Performance

Data

Table PD-15 — Belt Drive Evaporator Fan Performance WSC0120AD,T Downflow Configuration (SI)

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

25

 

50

 

75

 

100

125

150

175

200

225

250

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

5440

2.24 Nom kW Standard Motor & Low Static Drive

0.72

754

0.82

2.24 Nom kW Standard Motor & Drive

887

1.25

718

789

0.93

822

1.03

856

1.14

6120

694

0.71

731

0.81

764

0.90

797

0.99

829

1.10

860

1.22

892

1.34

922

1.46

6800

715

0.81

747

0.90

782

1.01

814

1.11

844

1.21

874

1.32

903

1.44

932

1.56

960

1.69

7480

741

0.95

773

1.04

803

1.14

834

1.24

864

1.36

894

1.48

922

1.59

948

1.70

975

1.82

1001

1.95

8160

803

1.21

833

1.31

861

1.42

887

1.52

916

1.64

947

1.77

972

1.90

997

2.02

1022

2.14

1046

2.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

275

300

325

350

375

400

425

450

475

500

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

5440

917

1.36

945

2.24 Nom kW Standard Motor & Drive

1.84

1048

1.97

1072

2.10

1095

2.23

1117

2.37

1140

3.36

1.47

973

1.60

999

1.72

1024

6120

951

1.57

979

1.69

1007

1.82

1033

1.94

1059

2.07

1082

2.20

1107

2.34

1130

2.49

1152

2.63

1173

3.71

6800

988

1.82

1015

1.95

1042

2.08

1068

2.21

1093

2.35

1117

2.48

1142

2.63

1164

2.76

1187

2.91

1209

4.11

7480

1028

2.09

1053

2.23

1078

2.38

1103

2.52

1128

2.66

1152

2.81

1176

2.95

1198

3.10

1221

3.25

8160

1071

2.41

1095

2.55

1119

2.70

1142

2.86

1166

3.02

1189

3.17

1212

3.33

 

 

 

 

 

 

 

 

2.24 Nom kW Standard Motor & High Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are Definite

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

Purpose Motors, Specifically Designed And Tested To Operate

 

 

2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

 

 

 

 

Reliably And Continuously At All Cataloged Conditions. Using The

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Horsepower Range Of Our Fan Motors As Shown In Our

 

 

 

Tabular Data Will Not Result In Nuisance Tripping Or Premature

Motor Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-15a — Belt Drive Evaporator Fan Performance WSC0120AD,T Downflow Configuration (IP)

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

 

0.70

0.80

0.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3200

3 HP Standard Motor & Low Static Drive

0.97

754

1.10

 

789

1.25

3 HP Standard Motor & Drive

887

1.67

718

 

822

1.38

856

1.53

3600

694

0.95

731

1.08

764

1.20

797

1.33

 

829

1.48

860

1.63

892

1.79

922

1.95

4000

715

1.09

747

1.21

782

1.35

814

1.49

844

1.63

 

874

1.77

903

1.93

932

2.09

960

2.27

4400

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

894

1.98

 

922

2.13

948

2.28

975

2.44

1001

2.62

4800

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

947

2.38

 

972

2.55

997

2.71

1022

2.87

1046

3.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Water)

 

 

 

 

 

 

 

 

 

1.10

1.20

1.30

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3200

917

1.82

945

1.97

3 HP Standard Motor & Drive

1024

2.47

1048

2.65

 

1072

2.82

1095

3.00

1117

3.17

1140

3.36

973

2.14

999

2.30

 

3600

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

1082

2.95

 

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

1117

3.33

 

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

1028

2.81

1053

3.00

1078

3.19

1103

3.38

1128

3.57

1152

3.77

 

1176

3.96

1198

4.15

1221

4.36

4800

1071

3.23

1095

3.42

1119

3.62

1142

3.83

1166

4.04

1189

4.25

 

1212

4.46

 

 

 

 

 

 

 

 

3 HP Standard Motor & High Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are Definite

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

Purpose Motors, Specifically Designed And Tested To Operate

 

 

3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

 

 

 

 

Reliably And Continuously At All Cataloged Conditions. Using The

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Will Not Result In Nuisance Tripping Or Premature Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure. Our Product’s Warranty Will Not Be Affected.

 

 

 

 

28

PKGP-PRC004-EN

Page 28
Image 28
Trane WSC060-120 manual Nom kW Standard Motor & Low Static Drive, Nom kW Standard Motor & High Static Drive