WinterWarm Small Insert
Installation
Installing the WinterWarm Small Insert into an existing masonry or
Requirements for Existing Fireplaces
The WinterWarm Small Insert is listed for installation within a properly built masonry or heat circulating, ma-
The fireplace and chimney must be clean and structur- ally sound. Have them inspected by a qualified pro- fessional chimney sweep, a mason, or your Vermont Castings’ Authorized Dealer before the WinterWarm Small Insert is installed. Any deterioration (cracks, loose mortar or loose bricks) must be repaired.
Codes may permit removal of the damper in order to make a positive connection for the vent between the firebox and the chimney. However, the fireplace should not be modified in any way without first checking with your local building inspector or fire marshal. Provision should be made to restore the fireplace to its original condition if the insert is removed. Do not remove bricks or mortar that may jeopardize the compliance of the fireplace with local building codes.
The WinterWarm Small Insert is also listed for installa- tion in tested and listed
local authorities before making any modifications.
Requirements for Existing Chimneys
Chimney requirements differ for the U.S. and Canada. Specifications for each are listed below. Connect the insert to the chimney in accordance with local codes and the requirements of the listing agency as specified in this manual.
Chimney Height / U.S. and Canada
Chimney height should be no less than 15’ (4.5m) above the hearth and no more than 35’ (10.5m).
The chimney should extend at least 3’ (914m) above the highest point where it passes through a roof, and at least 2’ (610mm) higher than any portion of a building
within 10’ (3m). (Fig. 2) |
| |
| 0 To 10' |
|
| 2' Min. 3' | 0 To 10' |
| Min. |
|
|
| 2' Min. 3' |
|
| Min. |
| Reference | AC617 |
| Point | |
Fig. 2 | The |
Do not connect your WinterWarm small insert to a chimney flue serving another appliance.
U.S.
In the U.S. (ANSI/NFPA 211, 1988), when installed in a masonry fireplace:
•A connector must extend from the flue collar to the flue liner.
•The cross sectional area of the flue must be less than or equal to three times the area of the flue collar. If larger, the chimney must be
•Means must be provided to prevent room air passing to the chimney cavity.
•Provision must be made for removal of the insert to clean the chimney flue.
4 | 2000888 |