Siemens 125-3208 Motor Overload Factor, Selection of Command Source, Start Command

Models: 125-3208

1 64
Download 64 pages 51.63 Kb
Page 34
Image 34
Motor Overload Factor

SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0640

Motor Overload Factor

1.

Press

to advance to

Setting =

 

 

As applicable

 

 

 

parameter P0640.

 

10% to 400%

 

 

 

 

 

 

Default = 110

 

 

 

 

 

 

Limited to the maximum SED2

2.

Press

to access the

 

 

output current rating, or to 400%

 

parameter values level.

 

 

of the rated current (P0305),

 

 

 

 

 

whichever is lower.

3.

Press

to advance to

 

 

 

 

 

NOTE:

 

desired value.

 

 

This parameter is available when

 

 

 

 

 

P0003 = 3 and

4.

Press

to confirm and save

 

 

P0010 = 1.

 

 

 

 

the setting.

 

 

 

 

 

 

 

P0700(0)**

Selection of Command Source

1.

Press

to advance to

Setting = 2

 

(Start Command)

 

 

 

 

parameter P0700.

Default = 2

 

Selects the command source as

 

 

 

 

 

 

 

 

 

follows:

2.

Press

to access the

 

 

 

 

 

0 = Factory default setting

 

parameter indexes.

 

 

 

 

 

 

 

1 = BOP (keypad)

3.

Press

to advance to index

 

 

2 = Terminal digital input

 

[0], IN000, AUTO.

 

 

 

 

 

 

 

4 = USS on BOP link (AOP)

4.

Press

to confirm index

 

 

 

selection.

 

 

 

 

 

 

 

 

5 = USS on COM link

 

 

 

 

 

6 = CB (Communications board

5.

Press

to advance to 2.

 

 

 

 

 

 

 

or module) on COM link (P1/N2)

6.

Press

to confirm and save

 

 

 

 

 

 

 

the setting.

 

 

 

 

 

 

 

NOTE:

Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2 resets all digital inputs to default settings.

** Parameters have two index settings: IN000 = Auto and IN001 = Hand.

26

Siemens Building Technologies, Inc.

Page 34
Image 34
Siemens 125-3208 operating instructions Motor Overload Factor, Selection of Command Source, Start Command