Startup Procedures

Additional Parameter Settings

NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz).

Flying Start

Parameter

 

Description

 

 

Action

Setting/

 

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

 

P1200

Flying Start

1.

Press

to enter the SED2

Minimum = 0

 

 

 

 

 

Starts SED2 into a spinning

 

parameter mode and to display

Default = 0

 

 

r0000.

 

 

motor by rapidly changing the

 

 

 

 

 

 

 

 

 

output frequency of the SED2

 

 

 

Maximum = 6

 

until the actual motor speed is

2.

Press

to advance to

 

 

found. Then, the motor runs up

Suggested = 2

 

 

parameter P1200.

 

to setpoint using the normal

 

 

 

 

 

 

 

ramp time.

 

 

 

 

 

0

= Flying start disabled.

3.

Press

to access the

 

 

 

parameter values level.

 

 

1

= Flying start is always active,

 

 

 

 

 

start in direction of setpoint.

 

 

 

 

 

2

= Flying start is active, if power

4.

Press

to advance to

 

 

on, fault, OFF2, start in direction

 

desired setting.

 

 

of setpoint.

 

 

 

 

 

3

= Flying start is active if fault,

5.

Press

to confirm and save

 

 

OFF2, start in direction of

 

 

setpoint.

 

the setting.

 

 

4

= Flying start is always active,

 

 

 

 

 

only in direction of setpoint.

 

 

 

 

 

5

= Flying start is active if power

 

 

 

 

 

on, fault, OFF2, only in direction

 

 

 

 

 

of setpoint.

 

 

 

 

 

6

= Flying start is active if fault,

 

 

 

 

 

OFF2, only in direction of

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1. Flying start is useful for motors with high inertia loads.

2. Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the setpoint.

3. Flying start must be used in cases where the motor may still be turning (such as after a brief input power break) or can be driven by the load. Otherwise, overcurrent trips occur.

4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by reducing the values in P1203 and P1202.