Weil-McLain GV90+ manual How it works, Integrated boiler control

Page 10

GV90+ gas-fired water boiler — User’s Information Manual

How it works . . .

1Integrated boiler control

The integrated boiler control (IBC) responds to signals from the room thermostat, air pressure switch, inlet water sensor and boiler limit circuit to operate the circulators, gas valve, igniter and blower. When a room thermostat calls for heat, the IBC starts the system circulator and blower.

The IBC runs the blower to purge the boiler flue passages, then turns on the igniter and lets it warm up.

After igniter warm-up, the IBC opens the gas valve, turns the igniter off, and checks for flame. The flame must come on within 4 seconds or the IBC will shut down and try the full cycle again.

When the room thermostat is satisfied, the IBC turns off the boiler components and waits for the next heat call.

The IBC indicator lights show normal sequence when the lights are on steady. When a problem occurs, the IBC flashes combinations of lights which indicate the most likely reason for the problem.

2Transformer

The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.

3Blower

The blower pulls in air and mixes it with gas from the gas valve. The blower forces this mixture into the burner for combustion inside the boiler chamber.

4Recuperator

The recuperator is a stainless steel heat exchanger that increases boiler efficiency by ex- tracting additional heat from the flue gases. Return water passes through the recuperator before entering the boiler.

5Water temperature limit switch

The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting. (The circulators will continue to run as long as there is a call for heat.)

6System circulator

The system circulator circulates water through the external (system) piping. The flow rate of the circulator is controlled by the IBC, depending on the temperature of the water entering the boiler sections. Pump must remain on boiler — do not remove.

7Bypass circulator

The IBC operates the bypass circulator to mix hot water from the boiler outlet with colder return water from the system as needed to prevent condensation of flue gases in the cast iron heat exchanger.

When the water returning to the boiler is below 140°F, the IBC regulates the bypass circulator and system circulator flow rates to raise the return water temperature up to 140°F before it enters the cast iron sections. By balancing these flow rates, the IBC can protect against condensation even if return water is as low as 60°F.

Pump must remain on boiler — do not remove.

8Air pressure switch

The air pressure switch signals the IBC, telling the control whether air is moving through the blower.

9Water temperature sensor

The water temperature sensor monitors the temperature of the water entering the boiler sections. The sensor sends this information to the IBC. The IBC determines how much to adjust the circulator flow rates to provide at least 140°F water to the cast iron heat exchanger.

10

LEGEND

aSupply to system, 1” NPT

bReturn from system, 1” NPT

cCombustion air inlet fitting — 3” PVC connection

dFlue outlet — 3”PVC connection

eGas valve — negative pressure regulated gas control

fPressure/temperature gauge

gFlueway inspection port cover

hSensor hose trap

iManual air vent

jRelief valve

kThermal fuse — a one-time fuse device that shuts boiler off if flue temperature exceeds its setpoint

mCondensate trap line — shipped loose with boiler, field installed

nCondensate drain connection — ½” PVC female

This boiler uses a negative-pressure- regulated gas valve, set for an outlet pressure approximately –0.20” water column.

DO NOT set the outlet pressure higher than factory setting.

Part number 550-142-055/0411

Image 10
Contents User’s Information Manual Please read this page first Read/useSTOP!! Read before proceeding Hazard definitionsPrevent combustion air contamination Air contamination Combustion air contaminationPerform maintenance per schedule below Start-upDaily User maintenance proceduresCheck boiler pressure/temperature gauge Check boiler areaCheck boiler interior piping MonthlyCheck venting system Periodic Test low water cutoff if installedClean vent termination & air intake screens Check condensate systemEND Season Follow boiler shutdown procedureEvery Months Oil blower motorHow it works Integrated boiler controlGV90+ Water Boiler Operating instructions Operating instructionsCommon problems and solutions Symptom Common Causes Possible CorrectionsPopping or percolating GV90+ gas-fired water boiler User’s Information Manual GV90+ gas-fired water boiler User’s Information Manual

GV90+ specifications

The Weil-McLain GV90+ is a high-efficiency gas boiler designed to meet the heating demands of residential spaces. Renowned for its reliability and superior performance, the GV90+ is ideal for home heating systems that require both efficiency and comfort.

One of the standout features of the GV90+ is its advanced condensing technology. This allows the boiler to recycle exhaust gases, extracting additional heat and maximizing energy usage. With an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 90%, the GV90+ significantly reduces energy consumption, lowering heating bills while minimizing environmental impact.

The GV90+ also boasts a versatile design that can be integrated into a variety of heating systems. It is suitable for both hydronic heating applications and combination systems that provide domestic hot water. This adaptability makes it a popular choice for homeowners looking to enhance their existing heating setup or those building new homes.

Built with durability in mind, the GV90+ features a cast aluminum heat exchanger that is not only lightweight but also highly resistant to corrosion. This construction ensures longevity and reduces maintenance needs, thereby providing peace of mind for homeowners. The boiler's compact size further facilitates installation in tight spaces, making it a convenient solution for both new installations and replacements.

The GV90+ is equipped with an intuitive control system that simplifies operation. The integrated electronic ignition removes the need for a standing pilot, enhancing safety and improving reliability. This smart control technology also allows for precise temperature management, ensuring optimal comfort without unnecessary energy consumption.

Another highlight of the GV90+ is its whisper-quiet operation. Designed to minimize noise, this boiler allows homeowners to enjoy a warm and cozy environment without disruptive sounds. Additionally, Weil-McLain has incorporated safety features such as overheat protection and vent safety switches, ensuring the system operates safely within defined parameters.

In conclusion, the Weil-McLain GV90+ sets a high standard in the residential heating market with its exceptional efficiency, innovative technologies, and robust construction. Catering to a range of heating needs, it promises homeowners reliability, comfort, and significant energy savings, making it a wise investment for any home.