MHP manual Finish Wall, Mantels, Side Wall Protection, Vermont Castings EWF36A, 20005167

Page 15
Finish Wall

Finish Wall

Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12” (305

mm)above the firebox grille opening. Do not install a mantel face plate less than 6” (159 mm) from top of grille opening. (Fig. 20) If a combustible material is used below a flat mantel shelf, consult your local build- ing codes for minimum clearance from top of fireplace opening to bottom of mantel shelf.

All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 21 and 25)

NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installation).

 

 

Vermont Castings EWF36A

 

 

 

 

 

Combustiible

12"

 

 

 

Mantel and

(305mm)

 

 

Trim

 

Finished Wall

Max.

 

 

 

 

 

 

156O"

Header

(38mm)

Standoff

12"

(305mm)

Noncombustible

Min.

Material

 

6"

 

(159mm)

Brick Ledge

Min.

 

GrilleOpening

FP1398

Fireplace Front

Fig. 22 Combustible mantel minimum opening.

Mantel Shelf

Side View

See mantel drawing for

Finished Wall

2 x 4 Stud

shelf-to-grille dimension

Noncombustible Finish Mate-

Standoff

rial Only in this Area

 

Brick Ledge

 

Cast Front

Top View

Fireplace

 

Front (Steel)

2 x 4 Stud

 

156O"

*

Ref.

** Mantels

Side Wall Protection Combustible materials are permitted within a shaded area shown in Figure 26 titled Minimum Wall Clearances

 

 

 

 

 

 

 

1” (25mm)

 

 

 

 

FP1200

Must be sealed with

noncombustible material

Fig. 21 Finishing materials placement.

Mantels

* 12” (305mm) from top of grille opening. ** 6” from top of grille opening.

Fig. 23 Combustible mantel clearances.

Side Wall Protection

MA81

The height that a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if fitted) and the fireplace.

For the correct mounting heights and widths, refer to Figures 22 and 23. When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent discoloration.

Adjacent combustible side walls that are within mini- mum dimensions shown in Figure 25 of the fireplace opening must be protected with MHSC Wall Shield Model SP40 or a specifically built wall shield described in Figure 20.

The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

20005167

15

Image 15
Contents EWF36A Fireplace Homeowner’s Installation and Operating ManualDo Not Discard This Manual: Retain for Future Use 20005167 Table of ContentsIntroduction Vermont Castings EWF36ADrafts Safety InformationPrecautions DescriptionVermont Castings EWF36A SpecificationsEWF36A EWF36A Woodburning FireplaceChase Installation Vermont Castings EWF36A20005167 Vermont Castings EWF36A Chimney Requirements - Offset Installations30˚ Elbow Offsets Illustration KeyThe Ten Foot Rule Planning InformationMounting the Fireplace Planning the Chimney RunInsulating Fireplace Enclosure for Cold Climates InstallationChase Installation Chimney SupportsEB1 Receptacle Hookup Straight-UpChimney InstallationOffset Installation FramingFraming the Ceiling Hole Positioning, Safety Strips Securing the FireplaceCeiling Chimney Hole Possible Obstructions Cutting the HoleVermont Castings EWF36A Installation InstructionsInstallating Outside Air Kit Installation PrecautionsInstalling the Chimney System Vermont Castings EWF36A20005167 in the Ceiling Hole Installing the Firestop SpacerProper Firestop Spacer Installation Continue Installing Pipe to Complete RunPenetrating the Roof Install Remainder of Chimney SectionsInstall Top Housing or Termination Installing Chimney in a ChaseVermont Castings EWF36A Finish WallMantels Side Wall Protection20005167 Hearth InstallationCOMMON MATERIALS AND FACTORS Vermont Castings EWF36A20005167 Minimum Hearth Extension DimensionsVermont Castings EWF36A Minimum Wall ClearancesPrimary Air Control OperationAttach Handles EWF36A ControlsBurn Only High-QualityWood Use the Air Control SettingsThe Fan Glass DoorsVermont Castings EWF36A Starting and Maintaining a Wood FireReloading and Reviving a Wood Fire Special Tactics for Cold-ClimateHeatingRemove and Store Ash Safely Vermont Castings EWF36A20005167 Inspection and Cleaning MaintenanceCleaning the Glass Adjust the Door Latch PeriodicallyInspecting the Combustor When to Suspect a Combustor ProblemRemoving, Cleaning or Replacing the Combustor How to Replace GasketsReplace Damaged Door Glass Immediately A Clean Chimney System is Safer and Works BetterThe Chimney System Replacing the Door GasketsFireplace Daily Maintenance ScheduleYearly Spring Cleaning Vermont Castings EWF36AChimney Components Vermont Castings EWF36A20005167 Description EWF36A FireplaceVermont Castings EWF36A 20005167Description EWF36A Fireplace continuedVermont Castings EWF36A 20005167Screen Kit Optional AccessoriesFan Kit Trim Kits20005167 Vermont Castings EWF36AWarranty Limited 3 Year Warranty20005167 149 Cleveland Drive • Paris, Kentucky MHSC