Startup Procedures

Automatic Restart

CAUTION:

Settings 2 through 7 can cause the motor to restart unexpectedly.

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1210

Automatic Restart

1.

Press

to enter the SED2

Minimum = 0

 

 

Default = 1

 

Enables SED2 restart after a

 

parameter mode and to display

 

 

Maximum:

 

 

r0000.

 

 

supply power break or after a

 

 

 

 

 

 

5=Control Board

 

fault.

 

 

 

 

 

 

 

Version 1.20

 

 

 

 

 

 

P1210 = 0, Disabled:

2.

Press

to advance to

or earlier

 

 

parameter P1210.

6=Control Board

 

Automatic restart is disabled.

 

 

 

 

 

Version 1.30

 

 

 

 

 

 

P1210 = 1, Trip reset after power on

3.

Press

to access the

7=Control Board

 

(P1211 disabled:

Version 1.40

 

The inverter will acknowledge

 

parameter values level.

Suggested:

 

(reset) faults; that is, it will reset a

 

 

 

 

 

 

 

3=Control Board

 

fault when it is re-applied. This

 

 

 

 

means the inverter must be fully

4.

Press

to advance to

Version 1.20

 

powered down, a brownout is not

 

desired setting.

or earlier

 

sufficient. The inverter will not run

 

6=Control Board

 

 

 

 

 

until the ON command has been

 

 

 

Version 1.30

 

toggled.

5.

Press

to confirm and save

7=Control Board

 

P1210 = 2, Restart after supply

Version 1.40

 

 

the setting.

 

power blackout (P1211 disabled):

 

 

 

 

 

The inverter will acknowledge the

 

 

 

 

 

fault F0003 at power on after

 

 

 

 

 

blackout and will restart the drive.

 

 

 

 

 

It is necessary that the ON

 

 

 

 

 

command is wired via digital input

 

 

 

 

 

(DIN).

 

 

 

 

 

P1210 = 3, Restart after brownout or

 

 

 

 

 

fault (P1211 enabled):

 

 

 

 

 

For these settings it is

 

 

 

 

 

fundamental that the drive only

 

 

 

 

 

restarts if it has been in a RUN

 

 

 

 

 

state at the time of the faults

 

 

 

 

 

(F0003, etc.). The inverter will

 

 

 

 

 

acknowledge the fault and will

 

 

 

 

 

restart the drive after a blackout

 

 

 

 

 

or brownwout. It is necessary that

 

 

 

 

 

the ON command is wired via

 

 

 

 

 

digital input (DIN).

 

 

 

 

 

 

 

 

 

 