Maximum Motor Frequency

Startup Procedures

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1082

Maximum Motor Frequency

1.

Press

to advance to

Site Setting

 

 

 

 

0 Hz to 650 Hz

 

parameter P1082.

Default = 50 or

 

 

 

 

 

 

 

 

 

60

 

Maximum motor frequency at

2.

Press

to access the

 

 

which the motor will run

 

parameter values level.

(Default is

 

regardless of the frequency

 

 

 

determined by

 

setpoint. This value applies to

 

 

 

the setting of

 

both clockwise and

3.

Press

to advance it desired

the motor

 

counterclockwise rotation.

 

value.

 

frequency and

 

 

 

 

 

unit of

 

 

 

 

 

measurement

 

 

4.

Press

to confirm and save

DIP switches.)

 

 

 

the setting.

 

 

 

 

 

 

 

NOTE:

This value is limited internally to 200 Hz or five times the rated motor frequency (P0305). When P1300 is greater than or equal to 20 (control mode = vector control), the value displays via r0209 (maximum frequency).

P1120

Ramp-up Time

1.

Press

to advance to

Site Setting

 

 

 

 

0s to 650s

 

parameter P1120.

Default = 10

 

 

 

 

 

 

2.

Press

to access the

Typical fan =

 

 

 

parameter values level.

120s

 

 

3.

Press

to advance it desired

Typical pump =

 

 

30s

 

 

 

value.

 

 

 

 

4.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTES:

1. Setting the ramp-up time too short can cause the SED2 to trip (F0001 over current, F0002 over voltage, or F0003 under voltage).

2. If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum SED2 performance by setting ramp time (P1120 and P1121) slightly shorter than those of the PLC.