Performance

Data

Table PD-10 — Belt Drive Evaporator Fan Performance WSC060AD,T Horizontal Configuration (SI)

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

25

 

 

50

 

75

100

125

150

175

200

225

250

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

 

kW

 

1.12 Nom kW Standard Motor & Low Static Drive

 

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

2720

692

0.25

761

0.30

823

0.36

884

0.41

941

0.47

990

0.52

1034

0.58

1077

0.64

1119

0.70

1158

0.75

3060

761

0.35

825

0.40

882

0.46

937

0.52

992

0.58

1043

0.65

1088

0.71

1130

0.77

1169

0.83

1207

0.90

3400

831

0.46

891

0.52

945

0.58

995

0.65

1045

0.72

1094

0.79

1141

0.86

1185

0.93

1224

1.00

1260

1.07

3740

901

0.60

958

0.67

1009

0.73

1057

0.80

1101

0.88

1146

0.95

1192

1.03

1235

1.11

1277

1.18

1314

 

1.26

 

4080

972.8

0.76

1026

0.84

1075

0.91

1120

0.98

1163

1.06

1204

1.14

1245

1.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.12 Nom kW Standard Motor &

Hi Static Drive

External Static Pressure (Pascals)

275300325350375 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW

 

1.12 Nom kW Standard Motor

1.12 Nom kW Standard Motor &

 

2720

 

& Drive

1231

0.88

1265

Hi Static Drive

1330

1.07

1196

0.82

0.94

1298

1.00

3060

1244

0.96

1280

1.03

1314

1.10

1346

1.16

1380

1.24

3400

 

1295

1.14

1330

1.21

1363

1.28

3740

 

4080

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-10a — Belt Drive Evaporator Fan Performance WSC060AD,T Horizontal Configuration (IP)

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

 

1-1/2 HP Standard Motor & Low Static Drive

 

 

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

 

 

1600

692

0.34

761

0.41

823

0.48

884

0.55

941

0.63

990

0.70

1034

0.78

1077

0.85

1119

0.93

1158

1.01

1800

761

0.47

825

0.54

882

0.62

937

0.70

992

0.78

1043

0.87

1088

0.95

1130

1.03

1169

1.12

1207

1.21

2000

831

0.62

891

0.70

945

0.78

995

0.87

1045

0.97

1094

1.06

1141

1.15

1185

1.25

1224

1.34

 

1260

1.43

2200

901

0.80

958

0.90

1009

0.98

1057

1.08

1101

1.18

1146

1.28

1192

1.38

1235

1.49

1277

1.59

1314

1.69

2400

972.8

1.02

1026

1.13

1075

1.22

1120

1.32

1163

1.42

1204

1.53

1245

1.65

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

 

 

 

 

1-

1/2 HP Standard Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.10

1.20

1.30

1.40

1.50

 

 

 

 

 

 

 

 

 

 

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

1-1/2 HP Std Motor & Drive

 

1600

1196

1.09

1231

1.17

1800

1244

1.29

1280

1.38

2000

1295

1.52

1330

1.62

2200

2400

1-1/2 HP Standard Motor & Hi Static Drive

1265

1.26

1298

1.35

1330

1.44

1314

1.47

1346

1.56

1380

1.66

1363

1.72

Notes:

Factory Supplied Motors, In Commercial Equipment,

Data Includes Pressure Drop Due To Wet Coils And Filters.

Are Definite Purpose Motors, Specifically Designed And Tested To

1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

Operate Reliably And Continuously At All Cataloged Conditions.

 

Using The Full Horsepower Range Of Our Fan Motors As Shown In

 

Our Tabular Data Will Not Result In Nuisance Tripping Or Premature

 

Motor Failure. Our Product’s Warranty Will Not Be Affected.

PKGP-PRC004-EN

23

Page 23
Image 23
Trane WSC060-120 manual Nom kW Standard Motor Hi Static Drive, HP Std Motor & Drive, HP Standard Motor & Hi Static Drive