MHP Operation, Attach Handles, EWF36A Controls, Primary Air Control, The Damper, 20005167

Page 18
Operation

Vermont Castings EWF36A

Operation

Attach Handles

The fallaway handles are used to open and close the front doors. Remove after each use so they will not get hot. Keep in convenient location for each use. (Fig. 27)

Assemble the primary air control and damper handles by passing the 3³⁄₈” screw through the ceramic shaft and into the bright metal hub. Tighten carefully until snug. Do not overtighten. Ceramic handle could crack.

(Fig. 28)

Attach HandlesEWF36A Controls Steel Handle

Fallaway Handle

 

FP1397

Fig. 27

Insert fallaway handles into door handle stubs.

Metal Hub

Ceramic Shaft

Screw

FP1396

Fig. 28 Assemble primary air control and damper handles.

EWF36A Controls

Three controls regulate the performance of the EW- F36A fireplace: A primary air control supplies oxy- gen for the fire, the damper directs air flow within the fireplace and a variable-speed fan control, or rheostat, regulates the warm air flow into the room. (Fig. 29)

Primary Air Control

A single air control regulates the amount of heat the fire will produce and how long it will burn.

 

Primary Air Control

Damper

 

 

FP1203

Fig. 29

EWF36A controls.

 

The primary air control is located in the upper left corner of the unit. (Fig. 27) It is the primary source of air for starting, maintaining, and reviving the fire.

Generally, more air entering the fireplace makes the fire burn hotter and faster, while less air prolongs the burn.

The air supply is open to the maximum when the control lever is rotated clockwise, and closed when rotated counterclockwise. To vary the burn rate, adjust the con- trol to the desired position in between these extremes; opening the primary air control makes the unit burn hotter. Closing the control slows the unit down. You may adjust to any position you desire.

The Damper

The damper directs air flow within the fireplace.

The damper is operated by moving the lever located in the upper right corner of the unit. It has two posi- tions: Open to start or revive the fire and closed, for normal operation and to control burn rate. The damper is open when the lever is fully rotated counterclockwise and pulled out and closed when pushed in. When the damper is in the open position, with the lever pulled out, and rotated fully in the clockwise direction, the handle can ‘telescope’ back without closing the damper or any damper movement. There are no intermediate settings for the damper.

NOTE: Full clockwise or counterclockwise movement of the damper handle is approximately 50°.

NOTE: Always open the damper before opening the doors. Close damper to set burn rate.

18

20005167

Image 18
Contents EWF36A Fireplace Homeowner’s Installation and Operating ManualDo Not Discard This Manual: Retain for Future Use Vermont Castings EWF36A Table of ContentsIntroduction 20005167Description Safety InformationPrecautions DraftsEWF36A Woodburning Fireplace SpecificationsEWF36A Vermont Castings EWF36AChase Installation Vermont Castings EWF36A20005167 Illustration Key Chimney Requirements - Offset Installations30˚ Elbow Offsets Vermont Castings EWF36APlanning the Chimney Run Planning InformationMounting the Fireplace The Ten Foot RuleChimney Supports InstallationChase Installation Insulating Fireplace Enclosure for Cold ClimatesFraming Straight-UpChimney InstallationOffset Installation EB1 Receptacle HookupCutting the Hole Positioning, Safety Strips Securing the FireplaceCeiling Chimney Hole Possible Obstructions Framing the Ceiling HoleInstallation Precautions Installation InstructionsInstallating Outside Air Kit Vermont Castings EWF36AInstalling the Chimney System Vermont Castings EWF36A20005167 Continue Installing Pipe to Complete Run Installing the Firestop SpacerProper Firestop Spacer Installation in the Ceiling HoleInstalling Chimney in a Chase Install Remainder of Chimney SectionsInstall Top Housing or Termination Penetrating the RoofSide Wall Protection Finish WallMantels Vermont Castings EWF36AVermont Castings EWF36A Hearth InstallationCOMMON MATERIALS AND FACTORS 20005167Minimum Wall Clearances Minimum Hearth Extension DimensionsVermont Castings EWF36A 20005167EWF36A Controls OperationAttach Handles Primary Air ControlGlass Doors Use the Air Control SettingsThe Fan Burn Only High-QualityWoodSpecial Tactics for Cold-ClimateHeating Starting and Maintaining a Wood FireReloading and Reviving a Wood Fire Vermont Castings EWF36ARemove and Store Ash Safely Vermont Castings EWF36A20005167 Adjust the Door Latch Periodically MaintenanceCleaning the Glass Inspection and CleaningHow to Replace Gaskets When to Suspect a Combustor ProblemRemoving, Cleaning or Replacing the Combustor Inspecting the CombustorReplacing the Door Gaskets A Clean Chimney System is Safer and Works BetterThe Chimney System Replace Damaged Door Glass ImmediatelyVermont Castings EWF36A Maintenance ScheduleYearly Spring Cleaning Fireplace DailyChimney Components Vermont Castings EWF36A20005167 20005167 EWF36A FireplaceVermont Castings EWF36A Description20005167 EWF36A Fireplace continuedVermont Castings EWF36A DescriptionTrim Kits Optional AccessoriesFan Kit Screen KitVermont Castings EWF36A 20005167Warranty Limited 3 Year Warranty20005167 MHSC 149 Cleveland Drive • Paris, Kentucky