Trane WSC060-120 manual Performance Data, Integrated Heating Capacity kW

Models: WSC060-120

1 52
Download 52 pages 50.2 Kb
Page 18
Image 18
Integrated Heating Capacity (kW)

Performance

Data

Table PD-5 – Net Heating Capacities (kW) WSC060AD,T at 3,400 m3/h (SI)

 

 

Integrated Heating Capacity (kW)

 

 

Total Power (kW)

 

Outdoor

 

At Indicated Indoor Dry Bulb Temp (C)

 

 

At Indicated Indoor Dry Bulb Temp (C)

 

Temp (C)

15

21

24

27

15

21

24

27

–24

4.1

4.1

4.1

4.0

3.2

3.7

3.9

4.2

–21

4.9

4.9

4.8

4.8

3.3

3.8

4.0

4.3

–18

5.8

5.7

5.6

5.5

3.4

3.8

4.1

4.3

–15

6.7

6.5

6.4

6.3

3.5

3.9

4.2

4.4

–12

7.6

7.4

7.3

7.2

3.6

4.0

4.3

4.5

–9

8.6

8.3

8.2

8.1

3.7

4.1

4.3

4.6

–6

9.6

9.3

9.1

9.0

3.8

4.2

4.4

4.7

–3

10.6

10.3

10.1

10.0

3.9

4.3

4.5

4.8

0

11.7

11.4

11.2

11.0

4.0

4.4

4.6

4.9

3

12.8

12.4

12.2

12.0

4.1

4.5

4.7

5.0

6

13.9

13.5

13.3

13.1

4.2

4.6

4.8

5.1

9

16.7

16.2

15.9

15.7

4.3

4.7

5.0

5.2

12

18.0

17.4

17.1

16.9

4.4

4.8

5.1

5.4

15

19.3

18.7

18.4

18.1

4.5

5.0

5.2

5.5

18

20.7

20.1

19.7

19.4

4.7

5.2

5.4

5.7

21

22.1

21.4

21.1

20.7

4.8

5.3

5.6

5.9

24

23.6

22.8

22.4

22.1

5.0

5.5

5.8

6.1

Notes:

1.Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

2.Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand defrost cycle.

Table PD-5a — Net Heating Capacities (MBH) WSC060AD,T at 2,000 CFM (IP)

 

 

Integrated Heating Capacity (MBh)

 

 

Total Power (kW)

 

Outdoor

 

At Indicated Indoor Dry BulbTemp (F)

 

 

At Indicated Indoor Dry BulbTemp (F)

 

Temp (F)

60

70

75

80

60

70

75

80

–8

15.8

15.6

15.4

15.2

3.3

3.7

4.0

4.2

–3

18.3

18.0

17.8

17.6

3.4

3.8

4.0

4.3

2

21.0

20.6

20.3

20.0

3.5

3.9

4.1

4.4

7

23.9

23.3

23.0

22.6

3.6

4.0

4.2

4.4

12

26.8

26.1

25.7

25.4

3.7

4.1

4.3

4.5

17

29.9

29.1

28.7

28.2

3.8

4.1

4.4

4.6

22

33.1

32.2

31.7

31.2

3.8

4.2

4.4

4.7

27

36.5

35.4

34.9

34.4

3.9

4.3

4.5

4.8

32

39.9

38.8

38.2

37.6

4.0

4.4

4.6

4.9

37

43.4

42.0

41.4

40.8

4.1

4.5

4.7

5.0

42

46.8

45.4

44.7

44.1

4.2

4.6

4.8

5.1

47

56.0

54.2

53.4

52.7

4.3

4.7

4.9

5.2

52

60.0

58.1

57.3

56.5

4.4

4.8

5.0

5.3

57

64.1

62.1

61.1

60.3

4.5

4.9

5.2

5.4

62

68.4

66.3

65.4

64.4

4.6

5.1

5.3

5.6

67

72.7

70.6

69.6

68.5

4.8

5.3

5.5

5.8

72

77.3

75.0

73.9

72.7

5.0

5.4

5.7

6.0

Notes:

1.Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

2.Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand defrost cycle.

18

PKGP-PRC004-EN

Page 18
Image 18
Trane WSC060-120 manual Performance Data, Integrated Heating Capacity kW