MHP EWF36A Installation Instructions, Installating Outside Air Kit, Installation Precautions

Page 11
Installation Instructions

Nail Top Stand- offs

Nail Side

Nailing

Flanges

FP1197

Fig. 12 Fasten fireplace in position.

Vermont Castings EWF36A

Installation Instructions

Determine the location of the fireplace as described in the fireplace Installation Manual. Then plan location of the duct termination and the route of the duct run between the fireplace and the duct termination.

Duct run must be limited to a maximum distance of 40 feet from the fireplace pipe collar to duct termination. This will provide the least restriction to air flow. No more than four (4) 90° elbows can be used. Duct run may be horizontal, vertical, inclined or any combination of these. Vertical duct runs must be at least three (3) feet below the fireplace chimney flue exit. (Fig. 13) You are now ready to install the AK-MST Outside Air Kit.

Installating Outside Air Kit

An outside air kit may be installed on the EWF36A. If desired, or if local codes mandate the use of an air kit, then two (2) AK-MSTs are required to complete the installation (from air kit to the outdoors). If the outside air kits are to be used, the AK-MSTs MUST be installed BEFORE the fireplace is enclosed.

NOTE: Air duct assemblies must be installed in con- junction with the AK-MST or cold air will enter the home. (Fig. 14)

NOTE: Four (4) inch Class 1 air duct, material or metal duct (not supplied) may be used with AK-MST. (For installation in New York State, only aluminum, non-

Duct Termination Must be More Than 3’ Below Chimney

Duct Termi- nation

40’ Max.

Duct Run

Attic

Installating Outside Air Kit Ceiling

Duct

combustible flexible or type “O” metal ducting is permissible.)

Installation Precautions

The duct termination should be located so it is exposed to an out-of-doors opening at least 100 square inches. If the duct termination must be located in a crawl space or basement, be sure the termination area has 100 square inches of ventilation opening to outside air.

Soffit Termination

The duct termination must be located so it does not compete for air flow with exhaust fans, gas vent hoods or other air consuming devices or appliances. It must not be obstructed by rafters, insulation materials or other obstructions. The less restrictive the air supply, the better the AK-MST will perform.

It is a good practice to protect your hands and eyes during installation by wearing work gloves and safety

Exterior Wall Installation Precautions

Rain Cap Manual background

Duct Termina- tion

Manual background 40’ Max. Duct Run

Duct

glasses.

CAUTION: Do not install termination into a garage or other area that could contain flammable liquids or fumes, or into an attic space.

Exterior Wall Termination

FP1060

Fig. 13 Typical installations.

1.Remove and discard the outside air cover plate located at the center of both sides of the fireplace. Use care not to rub against the sharp edges of this opening to avoid cuts. Remove the four (4) screws

20005167

11

Image 11
Contents Do Not Discard This Manual: Retain for Future Use EWF36A FireplaceHomeowner’s Installation and Operating Manual 20005167 Table of ContentsIntroduction Vermont Castings EWF36ADrafts Safety InformationPrecautions DescriptionVermont Castings EWF36A SpecificationsEWF36A EWF36A Woodburning Fireplace20005167 Chase InstallationVermont Castings EWF36A Vermont Castings EWF36A Chimney Requirements - Offset Installations30˚ Elbow Offsets Illustration KeyThe Ten Foot Rule Planning InformationMounting the Fireplace Planning the Chimney RunInsulating Fireplace Enclosure for Cold Climates InstallationChase Installation Chimney SupportsEB1 Receptacle Hookup Straight-UpChimney InstallationOffset Installation FramingFraming the Ceiling Hole Positioning, Safety Strips Securing the FireplaceCeiling Chimney Hole Possible Obstructions Cutting the HoleVermont Castings EWF36A Installation InstructionsInstallating Outside Air Kit Installation Precautions20005167 Installing the Chimney SystemVermont Castings EWF36A in the Ceiling Hole Installing the Firestop SpacerProper Firestop Spacer Installation Continue Installing Pipe to Complete RunPenetrating the Roof Install Remainder of Chimney SectionsInstall Top Housing or Termination Installing Chimney in a ChaseVermont Castings EWF36A Finish WallMantels Side Wall Protection20005167 Hearth InstallationCOMMON MATERIALS AND FACTORS Vermont Castings EWF36A20005167 Minimum Hearth Extension DimensionsVermont Castings EWF36A Minimum Wall ClearancesPrimary Air Control OperationAttach Handles EWF36A ControlsBurn Only High-QualityWood Use the Air Control SettingsThe Fan Glass DoorsVermont Castings EWF36A Starting and Maintaining a Wood FireReloading and Reviving a Wood Fire Special Tactics for Cold-ClimateHeating20005167 Remove and Store Ash SafelyVermont Castings EWF36A Inspection and Cleaning MaintenanceCleaning the Glass Adjust the Door Latch PeriodicallyInspecting the Combustor When to Suspect a Combustor ProblemRemoving, Cleaning or Replacing the Combustor How to Replace GasketsReplace Damaged Door Glass Immediately A Clean Chimney System is Safer and Works BetterThe Chimney System Replacing the Door GasketsFireplace Daily Maintenance ScheduleYearly Spring Cleaning Vermont Castings EWF36A20005167 Chimney ComponentsVermont Castings EWF36A Description EWF36A FireplaceVermont Castings EWF36A 20005167Description EWF36A Fireplace continuedVermont Castings EWF36A 20005167Screen Kit Optional AccessoriesFan Kit Trim Kits20005167 Vermont Castings EWF36A20005167 WarrantyLimited 3 Year Warranty 149 Cleveland Drive • Paris, Kentucky MHSC