Performance

Data

Table PD-9 — Belt Drive Evaporator Fan Performance WSC060AD,T Downflow Configuration (SI)

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

25

50

75

100

125

150

175

200

225

250

m3/h RPM kW

RPM kW

RPM kW

RPM

kW RPM kW

RPM kW

RPM

kW RPM

kW RPM kW

RPM kW

2720 — —

3060 693 0.31

3400 758 0.41

3740 824 0.54

4080 890 0.69

1.12 Nom kW Standard Motor & Low Static Drive

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

690

0.26

746

0.30

795

0.34

843

0.38

889

0.42

933

0.47

975

0.53

1014

0.58

1050

0.63

746

0.34

802

0.39

848

0.44

892

0.48

935

0.52

976

0.57

1016

0.62

1056

0.68

1093

0.74

806

0.45

856

0.50

904

0.55

945

0.60

985

0.65

1023

0.70

1061

0.75

1098

0.80

1135

0.86

869

0.58

913

0.63

959

0.68

1001

0.74

1038

0.80

1074

0.85

1109

0.90

1143

0.96

1177

1.01

933

0.74

972

0.78

1014

0.84

1056

0.90

1094

0.97

1128

1.03

1160

1.09

1193

1.15

1225

1.20

External Static Pressure (Pascals)

275300325350375 m3/h RPM kW RPM kW RPM kW RPM kW RPM kW

1.12 Nom kW Standard Motor & Drive

2720

1085

0.68

1118

0.72

1151

0.78

1183

0.83

1214

0.88

 

3060

1128

0.80

1160

0.86

1192

0.91

1223

0.97

1252

1.02

 

3400

1170

0.93

1203

1.00

1235

1.06

1265

1.12

1295

1.19

 

3740

1212

1.07

1244

1.14

1276

1.21

1308

1.29

 

4080

1256

1.26

1287

1.32

 

 

 

 

 

 

 

 

 

 

 

 

 

1.12Nom kW Standard Motor & Hi Static Drive

Notes:

Factory Supplied Motors, In Commercial Equipment, Are

Data Includes Pressure Drop Due To Wet Coils And Filters.

Definite Purpose Motors, Specifically Designed And Tested To

1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

Operate Reliably And Continuously At All Cataloged Conditions.

 

Using The Full Horsepower Range Of Our Fan Motors As Shown

 

In Our Tabular Data Will Not Result In Nuisance Tripping Or

 

Premature Motor Failure. Our Product’s Warranty Will Not Be

 

Affected.

Table PD-9a — Belt Drive Evaporator Fan Performance WSC060AD,T Downflow Configuration (IP)

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

0.10

0.20

0.30

0.40

0.50

0.60

 

0.70

0.80

0.90

1.00

CFM

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

1–1/2 HP Standard Motor & Low Static Drive

 

 

 

 

 

1–1/2 HP Standard Motor & Drive

 

1600

690

0.35

746

0.40

795

0.46

843

0.51

889

0.57

 

933

0.64

975

0.71

1014

0.78

1050

0.84

1800

693

0.41

746

0.46

802

0.52

848

0.59

892

0.65

935

0.70

 

976

0.76

1016

0.84

1056

0.92

1093

1.00

2000

758

0.56

806

0.60

856

0.67

904

0.74

945

0.81

985

0.87

 

1023

0.94

1061

1.00

1098

1.07

1135

1.16

2200

824

0.73

869

0.78

913

0.84

959

0.92

1001

1.00

1038

1.07

 

1074

1.15

1109

1.21

1143

1.28

1177

1.35

2400

890

0.93

 

933

0.99

972

1.05

1014

1.12

1056

1.21

1094

1.30

 

1128

1.38

1160

1.46

1193

1.54

1225

1.61

 

 

 

 

 

 

 

 

1-1/2 HP Standard Motor & Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.10

1.20

1.30

1.40

1.50

 

 

 

 

 

 

 

 

 

 

 

CFM

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

1–1/2 HP Standard Motor & Drive

1600

1800

2000

2200

2400

1085

0.91

1118

0.97

1151

1.04

1183

1.11

1214

1.18

 

 

 

1128

1.08

1160

1.15

1192

1.22

1223

1.29

1252

1.37

 

 

1–1/2 HP Standard Motor &

1170

1.25

1203

1.34

1235

1.43

1265

1.51

1295

1.59

 

 

 

 

Hi Static Drive

1212

1.44

1244

1.53

1276

1.63

1308

1.73

 

 

1256

1.69

1287

1.77

 

 

 

Notes:

Factory Supplied Motors, In Commercial Equipment,

Data Includes Pressure Drop Due To Wet Coils And Filters.

Are Definite Purpose Motors, Specifically Designed And Tested To

1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

Operate Reliably And Continuously At All Cataloged Conditions.

 

Using The Full Horsepower Range Of Our Fan Motors As Shown In

 

Our Tabular Data Will Not Result In Nuisance Tripping Or Premature

 

Motor Failure. Our Product’s Warranty Will Not Be Affected.

22

PKGP-PRC004-EN

Page 22
Image 22
Trane WSC060-120 manual Nom kW Standard Motor & Hi Static Drive, HP Standard Motor & Static Drive