Troubleshooting
Troubleshooting
WARNING:
Always disconnect all power sources before opening the SED2 Electronic Bypass Option.
Power-on Initialization Failure
(Unit Fault Condition)
During
Table 7 shows the fault codes. For example, if the basic sanity test indicator flashes three times rapidly, pauses, and then repeats, this means that there is a keypad failure.
| Table 7. Basic Sanity Test Fault Codes. |
Basic Sanity | Description |
Test Fault | |
Code/Flashes |
|
1 | |
|
|
2 | Flash Memory Failure (CRC, cyclic redundancy check) |
|
|
3 | Keypad Failure |
|
|
4 | RAM Memory Failure (not used) |
|
|
5 | EEPROM Read error |
|
|
6 | EEPROM Write Failure |
|
|
7 | Runtime Flash Failure (CRC, cyclic redundancy check) |
|
|
8 | Main Program Failed (or hangs) |
|
|
It may be possible to recover from the unit fault condition by simply attempting a power down/up of the Electronic Bypass Option. If the unit fault condition still exists, replace the Controller board.
CAUTION:
When powering down/up the Electronic Bypass Option, power down the unit, wait 5 minutes, and then power up the unit.