Trane WSC060-120 manual Electrical Data, Table ED-1- Unit Wiring

Models: WSC060-120

1 52
Download 52 pages 50.2 Kb
Page 35
Image 35
Electrical

Electrical

Data

Table ED-1 — Unit Wiring

 

 

Standard Indoor Fan Motor

 

Oversize Indoor Fan Motor

 

Unit

Minimum

Maximum Fuse

Minimum

Maximum Fuse

Unit

Operating

Circuit

Size Or Maximum

Circuit

Size Or Maximum

Model No.

Voltage Range

Ampacity

Circuit Breaker1

Ampacity

Circuit Breaker1

WSC060AD

342-456

18.9

25

 

18.9

25

WSC060AT

180-220

37.2

50

 

37.2

50

 

 

 

 

 

 

 

WSC072AD

342-456

21.9

30

 

22.9

30

WSC072AT

180-220

38.4

60

 

43.9

60

 

 

 

 

 

 

 

WSC090AD

342-456

24.8

35

 

26.5

35

WSC090AT

180-220

47.6

60

 

50.2

60

 

 

 

 

 

 

 

WSC120AD

342-456

31.2

40

 

31.2

40

WSC120AT

180-220

59.5

60

 

59.5

60

Notes:

1. All units to be installed under local codes.

PKGP-PRC004-EN

35

Page 35
Image 35
Trane WSC060-120 manual Electrical Data, Table ED-1- Unit Wiring