Regency P131-NG, P121LC-NG, P121RC-NG, P121-NG Vertical Termination, Where the flue will pene

Page 20

INSTALLATION

Diagram 3

to ensure that the termination is not recessed into the siding.

7)Before connecting the horizontal run of flue pipe to the flue termination, slide the Wall Thimble (Part # 942) over the flue pipe.

8)Slide the appliance and flue assembly to- wards the wall carefully inserting the flue pipe into the flue cap assembly. It is impor- tant that the flue pipe extends into the flue cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Se- cure the connection between the flue pipe and the flue cap by attaching the two sheet metal strips extending from the flue cap assembly into the outer wall of the flue pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 4.

9)Install wall thimble in the center of the 10" square and attach with wood screws (Di- agram 5).

Diagram 4

Diagram 5

VERTICAL

TERMINATION

1) Maintain the 1-1/4" clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfac- es. Do not pack air spaces with insulation. Check pages 17-19 for the maximum vertical rise of the flueing system and the maximum horizontal offset limitations.

2) Set the gas appliance in

 

its desired location. Drop

 

a plumb bob down from

 

the ceiling to the position

 

of the appliance flue exit,

 

and mark the location

Diagram 1

where the flue will pene-

trate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the flue will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will

obstruct the flueing system. You may wish

to relocate the appliance or to

offset, as shown in Dia-

gram 2 to avoid cutting load bearing mem- bers.

Diagram 2

Note: Apply sealant "Mill-Pac" to inner pipe and high temperature sili- cone sealant to outer pipe on eve- ry twist-lock joint.

3)A Firestop spacer must be installed in the floor or ceiling of every level. To install the Firestop spacer in a flat ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the firestop.

Diagram 3

4)Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.

5)Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to com- bustibles of 1-1/4". Slip the flashing under the shingles (shingles should overlap half the flashing) as per Diagram 4.

Diagram 4: The upper half of the flashing is installed under the roofing material and not nailed down until the chimney is installed.

This allows for small adjustments.

6)Continue to assemble pipe lengths.

Note: If an offset is necessary in the attic to avoid obstructions, it is impor- tant to support the flue pipe every 3 feet, to avoid excessive stress on the elbows, and possible sep- aration. Wall straps are available for this purpose (Diagram 2).

Galvanized pipe is desirable above the roof- line due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the flue cap meets theminimumheightrequirementsspecifiedin Diagram 5 or local codes. Note that for steep

Diagram 5

Roof Pitch

Minimum Vent Height

 

Feet

Meters

flat to 7/12

2

0.61

over 7/12 to 8/12

2

0.61

over 8/12 to 9/12

2

0.61

over 9/12 to 10/12

2.5

0.76

over 10/12 to 11/12

3.25

0.99

over 11/12 to 12/12

4

1.22

over 12/12 to 14/12

5

1.52

over 14/12 to 16/12

6

1.83

over 16/12 to 18/12

7

2.13

over 18/12 to 20/12

7.5

2.29

over 20/12 to 21/12

8

2.44

20

Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

Image 20
Contents Manual Please Keep These Instructions For Future ReferenceCongratulations To the New OwnerTable of Contents Safety Label Installation General Safety InformationInstallation Checklist Save These InstructionsSpecifications P121 See Thru P131 PierP121LC Left Corner Unit P121RC Right Corner Unit Locating Your GAS Fireplace Clearances Combustible MantelsP121LC Corner Unit P131 Pier P121RC Corner Unit P121 See Thru Framing DimensionsFraming and Finishing Unit Assembly Prior to Installation Top Standoff AssemblyFacing & Finishing Requirements Flueing IntroductionExterior Flue Termination Locations Clearance k in mmFlueing Arrangement Horizontal Terminations Simpson DURA-VENT Flueing Simpson DURA-VENT Flueing Components ListFlueing Arrangements Horizontal Terminations Simpson DURA-VENT Direct Vent GS System LPG & NGHorizontal Flueing with Two 2 90o Elbows Horizontal Flueing with Three 3 90o ElbowsFlueing Arrangements Vertical Terminations Vertical Flueing with Two 2 90o Elbows Vertical Flueing with Three 3 90o ElbowsHorizontal Installations Vent GS systemWhere the flue will pene Vertical TerminationFor Regency AstroCapTM Direct Flue System Flex Installation ProceduresOffset Chart Burner Orifice Pilot Adjustment GAS Line InstallationGAS Pipe Pressure Testing P121/P121LC/P121RC/P131-NG System DataLOG Installation 3-digit numbers ie are molded into the rear of each log327 Glass Door Removal Finishing Trim Louvers & Grills Slide Trim into Slot Push trim tight against magnetRemote Control Thermostat Wire TableWiring Diagram Terminal Block LocationOperating Instructions Copy of the Lighting Plate Instructions Maintenance InstructionsGeneral Flue Maintenance Maintenance Installing Valve Parts List P121 see Thru Main AssemblyP131 Pier Main Assembly P121RC Right Corner Main Assembly P121LC Left Corner Main Assembly P121/P121LC/P121RC/P131 Burner Assembly & LOG SET Page Warranty Warranty LifetimeConditions Exclusions

P121RC-NG, P131-NG, P121LC-NG, P121-NG specifications

The Regency P131-NG, P121LC-NG, P121RC-NG, and P121-NG are a series of advanced communication devices designed to set new standards in the realm of radio technology, especially for industrial and commercial applications. These devices are engineered to provide reliable performance, exceptional clarity, and robust features that cater to the diverse needs of users in various sectors.

One of the standout features of the Regency P131-NG and its counterparts is their enhanced communication range. Utilizing advanced digital signal processing technology, these radios ensure clear audio transmission even in challenging environments. This capability is crucial for users operating in areas with significant interference or in remote locations, where traditional radios may fail to maintain a stable connection.

The devices also boast a rugged design, tailored for durability and resistance to environmental factors. With an IP67 rating, the P131-NG series is protected against dust and can withstand immersion in water, making it ideal for outdoor use. The robust build quality ensures that these radios can endure the rigors of everyday use in industrial settings.

In terms of user interface, the P121LC-NG and P121RC-NG are equipped with intuitive controls that facilitate ease of use. The large display screen offers clear visibility of channel information and battery status, while the customizable buttons allow users to quickly access their most-used functions. Additionally, these models feature programmable channels, enabling users to tailor their communication needs effectively.

Battery life is another key characteristic of these radios. The devices are designed with energy efficiency in mind, offering extended use between charges. This is complemented by rapid charging technology, which ensures that downtime is minimized, allowing users to stay connected when it matters most.

Additionally, the inclusion of advanced security features is noteworthy. The P131-NG series incorporates encryption capabilities that safeguard sensitive communications, making them an excellent choice for organizations concerned about data security.

Overall, the Regency P131-NG, P121LC-NG, P121RC-NG, and P121-NG stand out in the crowded market of communication devices by offering a combination of superior range, robust construction, user-friendly interfaces, long battery life, and enhanced security features. These radios are poised to meet the demands of a wide array of users, from industrial workers to commercial enterprises, providing reliable communication solutions in any environment.