.39

 

 

 

 

 

 

 

 

 

 

 

4490

 

1081

1.23

1113

1.31

1146

1.40

1178

1.49

 

1208

1.57

 

 

 

 

 

 

 

 

 

 

 

4890

 

1117

1.40

1147

1.49

1178

1.59

1206

1.68

 

1236

1.77

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.50 Nom kW Over-Sized Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are Definite

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

 

 

 

 

 

 

 

 

Purpose Motors, Specifically Designed And Tested To Operate

 

 

1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

 

 

 

 

 

 

 

 

 

 

 

 

Reliably And Continuously At All Cataloged Conditions. Using The Full

 

1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

 

 

 

 

 

Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product’s Warranty Will Not Be Affected.

 

 

 

 

 

 

Table PD-12a — Belt Drive Evaporator Fan Performance WSC072AD,T Horizontal Configuration (IP)

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

 

0.40

0.50

0.60

 

0.70

0.80

0.90

1.00

CFM

 

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-1/2 HP Standard Motor & Low Static Drive

 

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

 

 

1920

535

0.28

595

0.34

654

0.42

 

703

0.49

750

0.56

794

0.65

 

838

0.73

882

0.82

923

0.90

963

0.99

2160

590

0.39

638

0.45

695

0.53

 

745

0.62

789

0.69

830

0.77

 

871

0.87

910

0.96

950

1.06

987

1.15

2400

647

0.51

686

0.58

737

0.66

 

787

0.76

831

0.85

870

0.93

 

908

1.02

944

1.12

980

1.23

1015

1.33

2640

703

0.67

 

740

0.74

781

0.82

 

828

0.92

872

1.03

911

1.13

 

948

1.22

983

1.31

1016

1.42

1049

1.53

2880

761

0.85

 

795

0.94

828

1.02

 

871

1.11

913

1.22

953

1.34

 

990

1.45

1023

1.55

1055

1.65

1086

1.75

 

 

 

 

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

 

 

 

1-1/2 HP Std Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.10

1.20

1.30

 

1.40

1.50

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

1920

1002

1.08

1-1/2 HP Standard Motor & Hi Static Drive

1.36

1140

1.46

 

 

 

 

 

 

 

 

 

 

 

 

1038

1.17

1073

1.27

 

1107

 

 

 

 

 

 

 

 

 

 

 

 

2160

1025

1.25

1060

1.34

1096

1.44

 

1129

1.54

1162

1.65

 

 

 

 

 

 

 

 

 

 

 

 

2400

1051

1.44

1085

1.54

1118

1.64

 

1152

1.75

1185

1.86

 

 

 

 

 

 

 

 

 

 

 

 

2640

 

1081

1.65

1113

1.76

1146

1.88

 

1178

1.99

1208

2.10

 

 

 

 

 

 

 

 

 

 

 

 

2880

1117

1.88

1147

2.00

1178

2.13

 

1206

2.25

1236

2.38

 

 

 

 

 

 

 

 

 

 

 

 

2 HP Over-Sized Motor & Hi Static Drive

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose

Motors, Specifically Designed And Tested To Operate Reliably And

1

1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

Continuously At All Cataloged Conditions. Using The Full Horsepower Range

2

HP – Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

 

Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In

Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will

Not Be Affected.

PKGP-PRC004-EN

25

Page 25
Image 25
Trane WSC060-120 Nom kW Standard Motor & Drive Hi Static Drive, External Static Pressure Pascals 275 300 325 350 375 M3/h