® VMH26TPB

COMPACT CLASSIC HEARTH® FIREPLACE

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

Example:

 

30,000

 

Gas furnace

 

___________________ Btu/Hr

Gas water heater

 

Btu/Hr

Vented gas heater

 

___________________ Btu/Hr

Vent-free fireplace

+

26,000

Btu/Hr

 

56,000

 

Total

=

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

 

 

 

 

 

Other gas appliances* +

___________________ Btu/Hr

 

 

 

 

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3 or applicable local codes.

6

107030

Image 6
Contents Shown with Optional Cabinet Mantel/Hearth Base Accessory What to do if YOU Smell GASSafety Information Compact Classic Hearth FireplaceLocal Codes Product FeaturesUnpacking Product IdentificationAssembling Fireplace AssemblyInstalling Log Assembling HoodUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Fireplace LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstallation Items Locating FireplaceBUILT-IN Fireplace Installation Locate fireplace where moving vehicle will not hit itRaise the mantel to an accept Mantel Clearances for Built-In InstallationOptional Mantel Able heightInstalling Blower Assembly Installing Blower Accessory GA3450TRemoving Upper Louver Assembly Assembling Brass Trim Brass trim shipped with mantelInstall the switch plate on the valve For Built-In Installation Extension CordConnecting to GAS Supply Attaching Wood Base to Solid FloorThread inlet connection and the flexible gas line provided Connecting Equipment Shutoff Valve to Heater Control Installation Items NeededValve should be accessible Pressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections For Your Safety Read Before Lighting Operating FireplaceLighting Instructions Inspecting Burner Burner Flame Pattern Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole CabinetTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atService Hints SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown VMH26TPBParts List KEY Description QTYAccessories 107030 Warranty Information