Enviro DV42DX owner manual Possibility of a fire, Horizontal Vent Termination

Page 22

Initial Installation

QUALIFIED INSTALLERS ONLY

HORIZONTAL TERMINATION:

NOTES:

 

 

 

 

 

 

 

 

 

1. Horizontal pipes must not be level. For every 12 inches (305 mm) of horizontal travel

(away from the stove), there should be at least 1⁄4 inch (6.4 mm) of vertical travel. Never

allow the vent to run downward, as this could cause high temperatures or even present

the possibility of a fire.

 

 

 

 

2. The exterior of the horizontal

 

 

vent termination must not be

 

 

blocked or obstructed.

 

 

 

 

3. If the vent termination is not

 

 

being

attached to

wood,

 

the

Wall thimble

 

four

wood

screws

provided

 

fire stop

Horizontal wall

should

be

replaced

with

 

termination

material appropriate fasteners.

 

 

4. For buildings with vinyl siding,

 

Wall framing

a vinyl standoff should be

 

 

installed between the vent cap

Elbow

 

and the exterior wall. Attach

 

 

the

vinyl

siding

standoff

to

 

 

the

horizontal

termination.

 

 

Note

 

that

 

the

termination

Exhaust

 

bolts onto the flat portion of

flex pipe

 

 

 

the standoff, providing an

air

Combustion air

 

space between the wall and

outer pipe

 

 

 

the vent termination. The air

 

 

gap

prevents excessive

heat

 

 

from possibly melting the vinyl

 

 

siding.

 

 

 

 

 

 

 

 

 

5. Horizontal

 

pipes

 

must

 

be

Figure 27. Horizontal Vent Termination

 

supported

every

3

feet

(914

 

mm). Plumber’s all round strap will suffice.

6.When running horizontal pipe, clearances to combustibles must be maintained 11⁄2 inches (38 mm) sides, 11⁄2 inches (38 mm) bottom, and 2 inches (51 mm) top.

Step 1. Set the fireplace in the desired location. Check to determine if wall studs will be in the way when the venting system is attached. If this is the case, the location of the fireplace may have to be adjusted or the venting may have to be offset.

Step 2. Direct vent pipe sections are designed with special twist-lock connections. Dry fit the desired combination of pipe and elbows to the appliance adaptor.

Step 3. With the pipe in the correct position and attached to the fireplace, mark the wall for a 10 inches (25.4 cm) x 10 inches (25.4 cm) square hole (see Figure 24). The center of the hole should match the center line of the horizontal pipe. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is made of a non-combustible material (i.e. masonry or concrete) a 7 inches (17.8 cm) hole is acceptable.

22

Image 22
Contents DV42DX S H E R W O O D I N D U S T R I E S L T DSafety Precautions GeneralTable of Contents Vented GAS Fireplace Heater DV42DX NG/LPG Codes And ApprovalsThis Enviro DV42DX Fireplace Specifications Installation OptionsOperating Instructions Pilot Lighting InstructionsNever USE AN Open Flame for Leak Testing To Turn GAS Fireplace OFF Component Sound & ReasonMaintenance And Service No substitute materials are allowedCleaning Decorative Surfaces To be Installed by a Qualified Service Agency only StepInitial Installation Qualified Installers onlyCorner Installation Rock or Brick Finish If the face Sheet are only approximations it is recommendedMantel Clearances KIT Components Qnty DescriptionInstallation Instructions Wire Spacer in PlaceManufacturer Trade Name Nominal Sizes Direct Vent Secure Vent Ameri Vent Description Temp SV4L6Venting terminals can not be recessed into a wall or siding Vent Configurations and Restrictor Settings Possibility of a fire Horizontal Vent TerminationAssemble Vertical Vent TerminationRoof Pitch Minimum Height H Feet Meters Use of Wall Straps Ducting Electrical Requirements GAS Line Connection To Test Valve PressuresImportant installation notes Secondary InstallationNever operate the fireplace with the glass door removed First Stage Log Set Installation Secondary Installation Burner and FAN Removal Troubleshooting Problem Possible Cause SolutionParts List Components Reference Description Part NumberComponentsParts Diagram Parts List Options Reference Options Part NumberParts Diagram Options To the Dealer WarrantyTo the Distributor Installation Data Sheet

DV42DX specifications

The Enviro DV42DX is a highly efficient and eco-friendly ventilation device designed to enhance indoor air quality while minimizing energy consumption. This powerful product is tailored for residential and commercial applications, making it a versatile choice for those looking to improve air circulation.

One of the standout features of the Enviro DV42DX is its dual-speed fan system, which allows users to select the optimal airflow needed for various conditions. This not only provides flexibility but also contributes to energy efficiency, as it can operate at lower speeds during quieter periods. The adjustable fan settings ensure that users can tailor the device’s performance to meet their specific requirements.

Incorporating advanced filtration technologies, the Enviro DV42DX features an integrated HEPA filter that effectively captures airborne particles, allergens, and pollutants. This makes it an ideal choice for individuals with allergies or respiratory conditions, as it significantly reduces exposure to harmful elements in the air. Additionally, the unit is equipped with a charcoal filter that helps eliminate odors, further enhancing the indoor atmosphere.

The Enviro DV42DX is designed with user convenience in mind. It includes a programmable timer and a remote control, allowing users to operate the device from a distance and set it on a schedule that aligns with their routines. This feature not only enhances the ease of use but also encourages energy-saving habits by allowing the unit to operate only when needed.

Another characteristic of the Enviro DV42DX is its energy-efficient design, boasting a high Energy Star rating. The device not only reduces energy consumption but also saves users money on utility bills over time. Its durable construction and high-quality materials ensure longevity and reliable performance, making it a wise investment for maintaining a healthy living or working environment.

Safety is also a top priority for the Enviro DV42DX. The unit is equipped with built-in sensors that monitor air quality and automatically adjust operation to ensure optimal performance. This smart technology ensures that the device operates efficiently while maintaining safe levels of indoor air quality.

In conclusion, the Enviro DV42DX offers an impressive array of features and technologies that prioritize indoor air quality and energy efficiency. Its combination of advanced filtration, user-friendly controls, and smart technology makes it an indispensable tool for any environment aiming for cleaner and healthier air. Investing in the Enviro DV42DX is a step toward a more sustainable and comfortable indoor atmosphere.